IBall NIRANTAR 1006B User Manual - page 14
12
8.
Input the group number to the box of marked in above image
, and click the right side “Apply” button
.
Note:
Please follow below steps to calcul
ate Battery group number to insert into “Number in marked box.
a. Battery group number = External battery AH / Standard UPS battery AH
For example,If you have connected
100AH
batteries
Standard UPS battery AH for 3KVA is 9AH; means Battery group number = 100/9 ~=11.
9.
Insert “11” in Battery number setting, under “Number in Parallel” box, If the password dialog will popup.
Please enter the password
(default password is “administrator”). If the password is ok, please click the
“Apply” button once again, and then the setting will be saved.
10. Disconnect the AC input and wait until the LCD display is off. The setting of ups is finish.
3-6. Operating Mode Description
Operating mode Description
LCD display
Online mode
When the input voltage is within
acceptable range, UPS will provide pure
and stable AC power to output. The
UPS will also charge the battery at
online mode.
ECO mode
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass
voltage to output for energy saving.
Frequency
Converter mode
When input frequency is within 40 Hz to
70 Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The
UPS will still charge battery under this
mode.