Eclipse EC-P8 Installation Manual - page 20
20
P0031-LI-02.01
6
Remote Detector Test
On: Zones with this attribute are monitored for specific activity
during the remote detector test. The detector must be
connected to the control panel using triple EOL wiring and
the detector remote test input must be connected to a panel
output programmed as “Remote Detector Test”.
Off: The zone functions as normal.
7 Momentary
Keyswitch
On: If the zone type is a keyswitch type, the operation mode is
changed to momentary.
Off: If the zone type is a keyswitch type, the operation remains as
latching mode.
Zone Bypass Options
Each zone can have one or more optional bypass attributes
programmed to control when the zone is bypassed.
Locations:
1501
to
1518
Zone 01 to 18: Zone Bypass Options.
Entry Mode:
Bit Toggle Selection (see page 16).
1
In Stay 1
On: The zone is bypassed when Stay 1 arming mode is selected.
Off: The zone is not bypassed when Stay 1 arming mode is
selected.
2
In Stay 2
On: The zone is bypassed when Stay 2 arming mode is selected.
Off: The zone is not bypassed when Stay 2 arming mode is
selected.
3
In Stay 3
On: The zone is bypassed when Stay 3 arming mode is selected.
Off: The zone is not bypassed when Stay 3 arming mode is
selected.
4 Manual
On: The zone can be bypassed by the user when arming the
system.
Off: The zone cannot be bypassed by the user.
5 Auto
Bypass
On: The zone is automatically bypassed at the end of exit mode if
the zone is still active.
Off: The zone is not bypassed at the end of exit mode, and the
system will fail to arm if the zone remains active.
6 Keyswitch
Bypass
On: The zone is bypassed when a “Bypass Key” zone type is
active and reinstated when the “Bypass Key” is secure.
Off: The zone is not bypassed when a Bypass Key is operated.
7 Cleaner
On: The zone is bypassed when a cleaner code is entered.
Off: The zone is not bypassed when the cleaner code is entered.
Zone Chime
Each zone can have an optional chime mode programmed that
allows the panel and remote keypads to generate an audible tone
when the zone is activated in the disarmed mode.
Locations:
1601
to
1618
Zone 01 to 18: Zone Chime.
Entry Mode:
Mode: Selection List (see page 15).
0 Off
The zone will not generate a chime tone.
1 Tone
1
The zone generates chime tone 1 when activated in the disarmed
mode.
2 Tone
2
The zone generates chime tone 2 when activated in the disarmed
mode.
3 Tone
3
The zone generates chime tone 3 when activated in the disarmed
mode.
Zone Soak Test
Each zone can be put on test for a programmed soak test period.
When a zone is on test it will not cause an alarm if activated, but
the system will record the failure in the event log and indicate the
fault to the user.
Locations:
1701
to
1718
Zone 01 to 18: Zone Soak Test.
Entry Mode:
Mode: Selection List (see page 15).
0 No
The zone is not on soak test.
1 Yes
The zone is on soak test.
Zone Text
Each zone can be assigned a 20 character label that is displayed
on LCD remote keypads when viewing the zone status and event
log.
Locations:
1801
to
1818
Zone 01 to 18: Zone Text.
Entry Mode:
String Edit - Text Mode (see page 18).
Zone Link
Each zone can be assigned a “Link” number, which in turn is used
to control “Link Control” output types, for details on link control,
see page 30.
Locations:
1901
to
1918
Zone 01 to 18: Zone Link.
Entry Mode:
Number Entry (see page 17).