FältCom ECII SE Manual And Installation Instructions - 6 Installation
Manual FältCom ECII SE Eng
Page 12 of 36
5.2.3 Programming and testing
On the back of the lift phone, there is a keypad used for programming call numbers, function
selection, and testing. All such settings are made during the installation and, normally, no
subsequent changes are required. It is also possible to remotely program the lift phone with a
special Windows program and a modem. Contact your local distributor for more information.
The FältCom ECII SE is capable of calling 6 alarm receivers or standard telephones with tone
selection.
The lift phone can be programmed to send a test alarm to a specific test alarm receiver with
an interval of 1–9 days. This alarm tests the lift-phone electronics and the telephone line.
The lift phone can also be programmed to answer an incoming call automatically after four
ringing signals. In this case, tones are heard in the receiver when the call is connected.
If an emergency power supply is connected, the lift phone automatically can send an alarm if
the battery is bad and need to be replaced. A special telephone number for the battery alarm
can be programmed.
See
Programming
section for detailed programming instructions.
6 Installation
instructions
Only competent and qualified personnel may install the FältCom ECII SE. Knowledge,
technical skill and correct equipment are required for safe and efficient installation.
Mind your own safety when installing FältCom ECII SE. You must never work in an
open lift shaft without a safety harness. Be extremely careful and break current if
you work close to a voltage of 230-400V, e.g. in the lift engine room. Never
disconnect a cable before you have made sure that it is not connected to any
voltage
Start by selecting a suitable place for the lift phone. Usually, you can find an easily accessible
and yet well protected place in the lift cage ceiling. Avoid installing the phone in a corner or
behind anything that may reflect the sound. Such installation might lead to acoustic feedback
instability between the loudspeaker and the microphone. You must be able to access the
existing suspension cable and the alarm button in the lift. Also, keep in mind that you must be
able to access the back of the lift phone in order to connect cables and program different
functions. Normally, this is easier to do inside of the lift, before the lift phone is screw-
mounted.
Make sure that you will not saw or drill in existing cabling when you make the holes!
6.1 Recessed
mounting
1.
Select a suitable place according to the instructions above.
2.
Drill a hole in the centre of the selected place and then make a hole with a 86-mm
rotary hole saw or drill. See the enclosed drill template.