Kane Hawk5000 Operator's Manual - Troubleshooting
HAWK 5000 OPERATOR MANUAL
KANE INTERNATIONAL LIMITED
13
Troubleshooting
HAWK5000 program
a)
The program displays '
Logger Not Found
' for more than a few seconds:
Is the HAWK powered up?
Is the HAWK connected by the correct serial lead to the PC?
Is the HAWK connected to the correct serial port on the PC?
Click SCAN NOW to try to re-establish communication
Starting a survey : Logging light doesn't flash
a)
A new survey has not been started:
Use HAWK5000 control program to start a new survey.
b)
Start time not yet reached:
Use HAWK5000 control program to change start time.
c)
Start next power up:
Disconnect the mains power lead from the HAWK and then re-connect it.
d)
If Phaser light is flashing, use PHASER.
Starting a survey: HAWK bleeps and CT lights flash
a)
The HAWK is set up for three-phase operation, but the CT clamps are not on three
different phases:
Use HAWK5000 program to change set-up.
b)
The HAWK is set up for single-phase operation, but the CT clamps are not all on the
same phase:
Use HAWK5000 program to change set-up.
c)
One or more of the CT clamps are on backwards:
Ensure the arrow on the CT clamps points towards the load.