Haier 1U24GS1ERA Service Manual - Hi5G)+C,c()./e)B/"(),-(4/
AS24GS1/2ERA 1U24GS1ERA-SM
Function and Control
Domestic Air Conditioner
14
HI5G)+C,C()./E)B/"(),-(4/
5.1 Main functions and control specification of indoor unit
5.1.1 Automatic operation
When the running mode is turned to automation after starting the system, the system will first
determine the running mode according to the current room temperature and then will run according to
the determined mode. Tr in the following selection conditions means room temperature, Ts means
setting temperature, Tp means temperature of indoor coil pipe
Tr≥23
Choose Cooling Mode
ć
Tr˘23
Choose Heating Mode
ć
After turning to the automation mode, the running mode can be switched between cooling mode, fan
mode and heating mode according to the change of the indoor ambient temperature. But the
automatic conversion between cooling mode and heating mode must be conducted after 15 minutes.
5.1.2 Cooling operation mode
Temperature control range: 16ć---30ć
Temperature difference: !1ć
* Control features: When Tr˄input airflow˅>Ts˄set temperature˅ , the compressor will be opened,the
ć
indoor fan will operate at the set speed and the mode signal will be sent to the outdoor system. When
Tr˄input airflow˅" Ts˄set temperature˅ , the compressor will be opened,the indoor fan will operate
ć
at the set speed and the mode signal will be sent to the outdoor system. The system will keep the
original status if Tr= Ts.
Airflow speed control: (temperature difference 1
)
ć
Automatic: When Tr>=Ts+3
, high speed.
ć
When Ts+1
=
, medium speed
ć
ć
When Tr , low speed ć When the sensor is off, low speed When the airflow speed has no delay from the high to low switching, the speed should be delayed for 3 minutes (remain at high speed for 3 minutes.) before the next switch. Manus: When the system is operating, you can set the high, medium or low speed manually. ( When the sensor is on or off, the system will change the speed 2 seconds after receiving the signal.) *Airgate location control: the location for the airgate can be set according to your needs. *Defrosting function: preventing the frosting on the indoor heat exchanger (when cooling or demoisture). When the compressor works continuously for 1/6 minutes (adaptable in EEPROM) and the temperature of the indoor coils has been below zero centigrade for 10 seconds, the compressor will be stopped and the malfunction will be recorded in the malfunction list. The indoor system will continue to run. When the temperature of the indoor coil is raised to 7 , the compressor will be ć restarted again (the prerequirement of 3 minutes’ delay should be satisfied.) * timing system on/off function. * Dormant control function. Service manual order no.!"##$%&$$#'$ ek&em-series model no. 1u24gs1era ©2011 (qingdao haier air conditioner general corp.,ltd) all right reserved .Unauthorized copying and distribution is a violation of law haier group this service information is designed for experienced repair technicians only and ... As24gs1/2era 1u24gs1era-sm 1. Introduction............................................................................................. 1 2. List of functions...................................................................................... 6 3. Specifications....................................... As24gs1/2era 1u24gs1era-sm 9.9 removal of outdoor panel.................................................................... 102 9.10 removal of electrcal box.................................................................... 104 9.11 removal of the side panel........................................... Introduction domestic air conditioner 1. Introduction 1.1 safety cautions be sure to read the following safety cautions before conducting repair work. The caution items are classified into “warning” and “caution”. The “warning” items are especially important since they can lead to death or serious i... Introduction domestic air conditioner warning do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock. Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock. Be sure to prov... Introduction domestic air conditioner warning be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient... Introduction domestic air conditioner 1.1.3 inspection after repair warning check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet all the way. If the plug has dust or loose connection, it can cause an electrical shock or fire. If the power cable... Introduction domestic air conditioner caution check to see if the parts and wires are mounted and connected properly, and if the connections at the soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, fire or an electrical shock. If the... Category healthy negative ion y child lock y 3d air flow n 24hour timer y y easy clean design intelligent air y anti-mold filter y 4 fan setting y auto mode y power mode soft mode y note: y: holding functions n : no functions make your room full of an abundance natural negative ions. Functions quick... 23900(7850-24900) 23200(7500-23900) 2120(600~2150) 1970(595~2000) 3.21 3.6 16.7 14.6 12.5 17.3 15.4 13.5 - - - - 0.15 0.15 0.15 0.15 33 33 33 33 50/47/45 60 7.10(2.3~7.3) 13.0 . 16.5 13.0 . 16.5 4 4 6.80(2.2~7.0) 5848(1892-6020) 7 9.5 9.1 2.6 25 10 15 20 25 10 15 20 1126x344x388 3 specification 6536... 0.50 r410a 1.60 51.7 1823.8 51.7 1823.8 52.2 48.2 60 860x308x730 995x420x815 2120 1970 9.5 9.1 60 27 35 70 70 snb130fgym2 900 fv50s 5 as24gs1/2era 1u24gs1era-sm. As24gs1/2era 1u24gs1era-sm connector wiring diagram domestic air conditioner 9 4.Printed circuit board connector wiring diagram 4.1˖indoor unit connectors "())*+,(-./ / / / / / / / / / / / 0"12#3/2"(),-(4/0"13/5(-/678#96"$:; 1) cn26 connector for fan motor 2) cn1 connector for heat exchanger thermis... As24gs1/2era 1u24gs1era-sm connector wiring diagram domestic air conditioner 10 0"12#3/ cn26 cn1 sw1 con1 cn11 con6 con6 con7 cn32 con2 con9 cn34 cn20 As24gs1/2era 1u24gs1era-sm connector wiring diagram domestic air conditioner 11 4.2: outdoor unit "())*+,(-./ / / / / / / / / / / / / 0"12#3/2"(),-(4/0"13 1) cn1,cn2 connector for power n and l 2) cn3 connector for ground 3) cn6 cn7 connector for terminal to indoor unit 4) cn25 connector for dc powe... As24gs1/2era 1u24gs1era-sm connector wiring diagram domestic air conditioner 12 0"12#3/ / / / / / / / / / / / / / / / / / / / / / / / / / / / cn2 cn1 cn23 cn8 cn10 cn12 cn11 cn21 cn20 cn19 cn18 cn22 cn25 cn28 cn45 cn17 cn7 cn6 cn47 cn16 cn15 cn4 cn36 cn22. As24gs1/2era 1u24gs1era-sm connector wiring diagram domestic air conditioner 13 0"12%3/ cn5 cn7 cn6 cn11 cn2 cn1 cn4 cn3 cn9 cn8 cn10 As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 14 hi5g)+c,c()./e)b/"(),-(4/ 5.1 main functions and control specification of indoor unit 5.1.1 automatic operation when the running mode is turned to automation after starting the system, the system will first determine the run... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 15 5.1.3 demoisture mode. * temperature control range: 16---30ć * temperature difference: !1ć control feature: send the demoisture signal to the outdoor system. When tr>ts+2 , the compressor will be turned on, the indoor fan wi... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 16 mode. *indoor fan control manual control: you can choose high, medium, low and automatic speed control. Automatic: when tr when ts= , medium speed. ć when tr> ts+2 , low speed. ć when the airflow speed has no delay from the ... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 17 entering ‘mute’, you can have normal operation or signal control such as timing to finish the strength operation. When the system is at the automatic option ,there is no strength/ mute function,. 5.1.6 mute operation the sys... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 18 temperature will be raised for 1 centigrade after 1 hour’s operation and will be raised for 1 centigrade 1 hour later. The system will keep this status for 6 hours and then close. 2.2 under the heating mode, after the settin... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 19 malfunction will be stored in the malfunction resume and will not be revealed. 5.1.12 high load protection control the outdoor system will be stopped if the coil temperature is above 65ć for 2 minutes. The indoor fan will be... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 20 according to the original status, the malfunction code will not be revealed or processed. Ni,-e).Fc..C()/em)(-fe4c,j?/ if the indoor system can’t receive the outdoor system for 8 minutes, the communication abnormality can be... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 21 heating signal to the outdoor system. Meanwhile, you can fix the indoor system at high speed mode, the location of the airflow directin board can be switched to the maximal position. C. Quitting condition: the fixed frequenc... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 22 58hz,88hz for one minute (the overheating protection of the outdoor unit air-blowing temperature, immediately decrease the frequency when the compressor is overflowing and releasing the pressure)ˈthen it can be operated towa... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 23 heating mode˖ k=∑ki/the number of running machines the calculation of the actual output frequency: when there is no healthy airflow: f =f-ed-*×p×k when the healthy airflow has been set: f =f-ed-*×p×k˄airflow speed˅×k˄healthy... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 24 the temperature of the outdoor air ˄ta˅ airflow speed ta 22 ̱ ć low 19 ta ć̰ ć keeping the speed 16 ta ć̰ ć medium 14 ta ć̰ ć keeping the speed ta high 5.2.3˖the control of the outdoor electronic expansion valve when startin... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 25 defrostings is 45 minutes (the time interval which is in 57 digits in eeprom can be adjusted˅ when the result of c×taˉα is in the scope of c×taˉα , the time interval between two ć defrostings is 65 minutes. "i=*k-(.,c)d/(l*-... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 26 increasing the frequency (1hz/10second) 98 increasing the frequency˄1hz/1second˅ ttc>=110ć lasts for 20 seconds. Overheating protection of air-blowing, alarm malfunction to the indoor, others don’t last. 5.2.6.2˖tc high temp... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 27 frequency of the compressor increases at the speed of no faster than 0.1hz/second. / 5.2.6.4 the protection function of ac current: during the starting process of the compressor, if the ac current is greater than 10.5a, the ... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 28 / 5.2.6.6 the frequency limitation of modification rate in the field which is controlled by high frequency, if the modification rate is not high enough, the control-driven on chip will enter into weak magnetic control, this ... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 29 5.3 value of thermistor 5.3.1 intdoor unit room sensor and pipe sensor r25ć=10kΩ±3% b25ć/50ć=3700k±3% temp.(( )) ć max.(kΩ) normal(kΩ) min.(kΩ) tolerance( ) ć -30 165.2170 147.9497 132.3678 -1.94 1.75 -29 155.5754 139.5600 1... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 30 -9 50.8956 47.1666 43.6714 -1.54 1.44 -8 48.3178 44.8454 41.5851 -1.51 1.42 -7 45.8860 42.6525 39.6112 -1.49 1.40 -6 43.5912 40.5800 37.7429 -1.47 1.39 -5 41.4249 38.6207 35.9739 -1.45 1.37 -4 39.3792 36.7676 34.2983 -1.43 1... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 31 34 7.2546 6.9673 6.6854 -1.06 1.04 35 6.9852 6.7008 6.4222 -1.10 1.07 36 6.7273 6.4459 6.1707 -1.13 1.11 37 6.4803 6.2021 5.9304 -1.17 1.14 38 6.2437 5.9687 5.7007 -1.21 1.18 39 6.0170 5.7454 5.4812 -1.25 1.22 40 5.7997 5.53... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 32 78 1.6409 1.5051 1.3794 -2.97 2.75 79 1.5923 1.4592 1.3360 -3.02 2.80 80 1.5454 1.4149 1.2942 -3.07 2.84 81 1.5000 1.3721 1.2540 -3.12 2.88 82 1.4562 1.3308 1.2151 -3.17 2.93 83 1.4139 1.2910 1.1776 -3.22 2.97 84 1.3730 1.25... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 33 ambient sensor, defrosting sensor, pipe sensor r25 =10kΩ±3% b25 /50 =3700k±3% ć ć ć temp.( ) ć max.(kΩ) normal(kΩ) min.(kΩ) tolerance( ) ć -30 165.2170 147.9497 132.3678 -1.94 1.75 -29 155.5754 139.5600 125.0806 -1.93 1.74 -... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 34 11 19.1149 18.2270 17.3646 -1.08 1.05 12 18.2580 17.4331 16.6305 -1.06 1.03 13 17.4442 16.6782 15.9315 -1.03 1.01 14 16.6711 15.9601 15.2657 -1.01 0.99 15 15.9366 15.2770 14.6315 -0.98 0.96 16 15.2385 14.6268 14.0271 -0.96 0... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 35 55 3.4195 3.2085 3.0079 -1.91 1.82 56 3.3060 3.0989 2.9021 -1.95 1.85 57 3.1969 2.9935 2.8005 -2.00 1.89 58 3.0919 2.8922 2.7029 -2.04 1.93 59 2.9909 2.7948 2.6092 -2.08 1.97 60 2.8936 2.7012 2.5193 -2.13 2.01 61 2.8000 2.61... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 36 99 0.8983 0.8088 0.7275 -4.07 3.69 100 0.8741 0.7863 0.7067 -4.12 3.74 101 0.8507 0.7646 0.6867 -4.18 3.78 102 0.8281 0.7436 0.6672 -4.23 3.83 103 0.8061 0.7233 0.6484 -4.29 3.88 104 0.7848 0.7036 0.6303 -4.34 3.92 105 0.764... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 37 -13 4738.4141 4032.7098 3429.0191 -2.73 2.34 -12 4451.4586 3795.3910 3233.1039 -2.72 2.33 -11 4183.5548 3573.4260 3049.5312 -2.70 2.32 -10 3933.3289 3365.7336 2877.4527 -2.69 2.31 -9 3699.5139 3171.3148 2716.0828 -2.67 2.30 ... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 38 31 420.1431 383.7151 350.1301 -1.97 1.81 32 400.3242 366.1295 334.5542 -1.95 1.80 33 381.5350 349.4341 319.7460 -1.93 1.78 34 363.7176 333.5801 305.6645 -1.90 1.76 35 346.8176 318.5216 292.2709 -1.88 1.75 36 330.7839 304.215... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 39 75 62.3423 60.1906 58.0609 -0.95 0.94 76 59.9821 57.9770 55.9885 -0.92 0.92 77 57.7223 55.8552 53.9998 -0.90 0.89 78 55.5583 53.8210 52.0912 -0.87 0.87 79 53.4856 51.8706 50.2591 -0.85 0.84 80 51.5000 50.0000 48.5000 -0.85 0... As24gs1/2era 1u24gs1era-sm function and control domestic air conditioner 40 119 14.5599 13.5942 12.6811 -2.36 2.23 120 14.1376 13.1879 12.2909 -2.41 2.27 121 13.7294 12.7955 11.9144 -2.45 2.31 122 13.3347 12.4165 11.5510 -2.50 2.35 123 12.9531 12.0503 11.2003 -2.54 2.39 124 12.5840 11.6965 10.8617 -... 1 as24gs1/2era 1u24gs1era-sm 6.2.1 the instruction for as24gs1era. Outdoor unit loading of the battery 1 2 3 4 parts and functions indoor unit outlet inlet connecting piping and electrical wiring drain hose remote controller remove the battery cover; load the batteries as illustrated. 2 r-03 batteries, resetting key (cylinder); be sure that the loading is in line w... Operation air flow direction adjustment auto cool dry fan heat 2.Select operation mode press fan button. For each press, fan speed follows: press mode button. For each press, operation mode changes as follows: remote controller: remote controller: press button every time the button is pressed, temp.... Operation sleep operation use of sleep function operation mode 1. In cool,dry mode sleep operation starts sleep operation stops sleep operation starts sleep operation stops approx.6hrs 1 hr 1 hr 1 hr 3 hrs 3 hrs rises 1 o c rises 1 o c rises 1 o c temp.Setting temp.Setting unit stop unit stop in coo... Operation set clock correctly before starting timer operation. 1.After unit starts, select your desired operation mode. 2.Press timer button to change timer mode. Every time the button is pressed, display changes as follows: remote controller: blank timer on timer off timer on-off then select your d... Indoor unit installaion driver ƽ torque wrench ƽ (17mm,22mm,26mm) nipper ƽ reamer ƽ hacksaw ƽ pipe cutter ƽ gas leakage detector or ƽ soap-and-water solution hole core drill ƽ flaring tool ƽ spanner(17,19 and 26mm) ƽ knife ƽ measuring tape ƽ necessary tools for installation power source before inser... Indoor unit installation fix to side bar and lintel a mounting bar, which is separately sold, and then ƽ fasten the plate to the fixed mounting bar. Refer to the previous article, “ when the mounting plate is ƽ position of wall hole. Make a hole of 70 mm in diameter, slightly descending to outside t... 1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed. 2. Pull out the cable on the front side, and connect the cable making a loop. When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not c... Setting of proper room temperature close doors and windows during operation if the unit is not to be used for a long time, turn off the power supply main switch. Use the timer effectively use the louvers effectively do not block the air inlet or outlet proper temperature during cooling operation pre... The power supply cord and so on. 2.Do not install in the place where there is any possibility of inflammable gas leakage around the unit. 3.Do not get the unit exposed to vapor or oil steam. Cautions please call sales/service shop for the installation. Do not attempt to install the air conditioner b... Trouble shooting normal performance inspection noise is heard phenomenon cause or check points the system immediately. Smells are generated. Mist or steam are multiple check poor cooling when unit is stopped, it won't restart elapsed to protect the system. When the electric plug is pulled out and re... 52 domestic air conditioner as24gs1/2era 1u24gs1era-sm introduction outdoor unit 4 loading of the battery 1 2 3 4 indoor unit outlet inlet connecting piping and electrical wiring drain hose remote controller remove the battery cover; load the batteries as illustrated. 2 r-03 batteries, resetting key... 53 domestic air conditioner operation air flow direction adjustment press fan button. For each press, fan speed follows: remote controller: press button every time the button is pressed, temp.Setting increase 1 o c,if kept depressed, it will increase rapidly every time the button is pressed, temp.Se... 54 domestic air conditioner 4 operation sleep operation if the wind speed is high or middle before setting for the sleep, set for lowing the wind speed after sleeping. If it is low wind, no change. 5.Set the wind speed change when sleeping operation mode 1. In cool,dry mode sleep operation starts sl... 55 domestic air conditioner operation 1.After unit starts, select your desired operation mode. 2.Press timer button to change timer mode. Every time the button is pressed, display changes as follows: remote controller: blank timer on timer off timer on-off then select your desired timer mode (timer ... 56 domestic air conditioner 6 indoor unit installaion driver ● torque wrench ● (17mm,22mm,26mm) nipper ● reamer ● hacksaw ● pipe cutter ● gas leakage detector or ● soap-and-water solution hole core drill ● flaring tool ● spanner(17,19 and 26mm) ● knife ● measuring tape ● necessary tools for installa... 57 domestic air conditioner 6 indoor unit installation fix to side bar and lintel a mounting bar, which is separately sold, and then ● fasten the plate to the fixed mounting bar. Refer to the previous article, “ when the mounting plate is ● position of wall hole. Make a hole of 70 mm in diameter, sli... 58 domestic air conditioner 1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed. 2. Pull out the cable on the front side, and connect the cable making a loop. When connecting the cable, confirm the terminal number of indoor and outdoor units c... 59 domestic air conditioner 6 reduced. Maintenance setting of proper room temperature close doors and windows during operation if the unit is not to be used for a long time, turn off the power supply main switch. Use the timer effectively use the louvers effectively do not block the air inlet or out... 60 domestic air conditioner the power supply cord and so on. 2.Do not install in the place where there is any possibility of inflammable gas leakage around the unit. 3.Do not get the unit exposed to vapor or oil steam. Cautions please call sales/service shop for the installation. Do not attempt to i... Domestic air conditioner 61 trouble shooting normal performance inspection noise is heard phenomenon cause or check points the system immediately. Smells are generated. Mist or steam are multiple check poor cooling when unit is stopped, it won't restart elapsed to protect the system. When the electr... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 62 7 service diagnosis 7.1 caution for diagnosis the operation lamp flashes when any of the following errors is detected. 1.When a protection device of the indoor or outdoor unit is activated or when the thermistor malfunctions, d... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 63 7.3.Error codes and description indoor display code indication indoor outdoor (led1 flash times) description reference page indoorand outdoor e7 15 communication fault between indoor and outdoor units page .72 e1 room temperatu... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 64 7.3.1thermistor or related abnormality (indoor unit) w)b((-/=c.L4ej/ s#: room temperature sensor failure s%: heat-exchange sensor failure 8*,a(b/(k/ / / / / / / / the temperatures detected by the thermistors are used to determi... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 65 7.4.2 indoor fan motor malfunction w)b((-/=c.L4ej/ s#n 8*,a(b/(k/ / / / / / / / the rotation speed detected by the hall ic during fan motor operation is used to determine 8e4kg)+,c()/ ///// abnormal fan motor operation/ =*,*+,c... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 66 7.3.3 ipm protection does fan rotate smoothly? No yes turn power on and operate fan does it rotate? No yes turn off power supply and disconnect fan motor connector,then turn power on check output of fan motor connector i s m o ... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 67 (g,b((-/bc.L4ej/// // led1 flash 2 times: w)b((-/=c.L4ej/ / 5# / 8*,a(b/(k/ / / / / / / / ipm protection is detected by checking the compressor running condition and so on. 8e4kg)+,c()/// / /// =*,*+,c()/ 8e4kg)+,c()/ / / / / /... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 68 7.3.4 the ipm and outdoor pcb don’t communicate or related abnormality (g,b((-/bc.L4ej/// / led1 flash 4 times indoor display f3 / / / 8*,a(b/(k/ / / / / / / communication is detected by checking the ipm module and the outdoor ... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 69 7.3.5 thermistor or related abnormality(outdoor unit) 5-(.,y-*f(qc)d/,*fl*-e,g-*/.*).(-/kec4g-*/ / w)b((-/bc.L4ej? 5%# (g,b((-/bc.L4ej? Led1 flash 10 times: soaeg.,/,*fl*-e,g-*/.*).(-/kec4g-*// / w)b((-/bc.L4ej: 5%h/ (g,b((-/bc... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 70 7.3.6 overheat protection for exhaust temperature w)b((-/bc.L4ej// /// /// /// /// // 5n (g,b((-/bc.L4ej led1 flash 8 times 8*,a(b/(k/ / / / / / / / the exhaust temperature control is checked with the temperature being detected... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 71 yes no [i:i[/ / pa*/ss0 / w)b((-/=c.L4ej/ / / / / sn: ˖indoor eeprom error 5#%˖outdoor eeprom error 8*,a(b/(k/ / / / / / / / the data detected by the eeprom are used to determine mcu / 8e4kg)+,c()/ / / / / =*,*+,c()/ 8e4kg)+,c(... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 72 7.3.8 communication error between the indoor and outdoor units / w)b((-/bc.L4ej// /// /// /// // s[˗ @g,b((-:/bc.L4ej˖ led1 flash 15 times / / 8*,a(b/(k/ / / / / / / / the date received from the another unit in indoor unit-outd... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 73 ˄a˅ no yes yes check the status of led1 on the indoor mainboard. If the led1 blinks no if the voltage is of a constant value of 0v dcto5v dc yes measure the voltage between jumpers 3 and 4 of ic8 on the indoor mainboard with a ... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 74 7.3.10 power supply over or under voltagve fault w)b((-/bc.L4ej// // / / / / / / / / / / / / / / / / / / / / / / / / 5#\ (g,b((-/bc.L4ej? Led1 flash 6 times 8*,a(b/(k/ / / / / / an abnormal voltage rise or fall is detected by c... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 75 7.3.11 loop of the station detect error @g,b((-/=c.L4ej/ / ]s=#//k4e.A//#9 //,cf*./ / / w)b((-/=c.L4ej/// 5##/ / ]s=#//k4e.A //#\/ /,cf*. ///w)b((-/ =c.L4ej/// 5%9/ 8*,a(b/(k/ / / / / / / / the position of the compressor rotor ... As24gs1/2era 1u24gs1era-sm service diagnosis domestic air conditioner 76 yes 7.3.12 over-current of the compressor @g,b((-/=c.L4ej/ led1 flash 3 or 24 or 25 times 8*,a(b/(k/ / / / / / / / the current of the compressor is too high/ 8e4kg)+,c()/// / // =*,*+,c() 8e4kg)+,c()/ / / / / / when the ipm mod... Domestic air conditioner 7 7 installation installation manual of room air conditioner 8 installation as24gs1/2era 1u24gs1era-sm ce all the products are in conformity with the following european provision: - low voltage directive 73/23/eec - low voltage directive 2006/95/ec -electomagnetic compatibil... 78 domestic air conditioner installation as24gs1/2era 1u24gs1era-sm please be subject to the actual product purchased. The above indoor and outdoor units’ picture is just for your reference. F a c e d optional parts for piping non-adhesive tape adhesive tape saddle (l.S) with screws connecting elect... 7 9 domestic air conditioner installation as24gs1/2era 1u24gs1era-sm warning caution. 80 domestic air conditioner installation as24gs1/2era 1u24gs1era-sm. Precautions for handling units for use with r410a o!Not!Use!The!E"isting!Refrigerant!#i#ing the!Old!Refrigerant!And!Refrigerator!Oil!In!The!E"isting!#i#ing contain!A!Large!Amount!Of!Chlorine$!Which!Will!Cause!The refrigerator!Oil!In!The!New!Unit!To!Deteriorate% r410a!Is!A!Highressure!Refrigerant$!An... Before installing (relocating) the unit or performing electric work round!The!Unit" #o!Not!Connect!The!Grounding!On!The!Unit!To!Gas!$i$es%water $i$es%!Lightning!Rods%!Or!The!Grounding!Terminals!Of tele$hones"!Im$ro$er!Grounding!$resents!A!Risk!Of!Electric shock%!Smoke%!Fire%!Or!The!Noise!Caused!&'!I... Installation as24gs1/2era 1u24gs1era-sm 83 domestic air conditioner. Installation as24gs1/2era 1u24gs1era-sm 84 domestic air conditioner. No wind direction air outlet cushion rubber 4.Installation dimension(unit:mm) * as24gs1/2era 1u24gs1era-sm 86 domestic air conditioner installation. 1u07bs1era 1u09bs1era 1u12bs1era 1u18fs1era 1u24gs1era 1. Outdoor unit indoor unit a b outdoor unit indoor unit a b a b outdoor unit indoor unit oil trap to bend a pipe, give the roundness as large as possible not to crush the pipe , ƽ and the bending radius should be 30 to 40 mm or longer. Connecti... As24gs1/2era 1u24gs1era-sm 88 domestic air conditioner installation. (e.G.1u18fs1era) as24gs1/2era 1u24gs1era-sm 89 domestic air conditioner installation. 1u07bs1era 1u09bs1era 1u12bs1era 1u18fs1era 1u24gs1era t 25a/250v. 3 2 ^ 1 ) (n ) (l ) (c 3 2 1 ) (n ) (l ) (c to indoor unit 1u07bs1era 1u09bs1era 1u12bs1era 1u18fs1era 1u24gs1era model connecting wiring power cable 3g2.5mm 2 3g4.0mm 2 3g1.5mm 2 4g0.75mm 2 4g0.75mm 2 4g0.75mm 2 n( 1 3 ) ) c( l( 2 )... 15 outdoor unit troubleshooting 2 9 15 8 12 10 5 13 19 1 18 4 11 6 25 25 25 110 haier group address:no.1 haier road,hi-tech zone,qingdao 266101 p.R.China contacts: tel +86-532-8893-6943;fax +86-532-8893-1010 website: www.Haier.Com suction temperature sensor failure when the the wiring of compressor ... 92 domestic air conditioner removal of procedure as24gs1/2era 1u24gs1era-sm 9.1 removal of front panel procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step s t n i o p e r u d e c o r p 1. Remove the front panel. Start the removal ... 93 domestic air conditioner removal of procedure as24gs1/2era 1u24gs1era-sm 1. Lift an air filter upwards slightly and then pull it out downwards. Insert the air filters along grooves when installing. When installing, insert 2 hooks of the air filter completely. Step s t n i o p e r u d e c o r p. 94 domestic air conditioner removal of procedure as24gs1/2era 1u24gs1era-sm 9.3 removal of horizontal blade and front grill 1 release the marked four hooks. When assembling, install the front grille horizontally so as not to stuff the flap inside. When assembling, make sure the three hooks are caugh... 95 domestic air conditioner removal of procedure as24gs1/2era 1u24gs1era-sm procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step procedure points 2. Remove the horizontal blade. The horizontal blade is single. Installation procedur... 96 domestic air conditioner removal of procedure as24gs1/2era 1u24gs1era-sm 4 pull the front grille out horizontally and remove it. When assembling, install the front grille horizontally so as not to stuff the flap inside. When assembling, make sure the three hooks are caught properly. Step procedur... 97 domestic air conditioner removal of procedure as24gs1/2era 1u24gs1era-sm procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step procedure points remove the front grille. Remove the assembly of the reduction motor. 1. Remove the dr... 98 domestic air conditioner procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step procedure points 2 push the hooks on the back of the vertical blades and remove. Loosen the marked 1 screws 9.5 removal of vertical blade and swing mo... Domestic air conditioner 99 procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step procedure points remove the front grille. Discharge the static electricity from your body before touching the electric parts like signal receiver pcb.... 100 domestic air conditioner procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step procedure points you can detach the indoor unit without removing the assembly of the outlet grille. Caution if gas leaks, repair the spot of leaking,... 101 domestic air conditioner procedure warning be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step procedure points 1 loosen the 6 screws. 2 remove the right side plate. 9.8 removal of fan and fan motor removal of procedure as24gs1/2era 1u24gs1era-... 102 domestic air conditioner 9.9 removal of outdoor panel step procedure points 1. Features 1 loosen the service cover screw and remove the service cover. Be careful not to fxw\rxu¿qjhue\ wkh¿qvriwkhkhdw h[fkdqjhu removal of procedure as24gs1/2era 1u24gs1era-sm. 103 domestic air conditioner step procedure points 2. Remove the panels. 1 loosen the 4 screws and lift the top panel 2 loosen the screws of the panel. 3 pull and remove the front panel. Removal of procedure as24gs1/2era 1u24gs1era-sm. 104 domestic air conditioner 9.10 romoval of electrcal box step procedure points 5hpryhwkh¿[lqj screws, then lift the electrical box * * * * * * * removal of procedure as24gs1/2era 1u24gs1era-sm. 105 domestic air conditioner 9.11 romoval of the side panel step procedure points 1 /rrvhqwkh¿[lqj screws and remove the side panel. Removal of procedure as24gs1/2era 1u24gs1era-sm. 106 domestic air conditioner step procedure points 2 remove the edfnsdqho 3 /rrvhqwkh¿[lqj screws and remove the side panel. Removal of procedure as24gs1/2era 1u24gs1era-sm. 107 domestic air conditioner step procedure points 1 loosen the ¿[lqjvfuhzdqg remove the fan put the lead wire wkurxjkwkhedfn of motor when dvvhpeolqjvrdv qrwwrhqwdqjohgzlwk the propeller fan) 9.12 removal of fan and fan motor removal of procedure as24gs1/2era 1u24gs1era-sm. 108 domestic air conditioner step procedure points 2 /rrvhqwkh¿[lqj screws and lift the fan motor. Removal of procedure as24gs1/2era 1u24gs1era-sm. 109 domestic air conditioner step procedure points 3 5hpryhwkh¿[lqj screws, then lift the idqprwrueudfnhw removal of procedure as24gs1/2era 1u24gs1era-sm. 110 domestic air conditioner step procedure points 4 5hpryhwkh¿[lqj screws, then lift the proof plate. Removal of procedure as24gs1/2era 1u24gs1era-sm. 111 domestic air conditioner 135rprydorifrpsuhvvrudqgkhdwh[fkdqjhu step procedure points 1 cut down the frqhfwlqjslsh and pull out the compressor and remove the ydoxheudfnhw removal of procedure as24gs1/2era 1u24gs1era-sm. 112 domestic air conditioner step procedure points 2 /rrvhqwkhpdunhg ¿[lqjvfuhzv removal of procedure as24gs1/2era 1u24gs1era-sm. 113 domestic air conditioner step procedure points 3 /rrvhqwkh¿[lqj krrndqguhpryh wkhkhdwh[fkdqjhu removal of procedure as24gs1/2era 1u24gs1era-sm. 114 domestic air conditioner step procedure points 4 remove the ydoyheudfnhw removal of procedure as24gs1/2era 1u24gs1era-sm. / as24gs1/2era 1u24gs1era-sm / / / / / / / / / / / / / / tc-c)d/=ced-ef. Domestic air conditioner 115 10.Wiring diagrams 10..1. Indoor unit. As24gs1/2era 1u24gs1era-sm domestic air conditioner 116 10.2.Outdoor unit %˖%/$&. :˖:+,7( 25˖25$1*( %/˖%/8( 5˖5(' $&1287 &1 &1 $&/287 &1 :$ 0 &1 &1ⱑ 9$/9($ &1 $&)$1 0 $&)$1 &1 3( 3 2 : ( 5 : &1 &20% &20$ 1 5 &1 &1 $&1 $&/ )86( 7$9$& &1 &1 02'8/(&20 02'8/(32:(5 7 2 , 1 ' 2 2 5 8 1 , 7 &1 &1 % %/ %/ 2... / as24gs1/2era 1u24gs1era-sm/ / / / / / / / / / / / / / "c-+gc,/=ced-ef. Domestic air conditioner 117 11.Circuit diagrams 11.1.Indoor unit a0 1 a1 2 a2 3 vss 4 sda 5 scl 6 test 7 vcc 8 ic1 at24c02b r33 560- +5v c11 0.1uf r29 10k r30 10k scl sda eeprom r3 2k c1 0.1uf r11 2k r23 10k r10 10k +5v reset ... / as24gs1/2era 1u24gs1era-sm/ / / / / / / / / / / / / / "c-+gc,/=ced-ef. Domestic air conditioner 118 11.2.Outdoor unit 11.2.1 control board circuit diagrams v a l v e d 1 1 v a l v e c 1 2 m o d e 3 v a l v e b 1 4 v a l v e a 1 5 r e s e t 6 x o u t 7 v s s /a v s s 8 x in 9 v c c /a v c c 1 0 s d... / as24gs1/2era 1u24gs1era-sm/ / / / / / / / / / / / / / "c-+gc,/=ced-ef. Domestic air conditioner 119 1 cn26 p 1 cn24 n e1 680u/400v/450v e2 680u/400v/450v cx6 105/275vac r23 220k/2w led2 power 250 connector 250 connector p n 11.2.2 module board circuit diagram c 0 0 9 4 7 1 1 2 3 4 5 6 7 8 9 10 11 ... Domestic air conditioner appendix 12 description of coding rules of unit model 120 as24gs1/2era 1u24gs1era-sm examples: as09gs1era ,it represents wall-mounted split type heat pump air conditioner cooling capacity is 9000btu/h,and the power supply is 220-240v/50hz,”s” means easy stock ,and"e" means t... Wu hongjin zhao ni zhang fei yang bifei 86 532 88936935 the end sincere forever haier group as18gs1era 1u18fs1era-sm.Summary of 1U24GS1ERA
Page 1
Page 2
Page 3
Page 4
Page 5
Page 6
Page 7
Page 8
Page 9
Page 10: 3 Specification
Page 11
Page 12
Page 13
Page 14
Page 15
Page 16
Page 17: Hi5G)+C,c()./e)B/"(),-(4/
Page 18
Page 19
Page 20
Page 21
Page 22
Page 23
Page 24
Page 25
Page 26
Page 27
Page 28
Page 29
Page 30
Page 31
Page 32
Page 33
Page 34
Page 35
Page 36
Page 37
Page 38
Page 39
Page 40
Page 41
Page 42
Page 43
Page 44
Page 45
Page 46
Page 47
Page 48
Page 49
Page 50
Page 51
Page 52
Page 53
Page 54: Haier Group
Page 55
Page 56
Page 57
Page 58
Page 59
Page 60
Page 61
Page 62
Page 63
Page 64: Haier Group
Page 65
Page 66
Page 67
Page 68
Page 69
Page 70
Page 71
Page 72
Page 73
Page 74
Page 75
Page 76
Page 77: / / / / / / / / / /
Page 78
Page 79
Page 80: 8 Installation
Page 81
Page 82
Page 83
Page 84
Page 85
Page 86
Page 87
Page 89
Page 90
Page 91
Page 92
Page 93
Page 94
Page 95
Page 96
Page 97
Page 98
Page 99
Page 100
Page 101
Page 102
Page 103
Page 104
Page 105
Page 106
Page 107
Page 108
Page 109
Page 110
Page 111
Page 112
Page 113
Page 114
Page 115
Page 116
Page 117
Page 118
Page 119
Page 120
Page 121
Page 122
Page 123
Page 124: Sincere Forever