TROUBLESHOOTING INSTRUCTIONS
For Setting and Error Lists refer to LAMTEC manual attacched.
OPERATING TROUBLE
In case of operating trouble it should be
checked whether the system is in proper
working order.
Make a check for the following:
1. Availability of fuel.
Availability of gas in the line at sufficiently
high pressure.
Availability of fuel oil in the tank (for dual
fuel burner).
Correct position of fuel selector switch.
2. Availability of electric power in the
burner system.
3. Proper functional order and setting of all
control and safety instruments such as
temperature controller, safety limiter, water
failure cut-out, electrical limit switches, etc.
If the trouble is not found to be due to any
of the above-mentioned points it will be
necessary to test the burner functions very
carefully.
Prevailing conditions:
The burner will be found to be out of
operation and in faulty and interlocked
position.
Proceed with searching for the cause of
the trouble and eliminate it. Unlock the
control box by pressing the fault eliminate
key and start the burner.
Do not press the fault eliminate key longer
than 10 seconds.
The start-up program will be initiated and
should be carefully monitored.
The possible cause of the fault may be
quickly found by reference to the fault
indicator of the control box and watching
the start-up and operating program.
APPENDIX
Control box - Display
Intent of the keys:
Reset
Load / Fault history up
Load / Fault history down
Load / Fault history down
Manual operation on / off
–
Compound
–
O
2
–
Flame intensity
–
Operating hours
Select operating modes*:
UEAN
PARA
O
2
1 )
AUTO
SPLO*
Select operating parameters
Status
load rating
setpoint
Actual value feedback
2)
Digital inputs
*
UEAN =
Monitoring processor display
PARA =
Parameterisation
1)
only, if parameter is active
AUTO =
Automatic
2)
only with Burner Control FA1
EINS =
Setting
SPLO =
Clear memory
!
Always switch off the power supply before installing or removing the control unit. Do not attempt to open or carry out repairs on
the control unit.
Refer to LAMTEC manual attacched.