Eaton Pulsar Series 1150 Installation And User Manual - 6. Appendices
34008235EN/AC - Page 19
6. Appendices
6.1 Technical specifications
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in extended frequency mode (programmable using Personal Solution-Pac software).
(3) Adjustable to 200 V (10% derating of output power) / 208 V / 220 V / 230 V / 240 V.
When the appliance is used in EU area, use an external circuit breaker in front of line with rating 16A, 250V which is
IEC/EN 60898-1 standard compliant;
When the appliance is used in America area, use an external circuit breaker in front of line with rating 20A, 250V.
This product is designed for IT power distribution system.
Evolution
650 / 650 Rack
850 / 850 Rack
1150 / 1150 Rack
1550 / 1550 Rack
Output power
650 VA /
420 W
850 VA /
600 W
1150 VA /
770 W
1550 VA /
1100 W
AC input power
◗
Rated input voltage
◗
Input-voltage range
◗
50 Hz input-frequency range
◗
60 Hz input-frequency range
Single phase 220~240 V
160 V to 294 V
(1)
47 Hz to 70 Hz
(2)
56.5 Hz to 70 Hz
(2)
Output on battery power
◗
Voltage
◗
Frequency
230 V (+6% / -10%)
(3)
50/60 Hz ±0.1 Hz
Battery (sealed lead acid,
maintenance free)
◗
Tower model
◗
Rack model
1 x 12 V - 9 Ah
2 x 6 V - 9 Ah
2 x 12 V - 7.2 Ah
4 x 6 V - 7.2 Ah
2 x 12 V - 9 Ah
4 x 6 V - 9 Ah
3 x 12 V - 9 Ah
6 x 6 V - 9 Ah
Environment
◗
Operating temperature range
◗
Storage temperature range
◗
Humidity
◗
Noise level
0 to 35°C
0 to 40°C
-25°C to 40°C
20 to 90% (without condensation)
< 40 dbA
Transformer
AVR
Filter
Charger
Inverter
Battery