FHP EV Series Installation And Maintenance Manual

Manual is about: Geothermal

Summary of EV Series

  • Page 1

    Table of contents model nomenclature..................................................................................................1 initial inspection .........................................................................................................2 general description .....................

  • Page 2

    Introduction: the ev series uses a scroll compressor and refrigerant r- 410a to achieve high efficiency levels, quiet operation and reliable performance. The new refrigerant provides performance similar to that of r- 22 with one major advantage. Refrigerant r-410a is an hfc so it does not contain an...

  • Page 3

    Some applications require an attic floor installation of the horizontal unit. In this case the unit should be set in a full size secondary drain pan on top of a vibration absorbing mesh. The secondary drain pan prevents possible condensate overflow or water leakage damage to the ceiling. The seconda...

  • Page 4

    Safety devices and the lockout circuit: each ev series unit is factory provided with a ccmi solid state controller. The ccmi controller incorporates the standard functions of electromechanical controls while adding several useful features commonly needed in water source and geothermal heat pump appl...

  • Page 5

    5 ev series (figure #5) (figure #6) cooling tower/boiler application 1. Line voltage disconnect (unit) 2. Low voltage control connection 3. P/t plugs (optional) 4. Hose kits (optional) 5. Ball valves 6. Supply and return lines of central system 7. Flex duct connection 8. Hanging brackets assembly (1...

  • Page 6

    Table 1 - hp series electrical data * all 15 and 20 kw heaters can be separated into two individual circuits. The wiring information listed presumes the unit transformer and blower motor will be wired to the first circuit. 6 ev series earth coupled application 1. Line voltage disconnect (unit) 2. Fl...

  • Page 7

    7 ev series a secondary heat exchanger (plate frame between the unit and the open cooling tower) may also be used. It is imperative that all air is eliminated from the closed loop side of the heat exchanger to prevent condenser fouling. In the heating mode, heat is absorbed from the water loop to th...

  • Page 8

    8 ev series 9. Increase the thermostat setting to approximately five (5) degrees above the room temperature. 10. Verify the heat pump is operating in the heating mode. 11. Set the thermostat to maintain the desired space temperature. 12. Check for vibrations, leaks, etc… 13. Instruct the homeowner o...

  • Page 9

    9 ev series present in the return line, flow should be reversed. This procedure should be repeated several times until no air is present. If air is left in the loop, it will have an immediate effect on the unit’s coaxial heat exchanger causing corrosion of it and any associated ferrous metal compone...

  • Page 10

    10 ev series temp ( ºf) 1.0 4.8 8.3 11.6 14.8 17.9 20.8 23.6 26.3 28.9 31.4 33.8 36.2 38.5 40.7 42.8 44.9 47.0 49.0 50.9 52.8 54.7 56.5 58.3 60.0 61.7 63.4 65.0 66.6 68.2 69.8 71.3 72.8 press (psig) 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185...

  • Page 11

    Ev series 11 problem entire unit does not run blower operates but compressor does not unit off on high pressure control unit off on low pressure control unit short cycles insufficient cooling or heating possible cause power supply off blown fuse broken or loose wires voltage supply low thermostat th...

  • Page 12

    Rev. 9/00 12 ev series.