Falcon ED-1000-1 User Manual - page 6
MODEL SELECTION GUIDE
4
Model Number
ED-1000-1
ED-1500-1
ED-2000-1
Nominal VA
1000
1500
2000
Electrical Input
AC Voltage, +10% -20%
120V
120V
120V
Current-Amps
10.4
15.6
20.8
Frequency Range
47 – 450
47 – 450
47 - 450
Electrical Output
AC Voltage,
±
3%
120V
120V
120V
Watts @ 50 or 60 Hz
700
1050
1400
Watts @ 400 Hz
595
892
1190
Current-Amps @ 50/60 Hz
8.3
12.5
16.7
Current-Amps @ 400Hz
7.1
10.6
14.2
50/60 Hz Non – Linear
Repetitive Peak (Amps)
20
30
40
400 Hz Non – Linear
Repetitive Peak (Amps)
14.2
21.3
28.3
Total Harmonic Distortion
Overload
200% for 0.5 Seconds, 120% for 30 Seconds
Dynamic Response
±
5% RMS for 100% Step Load Change, 1ms Recovery Time
Output Protection
Short Circuit and Overload
Battery
Type
Sealed Lead Acid Maintenance-Free
Back Up Time @ Full Load
@ 1/2 Load
8 Minutes
20 Minutes
5 Minutes
14 Minutes
Battery times are approximate.
Electrical Connections
Input
6’ Cord with 5-15P
8’ Cord with 5-20P
8’ Cord with L5-30P
Output
(4) 5-15R
(4) 5-15R
(4) 5-15R
Environmental
Operating Temperature
0º C to 35º C (32º F to 95º F)
Humidity
10% to 95% Non – Condensing
Altitude
7,000 Feet
Cooling
Low Velocity Forced Air Fans
Audible Noise @ 1.5 Meters
49dBA
54dBA
Controls and Indicators
Sequenced LED’s
Load Level
Single LED
Utility Present, Low Battery, Summary Alarm, Inverter On
Audible Alarms
Utility Interrupt, Inverter Failure, Overload, Low Battery
Communications
Dry Contact Closures on Utility Loss & Low Battery via 9 Pin “D” Connector
Mechanical
Dimensions H x W x D inches (mm)
13.5 x 6.25 x 19.4 (342.9 x 158.8 x 492.8)
Weight lb. (kg)
41 (18.6)
64 (29)
64 (29)
Design Standard
UL Listed 1778, FCC Class A