Mounting and
Operating Instructions
for room thermostats
RTR-E 8…
General Notes
The device may only be opened and installed accor-
ding to the circuit diagram on the device or these
instructions by a qualified electrician. The existing
safety regulations must be observed. Appropriate
installation measures must be taken to achieve the re-
quirementsofprotectionclassII.Thisindependently
mountable electromechanical device is designed
for controlling the temperature in dry and enclosed
rooms only under normal conditions. The device
confirms to EN 60730, it works according operating
principle 1C.
When commissioning the room temperature regula-
tor,pleasenotethatthebimetallicelementrequiresa
certain time to adjust itself to the room temperature.
Immediately after installation the switch-point will
deviate from the room temperature. Switch-point ac-
curacy is established only after about 1-2 hours ope-
ration.
Field of application
The room temperature controller is intended for the
control of temperature within enclosed dry areas with
typical surrounding.
Mounting
Location:
•Thepreferredmountinglocationisonaninnerwall
opposite the heating source
radiator
radiator
Room
Temperature Controller
•Mounting height: approximately1,5mabovefloor
level.
•Avoidouterwallsanddraftsfromwindowsanddoors.
•Ensurethatthenormalconvectioncurrentsofthe
room can reach the controller unimpeded. The
controller should not be mounted on the wall within
shelv ing or behind curtains or similar coverings.
•Externalheathasanadverseeffectoncontrolaccu-
racy. Avoid direct sunshine and the immediate vici-
nity of televisions, radios, heating appliances, lamps,
chimneys and heating pipes.
•Iffittedinamultiwaycarrier,thecontrollershould
always be put in the lowest position.
•Combinationwithdimmers!Ifthecontrolleranda
dimmer are being fitted in a common carrier, then a
switch or a socketoutlet must be interposed between
the controller and the dimmer, since the latter is
source of heat.
Electrical connection
Caution! De-energize the electric circuit first
Performthestepsdescribedbelow:
•Pulloffthetemperaturedial
•Releasethefixingscrew
•Removetheupperpartofthecasing
•Connectacc.tocircuitdiagram(seebottomofcasing)
Wiring diagram symbols
L
=Line
N
=Neutral
N
=Connectionfortimeswitchsignal
for temperature reduction
U
=LoadconnectionHeating
P
=LoadconnectionCooling
RF
=Resistanceforthermalfeedback
TA
=Resistancefornighttimereduction
of room temperature.
Lampred:
Mainson
Lampred:
Callforheat
Lampgreen: Temperaturesetbackon
Technical Data
Relative humidity
max.95%without
condensation
Rated impulse voltage
4KV
Pollutiondegree
2
Ball pressure test temperature
75±2°C
VoltageandCurrentforthepurposes
of interfernce measurements
230V;0.1A
Energy class
(acc.EU811/2013,812/2013,813/2013,
814/2013)
I=1%
Limiting the temperature
setting range
The room temperature controller is factory-set to its
fulladjustmentrangeof5to30°C(Fig.1).
There are two adjustment rings on the ad justing knob.
These enable the temperature adjustment range to be
limited as desired
Fig.1
Limitingthetemperaturesettingrange
Scale for temperature setting with
codemarks
P
=~ 5°C
=~20°C
2
=~10°C
5
=~25°C
3
=~15°C
6
=~30°C
Symbols
OFF
ON
É
Continuous day-time setting
ë
Continuous night-time setting
N
Automatic (nighttime reduction remotely
controllableviatimeswitch)
Ü
Auxiliary heating
This product should not be disposed of
with household waste.
Please recycle the products where
facilities for electronic waste exist.
Check with your local authorities for recy-
cling advice.
RTR-E 8001 / RTR-E 8002
RTR-E 8011 / RTR-E 8012
RTR-E 8015
RTR-E 8021 / RTR-E 8022
RTR-E 8031 / RTR-E 8032
RTR-E 8041
RTR-E 8051
RTR-E 8063
RTR-E 8065
RTR-E 8033
Technical data
Typ
RTR-E 8001
RTR-E 8002
RTR-E 8011
RTR-E 8012
RTR-E 8015
RTR-E 8021
RTR-E 8022
RTR-E 8031
RTR-E 8032
RTR-E 8033
RTR-E 8041
RTR-E 8051
RTR-E 8063
RTR-E 8065
Temperature range:
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
5…30°C
OperatingVoltage:
250 V~
24 V~
250 V~
24 V~
250 V~
250 V~
24 V~
250 V~
24 V~
250 V~
250 V~
250 V~
250 V~
250 V~
Switching current
(cosϕ=0,6)
UHeating
P Cooling
10 mA…10(4)A
––
10 mA…10(4 )A
––
10 mA…10(4)A
––
10 mA…10(4)A
––
10 mA…10(4)A
––
10 mA…10(4)A
––
10 mA…10(4)A
––
10 mA…10(4)A
10 mA…5(2) A
10 mA…10(4)A
10 mA…5(2) A
10 mA…10(4)A
10 mA…5(2) A
10 mA…10(4)A
––
10 mA…10(4)A
10 mA…(2) A
10 mA…10(4)A
––
10 mA…10(4)A
10 mA…5(2) A
Schaltleistung
UHeating
P Cooling
2.2 KW
––
240 W *
––
2.2 KW
––
240 W *
––
2.2 KW
––
2.2 KW
––
240 W *
––
2.2 KW
1.1 KW
240 W **
120 W **
2.2 KW
1.1 KW
2.2 KW
––
2.2 KW
1.1 KW
2.2 KW
––
2.2 KW
1.1 KW
Switching tempera-
ture differential
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0.5 K
ca.0,5 K
ca.0.5 K
ca.0.5 K
Temperature set-back ca.4 K
ca.4 K
ca.4 K
ca.4 K
ca.4 K
ca.4 K
ca.4 K
––
––
min.5 K
ca.4 K
––
––
ca.4 K
* with DC max. 100W
** with DC max. 30W