IBall NIRANTAR 1006B User Manual

Manual is about: 1KVA - 3KVA Online UPS

Summary of NIRANTAR 1006B

  • Page 1

    1kva - 3kva online ups user manual.

  • Page 2

    Table of contents 1. Important safety warning ....................................................................................................... 1 1-1. Transportation ................................................................................................................. 1 1-2. Prepara...

  • Page 3

    1 1. Important safety warning please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating i...

  • Page 4

    2 1-5. Maintenance, service and faults  the ups system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel.  caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components inside the ups sys...

  • Page 5

    3 2. Installation and setup note: before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. Note: there are two different types of online ups: standard and long-run models. Please refer to the fo...

  • Page 6

    4 step 3: communication connection communication port: usb port rs-232 port intelligent slot to allow for unattended ups shutdown/start-up and status monitoring, connect the communication cable one end to the usb/rs-232 port and the other to the communication port of your pc. With the monitoring sof...

  • Page 7

    5 3. Operations 3-1. Button operation button function on/mute button  turn on the ups: press and hold on/mute button for at least 2 seconds to turn on the ups.  mute the alarm: when the ups is on battery mode, press and hold this button for at least 5 seconds to disable or enable the alarm system....

  • Page 8

    6 display function remaining backup time information indicates the remaining backup time in pie chart. Indicates the remaining backup time in numbers. H: hours, m: minute, s: second fault information indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes ar...

  • Page 9

    7 3-3. Audible alarm battery mode beeping every 4 seconds low battery beeping every second overload beeping twice every second fault continuously beeping bypass mode beeping every 10 seconds 3-4. Lcd display wordings index abbreviation display content meaning ena enable dis disable esc escape hls hi...

  • Page 10

    8 01: output voltage setting interface setting parameter 3: output voltage for 200/208/220/230/240 vac models, you may choose the following output voltage: 200: presents output voltage is 200vac 208: presents output voltage is 208vac 220: presents output voltage is 220vac 230: presents output voltag...

  • Page 11

    9 05: eco voltage range setting interface setting parameter 2 & 3: set the acceptable high voltage point and low voltage point for eco mode by pressing down key or up key. Hls: high loss voltage in eco mode in parameter 2. For 200/208/220/230/240 vac models, the setting range in parameter 3 is from ...

  • Page 12

    10 08: autonomy limitation setting interface setting parameter 3: set up backup time on battery mode for general outlets. 0-999: setting the backup time in minutes from 0-999 for general outlets on battery mode. 0: when setting as “0”, the backup time will be only 10 seconds. 999: when setting as “9...

  • Page 13

    11 6. Click the “ups setting” option and select “parameters setting”. (please see images below) 7. The parameters setting windows will be shown as below..

  • Page 14

    12 8. Input the group number to the box of marked in above image , and click the right side “apply” button . Note: please follow below steps to calcul ate battery group number to insert into “number in marked box. A. Battery group number = external battery ah / standard ups battery ah for example,if...

  • Page 15

    13 battery mode when the input voltage is beyond the acceptable range or power failure and alarm is beeping every 4 second, ups will backup power from battery. Bypass mode when input voltage is within acceptable range but ups is overload, ups will enter bypass mode or bypass mode can be set by front...

  • Page 16

    14 4. Troubleshooting if the ups system does not operate correctly, please solve the problem by using the table below. Symptom possible cause remedy no indication and alarm even though the mains is normal. The ac input power is not connected well. Check if input power cord firmly connected to the ma...

  • Page 17

    15 symptom possible cause remedy fault code is shown as 01, 02, 03, 04, 05, 11, 12, 13 and 41 on lcd display and alarm is continuously beeping. A ups internal fault has occurred. There are two possible results: 1. The load is still supplied, but directly from ac power via bypass. 2. The load is no l...

  • Page 18

    16 6. Specifications model iball nirantar online ups 1006b (1kva - w battery) 1012e (1kva - w/o battery) 3001e (3kva - w/o battery) input capacity 1000 va / 800 w 3000 va / 2400 w voltage range low line transfer 160 vac / 140 vac / 120 vac / 110 vac ± 5 % ( based on load percentage 100% - 80 % / 80 ...

  • Page 19

    17 battery mode beeping every 4 seconds low battery beeping every second overload beeping twice every second fault continuously beeping physical dimension, d x w x h (mm) 397 x 145 x 220 419 x 190 x 318 net weight (kgs) 13 6 13 environment humidity 20-90 % rh @ 0- 40°c (non-condensing) noise level l...

  • Page 20

    18 note:  warranty: all iball products are governed by iball warranty terms. Refer www.Iball.Co.In for details.  product specifications are subject to change without notice,  all trademarks, logos, brands & product names are properties of their respective owners,  for any technical help on iball...