Eberle EM 524 89 Assembly And Operating Instructions Manual - Alarm Messages:

Manual is about: Ice Detector

Summary of EM 524 89

  • Page 1

    Assembly and operating instructions ice detector em 524 89 for open spaces and gutter heating k 468 931 003 375-2 box 64, 123 22 farsta, sweden phone:+46(0)8 683 33 00 fax:+46[0]8 605 81 746 visit us at www.Wahlstrom.Se.

  • Page 2: Contents

    Contents application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 3 controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ....

  • Page 3: Instructions:

    Instructions: the ice detector is installed for the fully automatic electric heating of open spaces, garage drives, stairs, ramps, flat roofs and gutters. Unlike manually controlled (touch- dependent) or thermostatically controlled (only temperature dependent) systems, the heating will only be switc...

  • Page 4: Ground/roof:

    “measured value” mode = normal operation: the current measured values are displayed in this mode: ground/roof: from –45 to +78°c (–49 to 172.4 °f) air: from –45 to +78°c (–49 to 172.4 °f) note 1* moisture: from 0 to 9 heating: off and on the display changes every three seconds between ground/roof an...

  • Page 5: Menu Mode

    5 menu mode in this mode the menu text is displayed in the top line of the menu text and the set value in the bottom line. If you press the top button (menu) the menu moves on one. If you press the middle button (value) the value of this menu item, shown in the bottom line, is advanced. If you press...

  • Page 6: Menu Items:

    Menu items: application: range: ground, roof default value: ground the application (gutter or ground)is selected with this setting. The application selected will be retained when you revert to the default program. Range: range: –5 … –20 °c (23 …–4 °f), off default value: –10 °c lower temperature lim...

  • Page 7: Base Temp

    Operation: range: automatic, permanent default value: automatic with this function, you can switch the heating on continuously, irrespective of the set temperatures and humidity. The heating remains switched on during an alarm. Sensor heater: range: auto, on default value: on in automatic mode the s...

  • Page 8: Alarm Messages:

    Alarm messages: in the event of an alarm, the display starts flashing at one second intervals. The alarm relay closing contact (terminals 5 and 6) closes. The word “alarm” appears on the top line. At the same time, the cause of the alarm is displayed on the bottom line. This alarm display appears in...

  • Page 9: Operating:

    Operating: if the temperature set in the ice detector falls below the predetermined value and if the set humidity is exceeded at the same time, the heating will be switched on by means of the heater relay and the terminals 8 and 9 (see connection diagram). If one of these conditions is not fulfilled...

  • Page 10

    Ice and snow sensor (5-core)esf 524 001 or esf 524 011 the sensor is equipped with an ntc resistor to measure the sensor surface temperature, a heating coil and two metal rings as humidity sensors. Nominal voltage: 8v- power consumption: approx. 7w surface temperature: approx. 4 °c (39.2 °f) connect...

  • Page 11: Or Tff 524 012 (4 Core)

    Combined temperature and moisture sensor tff 524 002 or tff 524 012 (4 core) the combined sensor is equipped with an ntc resistor for ground temperature measurement and two metal rings are installed as moisture sensors. This sensor is, however, not independently heated. Connecting lead: 4 x 0.5 mm; ...

  • Page 12: Sensor Assembly

    Sensor assembly the ice and snow sensor esf 524 001 (5 core) is assembled as follows. The snow and ice sensor is mounted outside the heated area (see figs. 2 and 3 on page 16). The sensor must be assembled so that it is directly exposed to the weather conditions (snow, rain, melt water (see figs. 4 ...

  • Page 13

    The combined temperature and moisture sensors tff 524 002 (4 core) are assembled as follows. The combined sensor is installed inside the heated area (see figs. 2 and 3 on page 16) as it must monitor the ground temperature of the heated surface at all times (whether it is switched on or it is switche...

  • Page 14

    Sensor assembly in fag 524 111 sensor housing determining where to fit the sensor/sensor housing is extremely important to ensure that the system works as well as it can. The sensor must be fitted where it first becomes smooth or where it is smooth for the longest length. The esf 524 001/011 sensor ...

  • Page 15

    Installation of the sensor in the fag 524 111 sensor housing a protective metal pipe running up to the sensor housing should be provided at the construction site for the connection cable. If the sensor is to be run over an appropriate underlay (foundation or base plate) must be provided so that the ...

  • Page 16: Installation Examples:

    Installation examples: fig.2 fig.3 16.

  • Page 17

    Fig.4 fig.5 fig.6 17.

  • Page 18

    Ice and snow sensor esd 524 003 (5-core) the sensor is equipped with an ntc resistor for temperature measurement, a heating coil and two small metal pipes as moisture sensors. Nominal voltage: 8 v- power consumption: 3 w surface temperature: approx. 4 °c (39.2 °f) connecting lead: 5 x 0.25 mm; 4 m p...

  • Page 19

    Tfd 524 004 (2 core)temperature sensor the temperature sensor is composed of a cable with a compound-filled cap on top and inbuilt ntc resistor. Connecting lead: 2 x 0.5 mm; 4 m pvc (2 x 20 gauge x 13 ft.) ambient temperature: –30 … 80 °c (–22 … 176 °f) sensor characteristics – sensor disconnected f...

  • Page 20: Assembly:

    Assembly: the esf 524 003 (5 core)ice and snow sensor is assembled as follows. Where possible, assemble the ice and snow sensor near to the downpipe or waste pipe (lowest point) of the gutter between the heating cables (do not let them come into contact with one another). The sensor is to be fitted ...

  • Page 21: Setting Desired Values

    Setting desired values range setting the range menu item is called up with the menu button and the lowest temperature limit is set with the value button. This temperature value specifies the lower operating temperature limit. The upper working temperature is fixed at +6 °c (42.8 °f). Up to this temp...

  • Page 22: Operating Modes

    Operating modes 1. Default settings: menu value remarks: application ground 2 range –10 °c temperature +3 °c moisture 3 base temp off post purge 20 minutes operation automatic sensor heater on standard program on temp unit °c 2 language german 2 2: during the initial installation the default value f...

  • Page 23

    3. Manual operation menu value operation permanent the heating is switched on immediately and can only be switched off using this menu item. With manual operation the heating remains switched on even during alarms. 4. Operating without moisture influence menu value temperature +3 °c (37.5°f) moistur...

  • Page 24: Maintenance

    Maintenance ensure that the surfaces of the esf 524 001/011, tff 524 002/012 and esd 524 003 sensors are kept clean at all times. A regular inspection of the control unit is recommended so that any alarm messages can be recognised and rectified in a timely fashion. Only then will it be possible for ...

  • Page 25

    Connection diagram for em 524 89 connection diagram 1: ice detector connection with esf 524 001/011 and tff 524 002/012 sensors for open space heating. Note: instead of the default 82 k Ω resistor a separate tfd 524 004 temperature sensor can be installed. This sensor is used to detect a drop in tem...

  • Page 26

    Connection diagram 2: ice detector connection with esd 524 003 and tfd 524 004 sensors for gutter heating. Note: instead of the default 82 k Ω resistor a separate tfd 524004 temperature sensor can be installed. This sensor is used to detect a drop in temperature and the air temperature thus measured...

  • Page 27

    Connection diagram 3: ice detector connection with esf 524 001 and tfd 524 004 sensors. Open space without second humidity measuring point (max. Open space. 5m 2 ). Alarm- unit ice and snow sensor esf 524 001 / 011 16 17 18 19 10 11 12 13 14 15 x2 20 21 x3 temperature sensor tfd 524 004 82 k* ws gr ...

  • Page 28: Technical Data

    Technical data type em 524 89 edv no. 0524 89 144 100 operating voltage: ac 230 v ±10 %, 50/60 hz power consumption: ≤ 15 va ambient temperature: –20 … + 50 °c (–4 … 122 °f) storage temperature: –20 … + 70 °c (–4 … 158 °f) desired value range range: lower temperature limit –5 ... –20 °c (3 … –4 °f) ...

  • Page 29

    Display* lcd display: 2-row 16-digit temperatures: –45 … + 78 °c (–49 … 172 °f) humidity: 0 … 9 heating: on, off fault status: fault sensor parameters: values and selection *) below 0°c (32 °f) the correct reading of the lcd display cannot be guaranteed, the operation of the equipment, however, will...

  • Page 30

    Brief operating instructions for ice detector em 524 89 for open space and gutter heating application: the ice detector is used for the fully automatic electric heating of open spaces, garage drives, stairs, ramps, flat roofs and gutters. Unlike manually-controlled (touch dependent) or thermostatica...

  • Page 31

    31 use the menu button to select all of the menu items in order. The selected menu item is shown in the top display line. The bottom display line shows the current value for this menu item and “active”. For example: temperature 3 °c active the desired value can be changed with the value button. When...