3.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault, the display will flash together
with the fault symbol (detail 20 - fig. 1) indicating the fault code.
There are faults that cause permanent shutdowns (marked with the letter “A”): to restore operation press the RESET
button (detail 8 - fig. 1) for 1 second or use the RESET on the optional remote timer control if installed; if the boiler fails
to start, it is necessary to first eliminate the fault.
Other faults (marked with the letter “F”) cause temporary shutdowns that are automatically reset as soon as the value
returns within the boiler's normal working range.
Table. 5 - Fault list
Fault
code
Fault
Possible cause
Cure
A01
The burner fails to light
No gas
Check the regular gas flow to the boiler and that the air
has been eliminated from the pipes
Ignition/detection electrode fault
Check the wiring of the electrode and that it is correctly
positioned and free of any deposits
Faulty gas valve
Check and replace the gas valve
Insufficient gas supply pressure
Check the gas supply pressure
Trap clogged
Check the trap and clean it if necessary
A02
Flame present signal with
burner off
Electrode fault
Check the ionisation electrode wiring
Card trouble
Check the card
A03
Overtemperature protection
activation
Heating sensor damaged
Check the correct positioning and operation of the
heating sensor
No water circulation in system
Check the circulating pump
Air in the system
Vent the system
A04
Fume extraction duct safety
device activation
Fault F07 generated 3 times in
the last 24 hours
See fault F07
A05
Fan protection activated
Fault F15 generated for 1 hour
(consecutive)
See fault F15
A06
No flame after ignition
stage (6 times in 4 minutes)
Ionisation electrode fault
Check the position of the ionisation electrode and
replace it if necessary
Flame unstable
Check the burner
Gas valve Offset fault
Check the Offset adjustment at minimum power
air/fume ducts obstructed
Remove the obstruction from the flue, fume extraction
ducts and air inlet and terminals
Trap clogged
Check the trap and clean it if necessary
F07
High fume temperature
Flue partially obstructed or insuf-
ficient
Check the efficiency of the flue, fume extraction ducts
and outlet terminal
Fume sensor position
Check the correct positioning and operation of the
fume sensor
F10
Delivery sensor 1 fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F11
Return sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected
F13
Fume sensor fault
Sensor damaged
Check the wiring or replace the sensor
Wiring shorted
Wiring disconnected