ECR International R15C Installation, Operation & Maintenance Manual - page 26
• If equipped with Motorized Fresh Air Damper, and is
active with Fresh Air Switch [FAS], damper will open
with call for the indoor fan.
• If room temperature is
below
thermostat setting fan
operation continues as noted.
• If room temperature is
above
thermostat setting,
reversing valve is energized. Compressor and outdoor
fan start provided Anti-Short Cycle Timer has timed out
from initial power-up, power restoration or previous
compressor on cycle. Operation will continue until room
temperature satisfies the thermostat.
• Once room temperature falls below set point by 3º F (2º
C)compressor, outdoor fan motor and reversing valve
will de-energize.
• If FCS is set to “Off”, indoor fan continues to operate for
60 seconds after compressor stops.
• If FCS is set to “On”, indoor fan continues to operate.
• As soon as the compressor is de-energized, Anti-Short
Cycle Timer is initialized and prevents compressor from
starting again for another 180 seconds.
• While Anti-Short Cycle Timer is active, Processor Board
Trouble Code LED is set to blink a 2 flash code.
• After Anti-Short Cycle Timer expires, Processor Board
Trouble Code LED is set to blink 1 blink Trouble Code,
indicating normal operation.
NOTE:
Remote-Mount Cooling Operation depends on
features of wall-mounted thermostat. By default fan will
cycle with call for cooling.
For thermostats with
AUTO / ON
fan switch, fan will run
continuously if this is “ON” (Continuous Fan Operation).
Fan cycles with call for cooling if this is set to “AUTO”
(Cycling Fan Operation).
In cooling, units will not start if indoor air temperature is
60º F (15.5º C) or below or outdoor temperature is below
40º F (4.5º C).
R_ _C / R_ _ H; Heating Operation
• With System Switch [SS] set to “Heat”, and Fan Cycle
Switch [FCS] set to “On” (Continuous Fan Operation),
indoor fan motor will start.
• If Fan Cycle Switch [FCS] is set to “Off” (Cycling Fan
Operation), indoor fan motor will start with call for
heating from the internal thermostat [T’stat].
• If equipped with Motorized Fresh Air Damper, and is
active with Fresh Air Switch [FAS], damper opens with
call for indoor fan.
• If room temperature is
above
thermostat setting fan
operation continues as noted above.
• If room temperature is
below
thermostat setting,
action of the unit will depend on outdoor temperature
and freeze sensor status.
NOTE:
Remote-Mount Heating Operation depends on
features of wall-mounted thermostat. By default fan will
cycle with call for Heating.
For thermostats with AUTO / ON fan switch, fan runs
continuously if this is “ON” (Continuous Fan Operation).
Fan cycles with call for heating if this is set to “AUTO”
(Cycling Fan Operation).
A. R_ _H; Mechanical Heating “Heat Pump"
• If outdoor coil temperature remains above 25º F
(-4º C), compressor and outdoor fan start provided
Anti-Short Cycle Timer has timed out from
initial power-up, power restoration or previous
compressor on cycle.
• Operation continues until room temperature
satisfies thermostat.
• Once room temperature rises above set point by 3º
F (2º C), compressor and outdoor fan motor will
de-energize.
• If FCS is set to “Off”, indoor fan continues to
operate for 60 seconds after compressor stops.
• If FCS is set to “On”, indoor fan continues to
operate.
• As soon as compressor is de-energized, Anti-Short
Cycle Timer is initialized and prevents compressor
from starting again for another 180 seconds.
• While Anti-Short Cycle Timer is active, Processor
Board Trouble Code LED is set to blink a 2 flash
code.
• After Anti-Short Cycle Timer expires, Processor
Board Trouble Code LED is set to flash 1 blink
Trouble Code, indicating normal operation.
B. R_ _H; Auxiliary Heating “Electric” or “Hydronic”
• If outdoor coil temperature falls to 25º F (-4º C) or
below for 180 seconds at anytime during heating
call, compressor and outdoor fan motor are de-
energized and auxiliary heat is energized.
• Anti-Short Cycle Timer is initiated, prohibiting
compressor operation for 180 seconds. Processor
Board Trouble Code LED flashes 3 blink Trouble
Code, indicating auxiliary heat operation.
• Heating operation with auxiliary heat continues
until outdoor coil sensor reaches 50º F (10º C).
B.1 “Electric Heat”
A. System Switch [SS] set to “Heat”, and Fan
Cycle Switch [FCS] set to “On” (Continuous
Fan Operation), indoor fan motor starts.
SEQUENCE OF OPERATION
The Right Fit for Comfort
26
P/N 240010545, Rev. B [10/24/2014
]