FAAC E-SC 1600 Instruction Manual - Cn2 -
CN2 -
Located on the lower left side of the board, these terminals are outputs for the opera-
tor arm(s), gate locks (optional), and lamps (optional).
APM1, CHM1 - terminals. For dual operations these ter minals are for the ar m that must
move first, for single operations these terminals are the output for controlling the operator arm.
APM2, CHM2 - terminals. For dual operations ONLY. Connect the ar m that is to move
second to these terminals. For single operations nothing should be connected to these terminals.
ELS - terminals. Brief 12V output at beginning of operation cycle, meant for release an
electric lock.
LAMP - terminals. Both a flashing lamp and a courtesy lamp can be connected to these
terminals with a power supply of 24V DC and a max output of 15 W. to change between flash-
ing lamps and courtesy lamps, select parameter “G”.
CN3 -
Located on the center bottom of the board, these terminals are for limit switches.
COMF - Common ter minal to make the needed normally closed connections for the limit
switches.
FCC1 - Nor mally closed contact. This ter minal is connected with the COMF through the
limit switch. When tripped (connection opened) it stops the motion of the first operator. (If not
being used, this terminal must be jumped with COMF)
Master Closed Limit Switch
FCA1 - Nor mally closed contact. This ter minal is connected with the COMF through the
limit switch. When tripped (connection opened) it stops the motion of the first operator. (If not
being used, this terminal must be jumped with COMF)
Master Open Limit Switch
FCC2 - Nor mally closed contact. This ter minal is connected with the COMF through the
limit switch. When tripped (connection opened) it stops the motion of the second operator. (If
not being used, this terminal must be jumped with COMF)
Slave Closed Limit Switch
FCA2 - Nor mally closed contact. This ter minal is connected with the COMF through the
limit switch. When tripped (connection opened) it stops the motion of the second operator. (If
not being used, this terminal must be jumped with COMF)
Slave Open Limit Switch
ENC1, ENC2 - terminals. NOT USED
CN4 -
Located on the bottom right of the board, these terminals are for accessories and safe-
ty devices.
OPEN A - terminal. This is the most common ter minal for accessories. Accessories utilizing
a normally open contact to set the gate in motion will be attached to this terminal and the COM
terminal (common or also know as ground).
OPEN B - terminal. This ter minal is for opening the first leaf only in dual gate operations.
It is a normally open contact that must be used in conjunction with the COM terminal.
STOP - terminal. This is a normally closed ter minal that is used for gate motion stopping
emergency commands. If a safety device is not being used in this terminal the operator must
have a jumper ran from this terminal to the COM terminal in order to operate.
FSW CL, FSW OP - terminals. These nor mally closed ter minals are for safety devices dur-
ing the closing (CL) and opening (OP) cycles of the gate. If a safety device is not being used in
this terminal the operator must have a jumper ran from this terminal to the COM termi-
nal in order to operate.
COM - terminal. This is a common, or sometimes refer red to as gr ound, ter minal. It is
used in conjunction will ALL accessories and safety devices.