Column 1 2 3 4 5 6 7 8 9 10
04.06.2005 16:55:30 0 363.8 0.37 134 226.1 0.53 103 23
04.06.2005 16:55:40 0 366.0 0.39 142 226.1 0.53 112 23
04.06.2005 16:55:50 0 359.5 0.41 147 226.1 0.53 116 23
04.06.2005 16:56:00 0 369.8 0.42 155 226.1 0.58 118 23
04.06.2005 16:56:10 0 377.0 0.43 162 226.1 0.63 131 23
04.06.2005 16:56:20 0 373.6 0.45 168 226.1 0.63 133 23
04.06.2005 16:56:30 0 364.0 0.48 174 226.1 0.68 146 23
04.06.2005 16:56:40 0 364.3 0.49 178 226.1 0.68 146 23
Figure 4.7: Extract from a
communication protocol via RS232
interface
Column Explanation
Column
Explanation
1
Date
6
Generator power in W
2
Hour
7
Grid voltage in V
AC
3
Operating mode/status (see below)
8
Grid current, delivered current in A
AC
4
Generator voltage in V
9
Grid-Utility Company power in W
5
Generator current in A
DC
10
Device temperature in °C
Table 4-1: Explanation of column headings in figure 4.7
Status
Explanation
Comment
0
Inverter has just switched on
Only after the first start-up in the morning.
1
Waiting for start
Grid parameters and generator voltage are checked.
2
Waiting for shut-down
Insufficient generator voltage and generator power.
Condition that precedes the night shutdown.
5
Grid feeding operation
The inverter starts feeding into the grid.
15
Transition to night cut-off
Inverter “goes to sleep”
16
Inhibited operation
3 errors during self test – operation will be resumed after
complete shutdown
24
DSP error
error
- Communication error
- Grid shutdown frequency
- Offset (grid feeding is to high)
- High-temperature cut-off
- Transducer (Plausibility error – measuring technique)
- Impedance cut off
- Overload cut off
25
Self test of power electronics
The shutdown behavior of the power electronics is
checked before the start of the grid-feeding process
26
Self test of grid isolation relay
The grid isolation relay is checked before the start of the
grid-feeding process.
28
Hardware error
Self test was unsuccessful, a defect has occurred.
Table 4-2: Explanation of RS232 operating code column 3