Warning: Always disconnect the electric power supply before
carrying out any work on the control unit (connection,
maintenance).
DS1
No.2: Lock activation delay
OFF = DISABLED
ON = ENABLED
If this dip-switch is enabled, the door movement is delayed
by 500msec with respect to the electric lock command. If
disabled, delay is 200 msec.
No.1: Inactive
SW1 SET-UP pushbutton
Hold down the SET-UP button for 5 sec. to start the set-up
cycle.
FUSE F1 1AT/230Vac - 5x20
J1 CONNECTOR Transformer Secondary winding - fig. 10
J2 CONNECTOR
Rapid Connector of Manual/Night,Open,Automatic
function selector switch
J3 CONNECTOR KP-Controller Connection
1- 2 Connector of KP-Controller programming unit (optional) as
shown in fig. 24.
Use a 2 x 0.5 mm² shielded cable (“bus” communication) for
the connection. Respect the connection polarity as shown
in figure 24.
Important: The maximum permissible length of the connection
cable is 50 m.
To inhibit operation of the SD-KEEPER, make the jumper
between terminals of the LOCK switch (fig.24).
J4 TERMINAL BOARD Inputs Connection (figs. 11,12,16)
7- 8 GND
Accessories power supply Negative and contacts Common
9
+24Vdc
+24Vdc accessories power supply
10
Internal Command - N.O. Contact
Any pulse generator (pushbutton, sensor, etc.) which, by
closing a contact, commands door opening.
To install several pulse generators as Internal Command,
connect the N.O. contacts in parallel.
11
External Command - N.O. Contact
Any pulse generator (pushbutton, sensor, etc.) which, by
closing a contact, commands door opening.
To install several pulse generators as External Command,
connect the N.O. contacts in parallel.
12
Emergency Command - N.C. Contact
Any pulse generator (normally a pushbutton) which, by
opening a contact, commands an emergency closure of the
system. Alternatively this input can be used to command
emergency opening by programming the system in a suitable
manner using the KP-CONTROLLER programming unit (optio-
nal).
To install several emergency command devices, connect the
N.C. contacts in series.
N.B.: If emergency command devices are not connected,
jumper inputs 7 and 12.
Attention: Using the KP-CONTROLLER programming unit, you
can change the type of contact from N.C. to N.O. contact.
13
CLOSURE Safety Command - N.C. Contact
Any device (safety sensor, photocell, etc.) which, by opening
a contact, has a safety effect on the closing movement of the
door.
The safety device causes an immediate reversing of the
closing movement of the door, but has no effect on the
opening movement of the door.
To install several CLOSURE safety devices, connect the N.C.
contacts in series.
N.B.: If CLOSURE safety devices are not installed, jumper inputs
7 and 14.
14
STOP Safety Command - N.C. Contact
Any device (safety sensor, photocell, etc.) which, by opening
a contact, has a safety effect on the operating cycle. In
particular, this safety device interrupts the opening/closing
movement of the door.
When the safety device is disengaged, the door resumes its
opening/closing movement and continues to the end of the
cycle.
To install several STOP safety devices, connect the N.C.
contacts in series.
N.B.: If STOP safety devices are not installed, jumper inputs 7
and 13.
7 8 9 10 11 12 13 14 15 16 17 18 19
GND
GND
+ 24 Vdc
Internal Command
External Command
Closure Safety Command
STOP Safety Command
Emergency Command
Key Command
Fire-alarm Command
Card Reader Command
GND
GND
J4
Fig. 11
7 8 9
13 14 15
TX
RX
PB SENSOR
+
-
C
+
+
-
-
C
J4
Fig. 12
7 8 9 10 11 12 13 14 15 16 17 18 19