Falcon ED-1000-1 User Manual - page 7
CHAPTER 2
CHAPTER 2
Installation
Inspecting the Equipment
If any FALCON
®
equipment has been damaged during shipment, keep the
shipping cartons and packing materials for the carrier and file a claim for
shipping damage. If you discover damage after acceptance, file a claim for
concealed damage.
To file a claim for shipping damage or concealed damage:
1) File with the carrier within 15 days of receipt of the equipment.
2) Send a copy of the damage claim within 15 days to the Falcon
®
Service Department.
UPS Setup
1. Verify that the following is included in the UPS shipping carton:
UPS, Owner's Guide and power cord of not attached to the unit.
2. Verify that the UPS unit is configured for the proper input/output
voltage. This information is stated on the nameplate label located on
the rear panel of the unit.
3. This UPS has been shipped with the battery connection fuse removed
to meet new transportation regulations.
THE BATTERY CONNECTION FUSE MUST BE INSTALLED PRIOR TO
PLUGGING IN AND ATTEMPTING TO TURN ON THE UPS.
4. Select a suitable location for the UPS, near enough to the computer or
equipment to allow connection of the equipment power plug to the
receptacles located on the rear panel of the UPS.
5.
DO NOT BLOCK UPS AIR VENTS. THE UPS MUST NOT BE
INSTALLED IN AN ENCLOSED AREA.
6. If you have not already done so, connect the equipment to be
protected to the UPS output receptacles located on the rear panel. Verify the
connected equipment does not exceed the rated output (in watts) of the UPS.
7. Plug the UPS power cord into the nearest grounded wall outlet. If the
UPS does not power up automatically, depress and hold the control
button located on the UPS front panel until the UPS turns on.
IMPORTANT
IMPORTANT
5