EMKO ESM-4410 Instruction Manual - Set1
5. Parameters
5.1 Set Parameter
SET1
5.2 Program Parameters
Parameters are divided into two groups as SET and PROGRAM parameters.
SET value for Output. Control of output relay is done according to this value.
This value can be adjusted according to input type, minimum and maximum
of scale.
Operation Type Selection parameter for output
Operation type of output relay can be adjusted as
“HEATING”. Normally energised.
Operation type of output relay can be adjusted
“COOLING”. Normally de-energised.
Hysteresis Parameter for Output ( Default = 0 )
0 to 100 °C for TC Type Devices,
0 to 100 °C for PT-100 (0°C , 400°C),
0.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C),
0 to 100 °C for PTC (-50°C, 150°C),
0.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
0 to 20 °C for NTC (-50°C, 100°C)
Process Offset Parameter (Default = 0).
This parameter is offset for the process value. This defined value is added to
the process value.
-10 to 10 °C for TC Type Devices,
-10 to 10 °C for PT-100 (0°C , 400°C),
-10.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C),
-10 to 10 °C for PTC (-50°C, 150°C),
-10.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
-10 to 10 °C for NTC (-50°C, 100°C)
Minimum Pulling Time Parameter for Output (Minimum Off Time)
(Default = 0)
When Output is inactive this time must be expired for Output to become active
again. It can be adjusted from 0 to 100 seconds
Programming Mode Accessing Password ( Default =0 )
It is used for accessing to the programming mode. It can be adjusted from 0 to
999. If it is selected 0, password is not entered for accessing to the
parameters.
If no operation is done in programming or Set value mode for 20 seconds, device
turns to main operation screen automatically.
i
27