JAYLINE WALLTHERM AIR Installation Instructions Manual

Other manuals for WALLTHERM AIR: Installation & Operation Instructions
Manual is about: FREESTANDING WOOD FIRE

Summary of WALLTHERM AIR

  • Page 1

    November 2016 1 150mm free standing wood fire flue kit mkiii installation instructions warning: this flue kit has been manufactured in accordance with as/nzs 2918:2001 and tested to appendix f. To ensure safety this flue kit must be installed as outlined in these instructions and the appropriate req...

  • Page 2: Walltherm

    November 2016 2 5) fix an appropriate flashing around the outer galv liner to seal onto the roofing material. Refer to the manufacturer’s recommendations for the correct fitting. Nb:onironroofs,fixingssuchasmetalanglebrackets(40mmx40mm)canbefittedundertheflashingto securelyfixtherooftooutergalvliner...

  • Page 3

    November 2016 3 17) leave all installation and operating instructions with the owner. The satin black painted flue pipe can be touched up using only stove bright aerosol paint. The stainless steel pipe used in the jayline mklil flue kit is warranted for five years from date of purchase to the initia...

  • Page 4: Walltherm

    November 2016 4 sloping ceiling installation theinstructionsforaslopingceilingandaflatceilingarethesameexceptforthefollowing: a) the 200mm inner liner, and the 250mm outer liner will need to be trimmed to the angle required to suit the ceiling (between 15-45 degrees). B) fitted to the non swaged end...

  • Page 5: Diagram A

    November 2016 5 roof and ceiling installation assembly list fixed cowl 150mm apron cover top spacing bracket stainless flue 150 x 600 galv slip liner 253 x 1200 stainless flue 150 x 1200 mounting rails (supplied) inner galv liner 200 x 1200 outer galv liner 250 x 1200 ceiling plate mounting rails (s...

  • Page 6: Diagram B

    November 2016 6 12mm gap to ensure the correct air flow. 250mm outer liner 200mm inner liner 150mm flue pipe ceiling timber framing tighten the ceiling plate so it touches the ceiling (do not over tighten) this diagram is suitable for flat ceilings only the 250mm outer liner can be secured directly ...

  • Page 7: Diagram C

    November 2016 7 b 250mm outer liner 200mm inner liner 150mm flue pipe framing timber ceiling plate with spacers (do not over tighten) ceiling the 250mm outer liner can be secured directly to timber framing at both the ceiling & roof penetration ends this diagram is suitable for sloping ceilings 15-4...

  • Page 8

    November 2016 8 3000 3000 or less more than 3000 1000 min. If clear within 3000 of flue top increase as necessary until nothing within 3000 of flue top any nearby structure 3000 600 5 increase from 1000 min. Until clear within 3000 of flue top 3000 or less more than 3000 3000 600 diagram 4 notes: depen...

  • Page 9

    November 2016 9 392 892 4 11 11 170 240 hole cut for 45 degree ceiling ceiling plate required as tested 9 diagram of 45° ceiling plate walltherm ® air.

  • Page 10: Flue Kit Black 4.2M Mkiii

    November 2016 10 flue kit black 4.2m mkiii contentsinclude: • 2 x flue stainless steel 150 x 1200mm (black) • 1 x flue stainless steel 150 x 1200mm • 1 x flue stainless steel 150 x 600mm • 1 x flue galvanised liner combination (inner: 200 x 1200mm / outer: 250 x 1200mm) • 1 x flue outer galvanised l...

  • Page 11

    November 2016 11.