Iwc cassette fan coils 2,6 kw - 9,1 kw technical manual en.
Iwc 2 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 table of contents 1 constructive features .............................................................2 2 construction versions ............................................................2 3 air range .........
Iwc 3 z y x all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 3 air range • fin inclination 45° • limit speed 0.2 m/s mode • heating in nominal conditions model iwc32-34 iwc42-44 iwc52 iwc62 iwc82 speed 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 air range z 1,7 3,0 3,...
Iwc 4 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 4 ratings and technical data notes: 1 = water temperature 7/12°c, air temperature d.B. 27°c, w.B. 19°c, 47% humidity 2 = inlet water temperature 50°c, water flow rate same as in cooling mode, air inlet tempera...
Iwc 5 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 4 ratings and technical data notes: 1 = water temperature 7/12°c, air temperature d.B. 27°c, w.B. 19°c, 47% humidity 3 = water temperature 70 - 60°c; air temperature 20°c 4 = sound power conforming to iso 3741...
Iwc 6 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 5 performances in order to define the performances of iwc subject to conditions different from rated conditions, a computer program for the correct choice of the units is provided by galletti spa. With a few i...
Iwc 7 lw iwc vr 125 hz 250 hz 500 hz 1000 hz 2000 hz 4000 hz 8000 hz lwa lpa db db db db db db db db/a db/a iwc o32 1 36,1 33,9 25,3 19,7 21,4 16,8 20,0 30,0 25,0 2 42,5 43,4 41,5 32,2 27,0 18,5 19,8 41,0 36,0 3 46,1 46,7 44,0 36,3 29,9 19,9 20,4 44,0 39,0 4 46,7 47,7 45,9 39,8 33,2 22,6 17,7 46,0 4...
Iwc 8 730 730 544 506 41 min. 544 10 10 10 506 259 41 min. 10 135 600 575 506 e 259 228 192 152 575 600 544 70 296 273 23 41 a c b d 730 730 544 506 41 min. 544 10 10 10 506 259 41 min. 10 135 600 575 506 h 259 228 192 152 575 600 544 70 296 273 23 41 a f e c b d g all copying, even partial, of this...
Iwc 9 860 760 l 500 h 30 240 48 125 200 z y e d c b a f 30 mini cwx 6 x all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 iwc 06-08, 2 pipes 8 overall dimensions a condensate hole: 32 mm Ø od b water inlet: ¾” gas female c water outlet: ¾” gas female d coil air ven...
Iwc 10 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections generalities • class 1 unit. • the electrical installation must comply with current standards and regulations (paying particular attention to standards nf c 15-100, cei 364). Details ...
Iwc 11 pe n u pe n u n f 230v/1/50hz all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections wiring diagrams: models with cable control for the connection to the power supply, use the terminal x1 (terminals u, n and pe) of the printed circuit boa...
Iwc 12 iwc 3-4 iwc 5 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections.
Iwc 13 iwc 6-8 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections.
Iwc 14 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections 1 - jumper setting c = closed o = open 2 - functions: a = available e = not available (when selected from the remote control, all signals are flashing) note: configurations other than...
Iwc 15 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections iwc 3-4 with cable control iwc 3-4 with cable control (2 pipes).
Iwc 16 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections iwc 5 with cable control iwc 6-8 with cable control.
Iwc 17 iwc + mycomfort base + kp all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections.
Iwc 18 iwc + mycomfort medium + kp all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections.
Iwc 19 iwc + mycomfort large + kp all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections.
Iwc 20 iwc + led503 + kp all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 9 electrical connections.
Iwc 21 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 10 accessories mycomfort base - wall-mounted microprocessor control, galletti model mycomfort base having the following main features: - room air temperature reading and adjustment - water temperature reading...
Iwc 22 in out 1 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 10 accessories 3-way motor driven valve and 4x2 motor driven valve kit the kit includes: - brass 3-way valve / 4 connections with built-in by-pass, maximum operating pressure 16 bar; electrothermal o...
Iwc 23 in out 2 in out 3 in out 4 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 warning: in order to avoid leakage problems, the maximum pressure difference between the hot side and the cold side of the water circuit should be lower than 1 bar. Warning: in orde...
Iwc 24 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 main heat exchanger water outlet iwc 03-04 4 tubi, iwc 03-04 4 pipes valvola a 2 vie - 2-way valve main heat exchanger water inlet additional heat exchanger water outlet additional heat exchanger water inlet ...
Iwc 25 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 iwc 06-08 2 tubi, iwc 06-08 2 pipes valvola a 2 vie - 2-way valve water outlet water inlet.
Iwc 26 all copying, even partial, of this manual is strictly forbidden. Wc66000113 - rev 04 models equipped with infrared remote control, can only mount a motor-driven valve kit with 230 volt actuator * the modulating valves can be managed in models configured for a wired controller. A mycomfort lar...
Notes.
Www.Galletti.It 40010 bentivoglio (bo) via romagnoli 12/a tel. 051/8908111 - fax. 051/8908122 company uni en iso 9001 and ohsas 18001 certified.