Eaton Powerware 5130 User manual - page 70
Summary of Powerware 5130
Page 1
Powerware series eaton 5130 rack/tower ups 1000–3000 va user's guide ®.
Page 2
Requesting a declaration of conformity units that are labeled with a ce mark comply with the following harmonized standards and eu directives: s harmonized standards: en 62040-1-1 and en 62040-2; iec 60950-1 s eu directives: 73/23/eec, council directive on equipment designed for use within certain v...
Page 3: Class A Emc Statements
Class a emc statements (low-voltage models) fcc part 15 note this equipment has been tested and found to comply with the limits for a class a digital device, pursuant to part 15 of the fcc rules. These limits are designed to provide reasonable protection against harmful interference when the equipme...
Page 4: Special Symbols
Special symbols the following are examples of symbols used on the ups or accessories to alert you to important information: risk of electric shock - observe the warning associated with the risk of electric shock symbol. Caution: refer to operator's manual - refer to your operator's manual for additi...
Page 5
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality i table of contents 1 introduction 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 safety warnings 3 . . . . . . . . . . . . . . . ...
Page 6
Table of contents eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality ii replacing batteries 48 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . How to replace internal...
Page 7
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 1 chapter 1 introduction the eaton ® 5130 uninterruptible power system (ups) protects your sensitive electronic equipment from basic power problems such as power failures, power sags, power surges, bro...
Page 8
Introduction eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 2 providing outstanding performance and reliability, the eaton 5130's unique benefits include: s hours of extended runtime with up to four ebms. S start‐on‐battery capability for powering ...
Page 9: Save These Instructions
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 3 chapter 2 safety warnings important safety instructions save these instructions this manual contains important instructions that you should follow during installation and maintenance of the ups and b...
Page 10: Sikkerhedsanvisninger
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 4 c a u t i o n s batteries can present a risk of electrical shock or burn from high short-circuit current. Observe proper precautions. Servicing should be performed by qualified servic...
Page 11: Bewaar Deze Instructies
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 5 a d v a r s e l s batterierne kan give risiko for elektrisk stød eller brandsår forårsaget af høj kortslutningsstrøm. Overhold gældende forsigtighedsregler. Servicering skal udføres a...
Page 12
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 6 s teneinde de kans op brand of elektrische schok te verminderen dient deze ups in een gebouw met temperatuur‐ en vochtigheidregeling te worden geïnstalleerd, waar geen geleidende vero...
Page 13: Tarkeita Turvaohjeita
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 7 tarkeita turvaohjeita tÄrkeitÄ turvaohjeita - suomi sÄilytÄ nÄmÄ ohjeet tämä käyttöohje sisältää tärkeitä ohjeita, joita on noudatettava ups-virtalähteen ja akkujen asennuksen ja huol...
Page 14: Consignes De Sécurité
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 8 consignes de sécurité consignes de sÉcuritÉ importantes conserver ces instructions ce manuel comporte des instructions importantes que vous êtes invité à suivre lors de toute procédur...
Page 15: Sicherheitswarnungen
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 9 a t t e n t i o n ! S les batteries peuvent présenter un risque de choc électrique ou de brûlure provenant d'un courant de court-circuit haute intensité. Observez les précautions appr...
Page 16: Avvisi Di Sicurezza
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 10 s um die brand‐ oder elektroschockgefahr zu verringern, diese usv nur in gebäuden mit kontrollierter temperatur und luftfeuchtigkeit installieren, in denen keine leitenden schmutzsto...
Page 17
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 11 a v v e r t e n z a s l'ups contiene la propria fonte di energia (batterie). Le prese d'uscita possono essere sotto tensione anche quando l'ups non è collegato all'alimentazione elet...
Page 18: Gjem Disse Instruksjonene
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 12 viktig sikkerhetsinformasion viktige sikkerhetsinstruksjoner gjem disse instruksjonene denne håndboken inneholder viktige instruksjoner som du bør overholde ved montering og vedlikeh...
Page 19: Regulamentos De Segurança
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 13 f o r s i k t i g s batterier kan utgjøre en fare for elektrisk støt eller brannsår pga. Høy kortsluttingsstrøm. Treff passende forholdsregler. Service bør utføres av kvalifisert ser...
Page 20
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 14 s para reduzir o risco de incêndios ou choques elétricos, instale a ups em ambiente interno com temperatura e umidade controladas e livres de contaminadores condutíveis. A temperatur...
Page 21
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 15 Ï Ð Å Ä Ó Ï Ð Å Æ Ä Å Í È Å s äàííîì ÈÁÏ óñòàíîâëåíû ñîáñòâåííûå èñòî÷íèêè ýíåðãèè (áàòàðåè). Íà âûõîäíûõ ðîçåòêàõ ìîæåò áûòü íàïðÿæåíèå, äàæå åñëè ÈÁÏ íå ïîäêëþ÷åí ê ñåòè ïåðåìåííîã...
Page 22: Advertencias De Seguridad
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 16 advertencias de seguridad instrucciones de seguridad importantes guarde estas instrucciones este manual contiene instrucciones importantes que debe seguir durante la instalación y el...
Page 23: Säkerhetsföreskrifter
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 17 p r e c a u c i Ó n s las baterías pueden constituir un riesgo de descarga eléctrica o quemaduras por corriente alta de corto circuito. Adopte las precauciones debidas. Personal cali...
Page 24
Safety warnings eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 18 s minska risken för brand eller elektriska stötar genom att installera denna ups-enhet inomhus, där temperatur och luftfuktighet är kontrollerade och där inga ledande föroreningar fö...
Page 25: Inspecting The Equipment
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 19 chapter 3 installation this section explains: s equipment inspection s ups internal battery connection s ups setup and installation, including extended battery modules (ebms) s remote power-off (rpo...
Page 26: Checking The Accessory Kit
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 20 checking the accessory kit verify that the following additional items are included with the ups: table 1. Ups accessory kit item description ups user's guide or cd ups front cover usb c...
Page 27
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 21 the high-voltage models include the following additional items: table 2. Additional high-voltage model accessory items item description two cord-retention brackets two equipment power c...
Page 28
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 22 connecting the ups internal battery to ensure proper battery operation: 1. Verify that the ups is off and unplugged. 2. Connect the internal battery connectors by firmly pressing the co...
Page 29: Ups Setup
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 23 ups setup the eaton 5130 ups is designed for flexible configurations and can be installed in a rack or as a standalone cabinet. If you are installing the ups in a rack, continue to the ...
Page 30
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 24 installing the rail kit c a u t i o n the ups and ebm are heavy (see page 54). A minimum of two people are required to lift the cabinets into the rack. Note mounting rails are required ...
Page 31
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 25 6. Place the ups on a flat, stable surface with the front of the ups facing you. 7. Attach the supplied mounting brackets to the cabinet and secure with four m4 screws on each side (see...
Page 32
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 26 2. For one 2u cabinet, the pedestals must be installed. Continue to step 3. For one 3u cabinet, continue to “installing the ups” on page 28. For two or more cabinets, the joining bracke...
Page 33
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 27 5. Align each joining bracket with the adjacent cabinet screw holes and secure with the supplied screws (see figure 7). Note joining brackets are required for installations with two or ...
Page 34: Installing The Ups
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 28 installing the ups note do not make unauthorized changes to the ups or accessories; otherwise, damage may occur to your equipment and void your warranty. See “ups rear panels” on page 3...
Page 35
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 29 3. If you plan to install power management software, connect your computer to the usb port or rs-232 communication port using the supplied communication cable. Or figure 9. Installing a...
Page 36
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 30 5. Plug the equipment to be protected into the appropriate ups output receptacles (see page 42 for more information on load segments). See figure 10. Note do not protect laser printers ...
Page 37: Rpo and Roo Installation
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 31 rpo and roo installation the eaton 5130 includes a two-position terminal (see figure 11) that can be either left closed or configured one of two ways: s rpo: allows a remote contact to ...
Page 38
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 32 w a r n i n g the rpo/roo circuit is an iec 60950 safety extra low voltage (selv) circuit. This circuit must be separated from any hazardous voltage circuits by reinforced insulation. T...
Page 39: Ups Rear Panels
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 33 ups rear panels this section shows the rear panels of the eaton 5130 models. Usb port rs-232 port ebm battery connector power cord (15a, 5-15 plug - 1000–1500 va 20a, 5-20 plug - 2200 v...
Page 40
Installation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 34 usb port rs-232 port ebm battery connector power cord (20a, l6-20 plug) rpo/roo connector (1) l6-30 receptacle communication bay ground bonding screw ebm rj-11 connector (2) l6-20 recep...
Page 41: Turning The Ups On
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 35 chapter 4 operation this section describes: s turning the ups on and off s starting the ups on battery s initiating the self‐test s operating modes turning the ups on to turn the ups on: 1. Plug the...
Page 42: Starting The Ups On Battery
Operation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 36 starting the ups on battery note before using this feature, the ups must have been powered by utility power at least once. To turn on the ups without using utility power, press and hold th...
Page 43: Operating Modes
Operation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 37 operating modes the eaton 5130 front panel indicates the ups status through the ups indicators. Figure 17 shows the ups front panel indicators and controls. Battery charge level indicators...
Page 44
Operation eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 38 battery mode when the ups is operating during a power outage, the alarm beeps once every 10 seconds and the button, the , and indicators are on. The bar graph indicators show the level of ...
Page 45: Usb Port
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 39 chapter 5 additional ups features this section describes: s usb port s rs-232 communication port s communication card s load segments (powershare) the eaton 5130 ups includes a usb port, a rs-232 co...
Page 46
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 40 figure 20. The usb port 2. Install the lansafe power management software and usb drivers according to the instructions provided at www.Eaton.Com/powerquality..
Page 47
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 41 contact communication port (optional) when a signal is activated, the contact is closed between the common (pin 4) and the pin for the corresponding signal. Contact character...
Page 48: Load Segments (Powershare)
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 42 load segments (powershare) each ups has programmable outlets as shown in figure 22 through figure 24. During a power outage, you can keep key pieces of equipment running whil...
Page 49
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 43 customizing the ups with the ups configuration tool to customize the ups settings: 1. Download the ups configuration tool from www.Eaton.Com/powerquality. 2. Follow the on-sc...
Page 50
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 44 table 6. Voltage threshold options low-voltage model function factory setting other available settings high threshold for transfer to battery 151 vac ±3% 141–153 vac low thre...
Page 51
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 45 table 8. Ups on/off options function factory setting other available settings automatic start enabled disabled cold start enabled disabled forced shutdown enabled disabled en...
Page 52
Additional ups features eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 46.
Page 53: Ups and Battery Care
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 47 chapter 6 ups maintenance this section explains how to: s care for the ups and batteries s transport the ups s store the ups and batteries s replace the batteries s test new batteries s recycle used...
Page 54: When To Replace Batteries
Ups maintenance eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 48 storing the ups and batteries if you store the ups for a long period, recharge the battery every 6 months by plugging the ups into a power outlet. The batteries charge to 90% capacit...
Page 55
Ups maintenance eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 49 how to replace internal batteries c a u t i o n s pull the battery out onto a flat, stable surface. The battery is unsupported when you pull it out of the ups. S to ensure safety and...
Page 56
Ups maintenance eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 50 3. Unscrew and remove the metal battery cover (see figure 27). 1 2 figure 27. Removing the battery cover 4. Pull the battery block out onto a flat, stable surface (see figure 28). Se...
Page 57
Ups maintenance eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 51 how to replace extended battery modules to replace the extended battery modules (ebms): 1. Unplug the ebm cable from the ups. If additional ebms are installed, unplug the ebm cable f...
Page 58
Ups maintenance eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 52 4. Replace the ebm. See “recycling the used battery or ups” on page 52 for proper disposal. 5. For tower models only. Install the joining bracket between cabinets. 6. Plug the new eb...
Page 59
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 53 chapter 7 specifications filter transformer “avr” charger inverter battery figure 30. Block diagram table 10. Low-voltage model specifications model number power levels (rated at nominal inputs) ac ...
Page 60
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 54 table 11. High-voltage model specifications model number power levels (rated at nominal inputs) ac input output on battery power nominal voltage voltage range 1 frequency range 2 volt...
Page 61
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 55 table 12. Weights and dimensions (continued) ebm model number dimensions (wxhxd) weight pw5130n1750-ebm2u 440 86 509 mm 17.3” 3.4” 20.0” 29.1 kg (64.2 lb) pw5130n3000-ebm2u 440 86 634...
Page 62
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 56 table 14. Environmental and safety low voltage models high voltage models operating temperature 0°c to 40°c (32°f to 104°f) storage temperature -25°c to 40°c (-13°f to 104°f) relative...
Page 63
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 57 table 16. Battery runtimes (in minutes) load ups internal batteries +1 ebm +2 ebms +3 ebms +4 ebms pw5130l1000-xl2u (with pw5130n1750-ebm2u) 100 va/70w 112 440 841 1196 1530 250 va/17...
Page 64
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 58 table 16. Battery runtimes (in minutes) +4 ebms +3 ebms +2 ebms +1 ebm ups internal batteries load pw5130l3000-xl2u / pw5130l3000-xl3u / pw5130g3000-xl2u (with pw5130n3000-ebm2u or pw...
Page 65
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 59 table 16. Battery runtimes (in minutes) +4 ebms +3 ebms +2 ebms +1 ebm ups internal batteries load pw5130i2500-xl2u (with pw5130n3000-ebm2u) 250 va/225w 77 300 410 780 1064 625 va/563...
Page 66
Specifications eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 60
Page 67
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 61 chapter 8 troubleshooting this section explains: s ups alarms and conditions s service and support audible alarms and ups conditions the ups has an audible alarm feature to alert you of potential po...
Page 68
Troubleshooting eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 62 table 17. Troubleshooting guide alarm or condition possible cause action when starting the ups with the button, all the indicators turn on once, the alarm beeps once, and then indica...
Page 69: Service and Support
Troubleshooting eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 63 service and support if you have any questions or problems with the ups, call your local distributor or the help desk at one of the following telephone numbers and ask for a ups techn...
Page 70
Troubleshooting eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 64.
Page 71: Warranty (Us and Canada)
Eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 65 chapter 9 warranty two-year limited warranty with extension to three-year limited warranty (us and canada) eaton ups models: 3105, 5110, 5115, 5125, and 5130 warrantor: the warrantor for the limited...
Page 72
Warranty eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 66 what this limited warranty does not cover: this warranty does not cover any defects or damages caused by: (a) failure to properly store the product before installation, including the charge...
Page 73
Warranty eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 67 costs not related to warranty: the end-user shall be invoiced for, and shall pay for, all services not expressly provided for by the terms of this warranty, including without limitation, si...
Page 74
Warranty eaton 5130 rack/tower ups (1000–3000 va) user's guide s 164201730 rev 4 www.Eaton.Com/powerquality 68 what this guaranty does not cover: any reimbursement or repair to end-user's equipment does not include reimbursement for or restoration of any data loss. This guaranty does not cover any d...