TABLE 1 - HP Series Electrical Data
* All 15 and 20 kW heaters can be separated into two individual circuits. The wiring information listed presumes the unit transformer
and blower motor will be wired to the first circuit.
6
EV SERIES
EARTH COUPLED APPLICATION
1.
LINE VOLTAGE DISCONNECT (UNIT)
2.
FLEX DUCT CONNECTION
3.
LOW VOLTAGE CONTROL CONNECTION
4.
LINE VOLTAGE CONNECTION (UNIT)
5.
P/T PORTS
6.
VIBRATION PAD
7.
CONDENSATE DRAIN
8.
GROUND LOOP CONNECTION KIT (550-016, 017)
9.*
GROUND LOOP PUMPING PACKAGE
10. POLYETHELENE WITH INSULATION
11. LINE VOLTAGE DISCONNECT (ELECTRIC HEATER)
NOTE: SEE FIGURE #3 FOR CONDENSATE DRAIN CONNECTION
* Optional Internal Installed
(Figure #7)
208V
240V
208V
240V
208V
240V
❍
EV030 thru 042
HP050-1XS
4.8
17.3
20.0
L1/L2
27.1
30.4
30
30
8
❍
EV048 thru 060
HP050-1XM
4.8
17.3
20.0
L1/L2
27.1
30.4
30
30
8
❍
EV030 thru 042
HP075-1XS
7.2
23.6
30.0
L1/L2
34.9
42.9
40
45
8
❍
EV048 thru 060
HP075-1XM
7.2
23.6
30.0
L1/L2
35.7
43.8
40
45
8
❍
EV030 thru 042
HP100-1XS
9.6
34.7
40.0
L1/L2
48.8
55.4
50
60
6
❍
EV048 thru 060
HP100-1XM
9.6
34.7
40.0
L1/L2
49.5
56.3
50
60
6
❍
EV048 thru 060
HP150-1XM
14.4
52.0
60.0
SINGLE
71.2
81.3
80
90
4
HP150-1XM
14.4
34.7
40.0
L1/L2
49.5
56.3
60
60
6
17.3
20.0
L3/L4
21.7
25.0
25
25
10
❍
EV048 thru 060
HP200-1XM
19.2
69.3
80.0
L1/L2
92.9
106.3
100
110
2
HP200-1XM
19.2
34.7
40.0
L1/L2
49.5
56.3
50
60
6
34.7
40.0
L3/L4
43.4
50.0
45
50
6
All heaters rated single phase 60hz, and include unit fan load. All fuses type “D” time delay or HACR type breaker or HRC FORM 1 Wire
size based on 60 deg. C copper conductors.
EV
HEATER
KW
HEATER
CIRCUIT
MCA
MAX
AWG
MODEL
MODEL
AMPS
FUSE
MIN