  • Page 1

    Powerware ® 9120 user’s guide 700 va - 3000va www.Powerware.Com.

  • Page 2

    Powerware ® 9120 700, 1000, 1500, 2000 & 3000va user’s guide important notice the ups ground (earth) conductor carries leakage current from the loads in addition to any leakage current generated by the ups. This ups generates no more than 1 ma of current. To limit the total leakage current to 3.5 ma...

  • Page 3

    If you have a question customer support if you have a question or problem, table 10, troubleshooting, may help. If you need more help, please have your ups model number and serial number (on the back label) nearby, and call the eaton powerware office nearest you (see the offices section). Eaton powe...

  • Page 4: Trademarks

    1 table of contents safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 1.0 ups features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 2.0 quick startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 3.0 ...

  • Page 5: Save These Instructions!

    2 safety instructions important safety instructions! Save these instructions! This user guide contains important instructions for your powerware 9120 that must be followed during installation and maintenance of the ups and batteries. The installation and use of this product must comply with all nati...

  • Page 6

    3 fig 1. Powerware 9120 controls and indicators 1.0 ups features the powerware 9120 provides protection against power problems, including power outages, brownouts, and sudden increases in power. It also provides spike suppression and line noise fil- tering to protect your equipment. Front panel leds...

  • Page 7

    4 assem b led in taiw an u se w ith :2b at 700 612-09910-00 o u tpu t :208/220/230/240v, 50/60h z 50/60h z, 3.4/3.2/3.0/2.9a in pu t :208/220/230v/240v, m o d el n o .:06250700a in pu t :24v,25a 700va/490w p/n :06250700a fig 2. 700va and 1000va rear panel fig 3. 1500va rear panel usb port communicat...

  • Page 8

    5 fig 4. 2000va rear panel usb port communication slot communication port fan inverter shutdown connector input connector iec c14 10a network surge suppression battery connector load segment 2 2 x australian 10a load segment 1 3 x australian 10a fig 5. 3000va rear panel usb port communication slot c...

  • Page 9

    6 2.0 quick startup 1 your powerware 9120 ups has a removable power cord. Connect the power cord to the back of the unit and plug the ups into a wall outlet. The lcd backlight will illuminate and the fan will run, but no output power is available. 2 let the unit charge the battery for at least 3 hou...

  • Page 10: 3.1

    7 3.0 operation this section describes: • the ups front panel • standby mode • turning the ups on and off • diagnostic tests • starting the ups on battery 3.1 ups front panel the ups front panel indicates the ups status and also identifies potential power problems. Figure 6 shows the ups front panel...

  • Page 11: 3.2

    8 3.2 turning the ups on after the ups is connected to a power source, the fan turns on and the ups enters standby mode. To turn on the ups, press and hold the button until you hear the ups beep (approximately one second). The lcd briefly displays “on delay” and the “power on” indicator illuminates....

  • Page 12

    4.0 configuration this section describes how to reconfigure options using the configuration mode, including: input and output voltage and frequency, site wiring fault, and silencing the alarm. Note the ups has been factory-configured with default settings appropriate for most installations. User con...

  • Page 13

    10 table 1. Configuration mode parameters parameter lcd message description default settings output voltage setting o/p v setting to change the output voltage • select 208, 220, 230, or 240v for 240v models. For 240v models: you are prompted to save this setting. O/p v= 230v input voltage tolerance ...

  • Page 14

    11 table 1. Configuration mode parameters (cont.) parameter lcd message description default settings manual battery test manual bat test to initiate a manual battery test, press the ↵ ↵ button battery test twice when “manual battery test” is displayed on the lcd. During the test the lcd displays on ...

  • Page 15: 5.1

    12 5.0 additional ups features this section describes: • inverter shutdown • network transient protector • load segments • using the communication port or usb port • optional sola communication cards 5.1 inverter shutdown the powerware 9120 includes a port that allows the ups inverter to be switched...

  • Page 16: 5.4

    13 5.4 communication port to establish communication between the ups and a computer, connect your computer to the ups communication port using the supplied communication cable. When the communication cable is installed, power management software can exchange data with the ups. The software polls the...

  • Page 17: 5.7

    14 5.7 relay card this interface provides true relay contact output to peripheral devices. Outputs are user-selectable as normally open or normally closed. Table 2. Relay card (as/400) pin assignment pin number signal name definition direction 1 - isolated common to pins 2 & 3 - 2 line ok relay cont...

  • Page 18: Caution!

    15 7.0 replacing the batteries the powerware 9120 batteries are user-replaceable and can be replaced while the powerware 9120 has ac input applied and powers the loads. This means that, if necessary, you can replace the batteries while the ups is running. Before you replace the batteries, make sure ...

  • Page 19: 7.1

    16 7.1 how to replace internal batteries use the following steps to replace the internal batteries: 1. Using caution not to put stress on the lcd display cable, pull the top of the front panel forward. Release the spring latches at the bottom of the front panel and remove it, placing it to the side ...

  • Page 20

    17 8.0 specifications eaton powerware reserves the right to change specifications without prior notice. This section provides the following specifications for the powerware 9120 models: • electrical input and output • environmental and safety • weights and dimensions • battery table 4. Electrical in...

  • Page 21

    18 table 6. Environmental and safety 240v models operating temperature 0°c to 40°c 0-1500 metres above sea level 0°c to 35°c 1500-3000 metres above sea level optimal battery performance: 25°c storage temperature -15°c to 50°c relative humidity 0-95% noncondensing operating altitude up to 3,000 metre...

  • Page 22

    19 table 8. Battery configuration 700 va: (2) 12v, 9 ah internal batteries; 24 vdc 1000 va: (3) 12v, 9 ah internal batteries; 36 vdc 1500 va: (4) 12v, 9 ah internal batteries; 48 vdc 2000-3000 va: (8) 12v, 9 ah internal batteries; 96 vdc type sealed, maintenance-free, valve-regulated, lead-acid char...

  • Page 23

    20 9.0 troubleshooting if you have a question or problem, the troubleshooting table may help (see table 10). If you need assistance, phone eaton powerware service or your local eaton powerware office. Please have the model number and serial number (located on the rear of the unit) available. If the ...

  • Page 24

    21 table 10. Troubleshooting lcd message or possible cause action condition ups does not turn on. The ups is not correctly check connections to the power source. Connected to the power source. The wall outlet is faulty. Have a qualified electrician test and repair the outlet. The inverter shutdown c...

  • Page 25

    22 table 10. Troubleshooting (cont.) lcd message or possible cause action condition low battery the battery is running low. 2 minutes or less of battery power remains 2 beeps every 5 seconds. (depending on load and battery charge). Prepare for a shutdown. Save your work and turn off your equipment. ...

  • Page 26

    23 table 10. Troubleshooting (cont.) lcd message or possible cause action condition over-charge batteries are over-charged. Save your work and turn off your equipment. Constant beep. Turn off the ups. Contact your service representative. Charger failure charger has failed. Save your work and turn of...

  • Page 27: Warranty Information

    24 10. Warranty warranty information this warranty is subject to eaton power quality pty ltd (epq) standard conditions of sale, which govern all sales of products by eaton power quality pty ltd. 1. Epq products, in general, are warranted against failure due to faulty materials and/or workmanship for...

  • Page 28

    25 6. High grade batteries, designed for uninterruptible power supply (ups) applications, are supplied by epq for use with epq ups equipment. These batteries have a finite life expectancy depending on a number of variables, including rate of discharge, depth of discharge, operating temperature, etc....

  • Page 29

    Eaton power quality pty ltd 13 healey road dandenong vic 3175 australia affix post age st amp.

  • Page 30

    6.Please specify the equipment being protected by your powerware ups? Brand........................................Model .................................. Operating system ........................ . 7.How would you classify your type of business? Retail wholesale/distribution manufacturing t elecom...

  • Page 31

    28 eaton powerware australia/new zealand offices head office - sydney eaton power quality pty ltd abn 82 054 056 709 10 kent road mascot nsw 2020 phone: 61-2-9693 9366 fax: 61-2-8338 1159 national service and repair centre 1300 303 059 web site: www.Powerware.Com.Au customer service offices adelaide...

  • Page 32

    You have purchased a ups that will provide you with many years of service, protecting your equipment from surges, sags, and blackouts. This product incorporates the highest quality standards in engineering, manufacturing and testing, and carries a 2 year warranty against defects in material and work...