Haier 1U12LC2VHA Installation Manual

Other manuals for 1U12LC2VHA: Installation Manual
Manual is about: Ductless Split Air Conditioner

Summary of 1U12LC2VHA

  • Page 1

    Ductless split air conditioner installation manual indoor aw12lc2vha aw18lc2vha ab12sc2vha ab18sc2vha ad12sl2vha ad18sl2vha outdoor 1u12lc2vha 1u18lc2vha 1u12lc2vha 1u18lc2vha 1u12lc2vha 1u18lc2vha outdoor unit installation and indoor unit installation – wall mount . . . . . . . . . . . . . . . . . ...

  • Page 2

    Installation 24k for: 09k required tools for installation procedure for selecting the location than 10ft away depending on radio wave conditions.) • drill • wire snipper • hole saw 2 3/4” • vacuum pump • soap-and-water solution or gas leakage detector • torque wrench • 17mm, 22mm, 26mm • tubing cutt...

  • Page 3

    Installation page 3 step 2 - installation of the indoor unit attaching the mounting plate to the wall using a stud sensor, locate and mark the stud positions in the wall where the indoor unit is to be mounted. Place the mounting plate on the wall in the desired location taking into account the minim...

  • Page 4

    Installation step 2.9 attaching drain elbow to outdoor unit with the top of the indoor unit closer to the wall, hang the indoor unit on the upper hooks of the mounting plate. Slide the unit slightly side to side to verify proper placement of the indoor unit on the mounting plate. Rotate the lower po...

  • Page 5

    Installation page 5 3.3 step - 3.3 connect the wiring for both the power source and indoor wiring. Wire the system according to applicable national / local codes. Verify that the wiring connections for the indoor unit match wire for wire. (1-1, 2-2, 3-3, gnd-gnd). Failure to wire the system correctl...

  • Page 6

    Installation hazard of explosion! Never use an open flame to detect gas leaks. Explosive conditions may occur. Use a leak test solution or other approved methods for leak testing. Failure to follow recommended safe leak test procedures could result in death or serious injury or equipment or property...

  • Page 7

    Installation page 7 piping hole. Use a sealant to seal the piping hole opening to prevent weather elements from entering the building. (illustration 6) less than 5cm verify the condensate drain line has a constant pitch downward for proper water flow. There should be no kinks or rises in the tubing ...

  • Page 8

    Installation • using the operating instructions, explain to the user how to use the air conditioner (the remote controller, removing the air filters, placing or removing the remote controller from the remote controller holder, cleaning methods, precautions for operation, etc.) • recommend that the u...

  • Page 9

    Installation page 9 indoor unit installation - cassette the cassette indoor air handler ships consists of a cassette assembly and operational louver. The cassette indoor unit is operated via a factory supplied remote control. Wired controller is optional. The cassette unit will install between stand...

  • Page 10

    Installation 1 9 .6 i n . B e lo w fresh air intake option the cassette has a marked area to cut out if outside air is desired. The piping connection should be made with a 4 inch diameter pipe. Outside air should be pre-filtered prior to entry into the cassette. Condensate handling the cassette unit...

  • Page 11

    Installation page 11 required tools for installation • drill • wire snipper • hole saw 2 3/4” • vacuum pump • soap-and-water solution or gas leakage detector • torque wrench • 17mm, 22mm, 26mm • tubing cutter • flaring tool • razor knife • measuring tape • level • micron gauge • nitrogen • mini-spli...

  • Page 12

    Installation use cardboard template to locate center point of cassette for mounting. Use a plumb bob and string to position cassette by referencing center hole of template. Mark the mounting positions of the threaded rods using the guides on the cardboard template. Install threaded rods to structure...

  • Page 13

    Installation page 13 step 2.5a step 2.5b step 2.6 step 2.7 step 2.8a step 2.8b step 2.8c step 2.8d step 2 - installation of the cassette unit e n g l is h.

  • Page 14

    Installation electrical connections indoor and outdoor units 14 awg stranded wire only. (central controller not used) maintain 10 feet of separation between tv and any radio wiring. To mount the louver cover onto the cassette assembly. Install 2 screws at the keyhole slot positions shown in the firs...

  • Page 15

    Installation page 15 indoor cassette unit installation complete indoor unit installation - slim duct the slim duct indoor air handler ships consisting of a single assembly. The slim duct indoor unit is operated via a factory supplied wired remote control. The slim duct unit will install above the ce...

  • Page 16

    Installation 1 9 .6 i n . B e lo w condensate handling the slim duct unit has a built-in condensate pump and water level safety switch. There are also two optional ports for gravity drainage. The condensate pump is rated to lift water up to 24” from the point of discharge on the slim duct unit. The ...

  • Page 17

    Installation page 17 • drill • wire snipper • hole saw 2 3/4” • vacuum pump • soap-and-water solution or gas leakage detector • torque wrench • 17mm, 22mm, 26mm • tubing cutter • flaring tool • razor knife • measuring tape • level • micron gauge • nitrogen • mini-split ad-87 adapter (1/4” to 5/16”) ...

  • Page 18

    Installation determine and mark the position of where the slim duct unit is to be installed. Install the hardware necessary to mount the threaded rods. Always select a location strong enough to support the indoor slim duct unit. Install the threaded rods to the hardware attached to the structure. Li...

  • Page 19

    Installation page 19 step 2.5 step 2.5a step 2.6 step 2.7 step 2.7a step 2.7b re-install electrical box cover step 2.8 installation is now complete bottom side air inlet diffuser return duct rear side air inlet diffuser return duct step 2 - installation of the slim duct unit e n g l is h.

  • Page 20

    Page 30 installation electrical connections indoor and outdoor units 14 awg stranded wire only. (central controller not used) maintain 10 feet of separation between tv and any radio wiring. See step 4.2 of the outdoor unit installation section for how to pull a vacuum. Indoor slim duct unit installa...

  • Page 21

    [this page intentionally left blank.].

  • Page 22

    Www.Haier.Com model #: 1u12lc2vha, 1u18lc2vha, aw12lc2vha, aw18lc2vha, ab12sc2vha, ab18sc2vha, ad12sl2vha, ad18sl2vha issued date: may 2015 haier america, wayne, nj 07470 ©2015 haier america trading, llc..