TECHNICAL CHARACTERISTICS
5.1
RATED TECHNICAL DATA OF HEAT PUMPS
* Weights refer to model with pump and storage reservoir
- Cooling capacity: outdoor air temperature 35°C, water temperature 12°C / 7°C
- Heating capacity: outdoor air temperature 7°C dry bulb and 6.2°C wet bulb, water temperature 40°C/45°C
- Sound power measured according to standards ISO 3741 - ISO 3744 and EN 29614-1
- Sound pressure measured at a distance of 10 m and a height of 1.5 m above the ground in a clear field (fan side).
- The maximum electrical input is the mains electricity that must be available in order for the unit to work.
- The maximum current absorption refers to the current that will trigger the internal safety devices of the unit. It is the maximum current allowed in the unit.
This value may never be exceeded; it must be used as a reference for determining the size of the power supply line and the related safety devices (refer to the
wiring diagram supplied with the units).
MXE
009 M
009
011 M
011
014
016
019
021
Power supply
V-ph-Hz
230-1-50
400-3-50
230-1-50
400-3-50
400-3-50
400-3-50
400-3-50
400-3-50
Cooling capacity
kW
7,33
7,46
9,34
9,34
12,20
14,40
16,05
18,50
Total power input
kW
2,83
2,71
3,58
3,38
4,30
5,24
5,54
6,21
EER
2,98
3,19
2,91
3,10
3,10
2,96
3,10
3,17
ESEER
3,92
3,62
3,73
3,31
3,77
3,59
3,67
3,79
Heating capacity
kW
8,54
8,46
10,82
10,51
13,66
15,84
18,53
20,64
Total power input in heating mode
kW
3,15
2,99
3,72
3,47
4,47
5,24
5,71
6,31
COP
3,07
3,21
3,23
3,39
3,33
3,25
3,47
3,47
Maximum power input
A
22,3
9,3
26,3
11,3
13,3
16,3
19,6
20,0
Starting absorbed current
A
84
37
98
50
66
72
77
103
n° of scroll compressor / circuits
1/1
1/1
1/1
1/1
1/1
1/1
1/1
1/1
Low/high pressure switch
bar
0,7 / 42
0,7 / 42
0,7 / 42
0,7 / 42
0,7 / 42
0,7 / 42
0,7 / 42
0,7 / 42
n° of axial fan
2
2
2
2
2
2
4
4
Air flow
m
3
/h
7.705
7.705
7.705
7.705
7.355
7.355
12.679
12.679
Water flow in cooling mode
l/h
1.261
1.283
1.606
1.606
2.098
2.477
2.761
3.182
Water flow in heat pump
l/h
1.469
1.454
1.861
1.821
2.442
2.853
3.211
3.605
Diameter of hydrualic connections
"
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
1 1/4
Available pressure head (cooling)
kPa
130
130
132
132
115
111
154
157
Available pressure head (heating)
kPa
118
118
121
125
103
98
143
148
Expansion tank
dm
3
5
5
5
5
5
5
5
5
Buffer tank
dm
3
30
30
30
30
30
30
30
50
Height
mm
1250
1250
1250
1250
1250
1250
1275
1275
Length
mm
1220
1220
1220
1220
1220
1220
1590
1590
Depth
mm
550
550
550
550
550
550
600
600
Sound power level
dB(A)
69
69
69
69
69
69
72
72
Sound pressure level
dB(A)
41
41
41
41
41
41
44
44
Transport weight *
kg
212
212
215
215
219
220
273
273
Operating weight *
kg
237,5
237,5
240,5
240,5
244,5
245,5
309,3