Insulation Work
Installation
59
3.4.3 Install the pendant bolt
①
Ceiling installation
Select the position of installation hooks according to the hook holes positions showed in upper picture.
Drill four holes of Ø12mm, 45~50mm deep at the selected positions on the ceiling. Then embed the
expansible hooks (fittings).
①
Wall-mounted installation
Install the tapping screws onto the wall.(Refer to picture below)
3.4.4 Install the main body
①
Ceiling installation (The only installation method for the unit with drain pump)
Remove the side board and the grille.