Kaysun Zen On 2014 Service Manual - page 83
Electrical Control Function
Electrical Control
77
For Ceiling & Floor:
T3
TE10
Off
On
TE11
When T3
≥
TE10, the compressor will shut off. When T3
<
TE11,the compressor will restart.
1.3.3 Heating Mode
1.3.3.1 Compressor running rules:
For Duct & super-slim cassette type: Once the compressor starts up, it keeps running 7 minutes,
For Ceiling & Floor
: Once the compressor starts up, it keeps running HEATFTIM minutes,
then it will follow the below rules:
When indoor room temp.T1 is higher than Tgap0, the compressor and outdoor fan will shut off. When T1 is
lower than Tgap0-1, the compressor and outdoor fan will start up.
Tgap0
T1-TS
On
Off
Tgap0-1
For Ceiling & Floor:Tgap0
= setting temperature-compensation.
1.3.3.2 Outdoor fan running rules:
Fan(below): The outdoor fan runs all the time.
Fan(above):
18
T4
Off
On
16
1.3.3.3 Indoor fan running rules:
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind function
has the priority.