KeepRite DLCCAR Service Manual

Other manuals for DLCCAR: Installation instruction
Manual is about: High Wall Ductless Split System - Sizes 09 to 36

Summary of DLCCAR

  • Page 1

    Specifications subject to change without notice. Dlfcab / dlccar / dlfchb / dlcchr dlfdab / dlcdar / dlfdhb / dlcdhr service manual high wall ductless split system − sizes 09 to 36 table of contents page safety considerations 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Introduction 1...

  • Page 2

    2 328 080000 01 specifications subject to change without notice. Model / serial number nomenclatures b a j unit type b = high wall system type a = cooling only q = heat pump 1 = all models indoor unit dlf c a 09 dlf = fan coil unit c = model d = model a = all models nominal capacity 09 - 3/4 ton 12 ...

  • Page 3

    328 080000 01 3 specifications subject to change without notice. Dimensions − indoor fig. 1 - indoor unit dimensions table 1—dlfcab / dlccar / dlfchb / dlcchr system size 9k 12k 9k 12k 18k 24k 30k 36k voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-...

  • Page 4

    4 328 080000 01 specifications subject to change without notice. Dimensions − outdoor n m h d w s p fig. 3 - outdoor unit table 5—dlfcab / dlccar / dlfchb / dlcchr system size 9k 12k 9k 12k 18k 24k 30k 36k voltage 115/1/60 115/1/60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208...

  • Page 5

    328 080000 01 5 specifications subject to change without notice. Clearances − indoor 6" (0.15m) min. 5" (0.13m) min. 6' 5" (0.13m) min. (1.8m) ceiling floor fig. 4 - indoor unit clearance clearances − outdoor a d b air-outlet air-inlet c e fig. 5 - outdoor unit clearance table 7—outdoor clearances u...

  • Page 6: Caution

    6 328 080000 01 specifications subject to change without notice. Wiring all wires must be sized per nec (national electrical code) or cec (canadian electrical code) and local codes. Use the electrical data table mca (minimum circuit amps) and mocp (maximum over current protection) to correctly size ...

  • Page 7

    328 080000 01 7 specifications subject to change without notice. Connection diagrams fig. 6 - connection diagram 9k & 12k units 115v fig. 7 - connection diagram 9k & 12k units 208/230v fig. 8 - connection diagram 18k − 36k units 208/230v.

  • Page 8

    8 328 080000 01 specifications subject to change without notice. Wiring diagrams table 10—wiring diagrams symbol symbol color symbol symbol color symbol name wh white gn green cap jumper cap ye yellow bn brown comp compressor rd red bu blue grounding wire yegn yellow/green bk black / / vt violet og ...

  • Page 9

    328 080000 01 9 specifications subject to change without notice. Wiring diagram indoor unit − dlfcab/dlfchb (cont) fig. 10 - indoor unit sizes 18 − 24 (208/230v) fig. 11 - indoor unit sizes 30 − 36 (208/230v).

  • Page 10

    10 328 080000 01 specifications subject to change without notice. Wiring diagram − outdoor unit − dlccar / dlcchr fig. 12 - outdoor unit sizes 09 − 12 (115v) fig. 13 - outdoor unit sizes 09 − 12 (208/230v).

  • Page 11

    328 080000 01 11 specifications subject to change without notice. Wiring diagram − outdoor unit − dlccar / dlcchr (cont) fig. 14 - outdoor unit size 18 (208/230v) fig. 15 - outdoor unit size 24 (208/230v).

  • Page 12

    12 328 080000 01 specifications subject to change without notice. Wiring diagram − outdoor unit − dlccar / dlcchr (cont) fig. 16 - outdoor unit sizes 30 − 36 (208/230v) wiring diagram − indoor unit − dlfdab / dlfdhb fig. 17 - indoor unit sizes 09 − 12 (115v).

  • Page 13

    328 080000 01 13 specifications subject to change without notice. Wiring diagram − indoor unit − dlfdab / dlfdhb (cont) fig. 18 - indoor unit sizes 09 − 24 (208/230v) 287'22581,7 *(1(5$725 &22/3/$60$ -803 &$3 7(06(1625 5220 78%( 7(06(1625 )$102725 6:,1*02725 $3 6:,1*8' 78%( 5220 $&/ ',63/$ $3 ',63 '...

  • Page 14

    14 328 080000 01 specifications subject to change without notice. Wiring diagram − outdoor unit − dlcd :$51,1* 3ohdvhgrqwwrxfkdq\hohfwurqlf frpsrqhqwdqgwhuplqdozkhqwkhpdfklqh lvuxqqlqjvwrsslqjrukdvehhq srzhuhgriiiruohvvwkdqplqxwhvwr suhyhqwhohfwulfvkrfn 1 / 32:(5 jurxqg rqo\ 127( 8 9 &1 $&/ %8 ( %1 ...

  • Page 15

    328 080000 01 15 specifications subject to change without notice. Wiring diagram − outdoor unit − dlcd (cont) $3 7(036(1625 (;+$867 7(036(1625 2875220 28778%( 7(036(1625 %. :+ %8 ; &203 6$7 :+ :+ 29&b&203 5' 57 57 57 * * 5' %8 8%8 9 7b6(1625 29(5/2$'3527(&725 / 0$*1(7,& 5,1* / / $&b/ 1 &20b,11(5 3( ...

  • Page 16

    16 328 080000 01 specifications subject to change without notice. Wiring diagram − outdoor unit − dlcd (cont) ,1'22581,7 +($7b/ +($7b1 / / / 5' %8 :$51,1* plqxwhvwrsuhyhqwwkhulvn srzhuhgriiiruohvvwkdq uxqqlqjvwrsslqjrukdvehhq whuplqdozkhqwkhpdfklqhlv 3ohdvhgrqwwrxfkdq\ rihohfwulfvkrfn 97 97 %.%1 :+%...

  • Page 17

    328 080000 01 17 specifications subject to change without notice. Wiring diagram − outdoor unit − dlcd (cont) fig. 26 - outdoor unit dlcdhr size 30 (208/230v) fig. 27 - outdoor unit dlcdhr size 36 (208/230v).

  • Page 18

    18 328 080000 01 specifications subject to change without notice. Pcb printed diagrams table 11—pcb printed diagrams no. Description 1 this terminal is not used 2 zero line 3 indoor fan motor 4 this jumper is not used 5 jumper 6 vertical swing motor 7 this terminal is not used 8 horizontal swing mot...

  • Page 19

    328 080000 01 19 specifications subject to change without notice. Pcb printed diagrams (cont) 2 1 3 4 5 6 7 8 9 10 11 12 13 14 15 16 fig. 28 - indoor units dlfcab / dlfchb sizes 9 to 24 top view table 12—indoor units dlfcab / dlfchb 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 neutral wire dc fan up & dow...

  • Page 20

    20 328 080000 01 specifications subject to change without notice. Pcb printed diagrams (cont) 1 2 2 2 3 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 fig. 30 - indoor units dlfcab / dlfchb sizes 30 and 36 top view table 13—indoor units dlfcab / dlfchb 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18...

  • Page 21

    328 080000 01 21 specifications subject to change without notice. Pcb printed diagrams (cont) 4 3 2 1 5 6 7 8 9 10 11 12 13 grjw819-a3 v1.2 2013/06/25/12 fig. 32 - outdoor units dlccar / dlcchr 115v sizes 9 and 12 top view table 14—outdoor units dlccar / dlcchr no. Name no. Name no. Name 1 compresso...

  • Page 22

    22 328 080000 01 specifications subject to change without notice. Pcb printed diagrams (cont) 2 1 3 4 5 6 8 7 9 10 11 12 13 fig. 34 - outdoor units dlccar / dlcchr 208/230v sizes 9 and 12 top view table 15—outdoor units dlccar / dlcchr 1 live wire input 4 ground wire input 7 electric heater compress...

  • Page 23

    328 080000 01 23 specifications subject to change without notice. Pcb printed diagrams (cont) 1 2 3 4 5 6 7 8 13 9 10 11 12 fig. 36 - outdoor units dlccar / dlcchr size 18 top view table 16—outdoor units dlccar / dlcchr 1 2 3 4 5 6 7 8 9 10 11 12 13 compressor wire terminal outdoor heat exchanger mi...

  • Page 24

    24 328 080000 01 specifications subject to change without notice. Pcb printed diagrams (cont) 1 2 3 4 5 6 7 8 9 11 10 12 fig. 38 - outdoor units dlccar / dlcchr size 24 top view table 17— outdoor units 1 compressor interface 2 compressor overload protector 3 temperature sensor 4 electric expansion v...

  • Page 25

    328 080000 01 25 specifications subject to change without notice. Pcb printed diagrams (cont) fig. 40 - outdoor units dlccar / dlcchr sizes 30 and 36 top view table 18—outdoor units dlccar / dlcchr no. Name no. Name no. Name 1 high-frequency transformer t1 6 high pressure protection terminal hpp1 11...

  • Page 26

    26 328 080000 01 specifications subject to change without notice. Pcb printed diagrams (cont) 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 fig. 42 - indoor units dlfdab / dlfdhb sizes 9 − 24 top view fig. 43 - indoor units dlfdab / dlfdhb sizes 9 − 24 bottom view.

  • Page 27

    328 080000 01 27 specifications subject to change without notice. Pcb printed diagrams (cont) fig. 44 - indoor units dlfdhb sizes 30 and 36 top view table 19—indoor units dlfdab / dlfdhb no . Name 1 terminal of neutral wire 2 auto button 3 horizontal swing terminal 4 vertical swing terminal 5 commun...

  • Page 28

    28 328 080000 01 specifications subject to change without notice. Pcb printed diagrams (cont) 1 2 3 4 5 6 7 8 9 10 11 12 fig. 46 - outdoor units dlcdar / dlcdhr sizes 9 and 12 top view fig. 47 - outdoor units dlcdar / dlcdhr sizes 9 and 12 bottom view.

  • Page 29

    328 080000 01 29 specifications subject to change without notice. Pcb printed diagrams (cont) 4 5 6 8 9 11 12 13 14 15 16 17 18 19 1 2 3 7 10 fig. 48 - outdoor units dlcdar / dlcdhr sizes 18 and 24 top view fig. 49 - outdoor units dlcdar / dlcdhr sizes 18 and 24 bottom view.

  • Page 30

    30 328 080000 01 specifications subject to change without notice. Pcb printed diagrams (cont) fig. 50 - outdoor units dlcdhr sizes 30 and 36 top view table 20—outdoor units dlcdhr sizes 30 and 36 no. Name no. Name no. Name 1 high−frequency transformer t1 5 terminal of 4−way valve 9 protective tube f...

  • Page 31

    328 080000 01 31 specifications subject to change without notice. Refrigeration diagrams indoor unit outdoor unit cooling heating 4-way valve discharge suction heat exchanger (evaporator) heat exchanger (condenser) valve valve liquid pipe side gas pipe side strainer electron expansion valve strainer...

  • Page 32

    32 328 080000 01 specifications subject to change without notice. Refrigerant lines general refrigerant line sizing: 1. The units are shipped with a full charge of r410a refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft. (7.6 m). For runs over 25 ft. (7.6 m), review th...

  • Page 33: Caution

    328 080000 01 33 specifications subject to change without notice. System evacuation and charging unit damage hazard failure to follow this caution may result in equipment damage or improper operation. Never use the system compressor as a vacuum pump. Caution ! Refrigerant tubes and indoor coil shoul...

  • Page 34

    34 328 080000 01 specifications subject to change without notice. Brief description of modes and functions indoor unit basic system functions cooling mode 1. Under this mode, the fan and swing operate at the setting status. The temperature setting range is 60.8~86.0 _ f. 2. During a malfunction of t...

  • Page 35

    328 080000 01 35 specifications subject to change without notice. Liquid valve gas valve refrigerant charging vent nut of refrigerant charging vent vacuum pump piezometer valve cap lo hi inner hexagon spanner open close fig. 59 - tighten the screw caps leakage detection 1. With a leakage detector: c...

  • Page 36

    36 328 080000 01 specifications subject to change without notice. Troubleshooting this section provides the required flow charts to troubleshoot problems that may arise. Note: information required in the diagnoses can be found either on the wiring diagrams or in the appendix. Required tools: the fol...

  • Page 37

    328 080000 01 37 specifications subject to change without notice. Troubleshooting table 23—flashing led of indoor/outdoor unit and primary judgment no. Malfunction name display method of indoor unit display method of outdoor unit ac status possible causes dual-8 code display indicator display (durin...

  • Page 38

    38 328 080000 01 specifications subject to change without notice. Troubleshooting (cont) no. Malfunction name display method of indoor unit display method of outdoor unit ac status possible causes dual-8 code display indicator display (during blinking, on 0.5s and off 0.5s) indicator has 3 kinds of ...

  • Page 39

    328 080000 01 39 specifications subject to change without notice. Troubleshooting (cont) no. Malfunction name display method of indoor unit display method of outdoor unit ac status possible causes dual-8 code display indicator display (during blinking, on 0.5s and off 0.5s) indicator has 3 kinds of ...

  • Page 40

    40 328 080000 01 specifications subject to change without notice. Troubleshooting (cont) no. Malfunction name display method of indoor unit display method of outdoor unit ac status possible causes dual-8 code display indicator display (during blinking, on 0.5s and off 0.5s) indicator has 3 kinds of ...

  • Page 41

    328 080000 01 41 specifications subject to change without notice. Troubleshooting for the main malfunction indoor unit 1. Malfunction of temperature sensor f1, f2 troubleshooting for f1,f2 malfunction is the wiring terminal between the temperature sensor and the controller loosened or poorly contact...

  • Page 42

    42 328 080000 01 specifications subject to change without notice. 2. Malfunction of blocked protection of idu fan motor h6 end no yes no yes yes yes yes no no no yes yes no turn the fan blades by hand under power-off condition do the fan blades rotate smoothly with little to no resistance adjust the...

  • Page 43

    328 080000 01 43 specifications subject to change without notice. 3. Malfunction of protection of jumper cap c5 appearance of the jumper cap troubleshooting for c5 malfunction is there jumper cap on the mainboard ? Is the jumper cap inserted correctly and tightly ? Replace the jumper cap with the sa...

  • Page 44

    44 328 080000 01 specifications subject to change without notice. 4. Malfunction of over current protection e5 no no no no yes no no end yes malfunction is eliminated is the supply voltage unstable with big fluctuation? Is the supply voltage too low with overload? The fan is abnormal? Fan speed is t...

  • Page 45

    328 080000 01 45 specifications subject to change without notice. 5. Communication malfunction e6 start cut off power supply. Check if connection line of idu and odu and the wire inside electric box are correctly connected. Correct connection? Main board matches with display board? Main board of idu...

  • Page 46

    46 328 080000 01 specifications subject to change without notice. Outdoor unit 09k/12k 1. Capacity charging malfunction (outdoor unit malfunction) (ap1 below means control board of the outdoor unit) main detection points: s detect of the voltage of l1 and l2 terminals of xt wiring board is between 2...

  • Page 47

    328 080000 01 47 specifications subject to change without notice. 2. Check if the reactor (l) of the outdoor unit and the pfc capacitor are broken. Main detection points: s check if the reactor (l) of the outdoor unit and the pfc capacitor are broken fault diagnosis process: y n n n n y y start chec...

  • Page 48

    48 328 080000 01 specifications subject to change without notice. 3. Communication malfunction: (following ap1 for outdoor unit control board) mainly detect: s is there any damage for the indoor unit mainboard communication circuit? Is communication circuit damaged? S detect the indoor and outdoor u...

  • Page 49

    328 080000 01 49 specifications subject to change without notice. 4. High temperature and overload protection (e8) (ap1 below means control board of outdoor unit) main detection points: s is the outdoor ambient temperature in normal range? S is the indoor and outdoor fan running normally? S is the c...

  • Page 50

    50 328 080000 01 specifications subject to change without notice. 5. Start−up failure (lc) (ap1 below means control board of the outdoor unit. Main detection points: s is the compressor wiring correct? S is the compressor stop time sufficient? S is the compressor damaged? S is the unit overcharged? ...

  • Page 51

    328 080000 01 51 specifications subject to change without notice. 6. Overload and high discharge temperature malfunction main detection points: s is the electronic expansion valve connected to the board? S is the electronic expansion valve damaged? S do you have a refrigerant leak? S is the compress...

  • Page 52

    52 328 080000 01 specifications subject to change without notice. 7. Odu fan motor can not operate table 24—troubleshooting possible causes discriminating method (air conditioner status) troubleshootng wrong wire connection, or poor connection check the wiring status according to circuit diagram con...

  • Page 53

    328 080000 01 53 specifications subject to change without notice. 11. Communication malfunction (e6) main detection points: s check if the wire is damaged or the polarity is mixed between terminals. S is the communication circuit of the indoor mainboard damaged? S is the communication circuit of the...

  • Page 54

    54 328 080000 01 specifications subject to change without notice. Troubleshooting (cont) table 28—air conditioner can not start up possible causes discriminating method (air conditioner status) troubleshooting no power supply or poor connection for power plug after energizer, operation indicator is ...

  • Page 55

    328 080000 01 55 specifications subject to change without notice. Table 31—odu fan motor does not operate possible causes discriminating method (air conditioner status) troubleshooting wrong wire connection or poor connection check the wiring status according to circuit diagram connect wires accordi...

  • Page 56

    56 328 080000 01 specifications subject to change without notice. Disassembly instructions indoor unit remove the left end connection. Hold the end of connection rod with left hand. Hold the horizontal louver with right hand to separate connection rod and horizontal louver. Remove the horizontal lou...

  • Page 57

    328 080000 01 57 specifications subject to change without notice. Disassembly instructions indoor unit (cont) 6 7 8.

  • Page 58

    58 328 080000 01 specifications subject to change without notice. Disassembly instructions indoor unit (cont) 9. Remove electric box 10. Remove evaporator.

  • Page 59

    328 080000 01 59 specifications subject to change without notice. Disassembly instructions indoor unit (cont).

  • Page 60

    60 328 080000 01 specifications subject to change without notice. Disassembly instructions indoor unit (cont) 11. Remove swing blade.

  • Page 61

    328 080000 01 61 specifications subject to change without notice. Disassembly instructions indoor unit (cont) 12. Remove cross flow blade and motor.

  • Page 62

    62 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit 9−12 procedure steps 1.Remove the panel 3.Remove the front grille 2.Remove the top cover open the front panel. Push the rotor shaft on both sides of the panel to separate it from the groove. Remov...

  • Page 63

    328 080000 01 63 specifications subject to change without notice. Disassembly instructions outdoor unit 9−12 (cont) 4.Remove the front panel 5.Remove the right side plate 6.Remove the axial flow blade procedure steps remove t h e connection screws connecting the front panel with the chassis and the ...

  • Page 64

    64 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit 9−12 (cont) 7.Remove the motor and motor support 8.Remove the electric box assy 9.Remove the clapboard sub-assy procedure steps remove the 4 tapping screws securing the motor. Pull out the lead-ou...

  • Page 65

    328 080000 01 65 specifications subject to change without notice. Disassembly instructions outdoor unit 9−12 (cont) 10.Remove the 4-way valve assy 11.Remove the compressor procedure steps unscrew the fastening nut of the 4-way valve assy coil and remove the coil. Wrap the 4-way valve assy with wet c...

  • Page 66

    66 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 18−24 1.Remove handle handle 2.Remove top panel top panel twist off the screws used for fixing the handle , pull the handle up ward to remove it. Remove the screws connecting the top panel w...

  • Page 67

    328 080000 01 67 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 18−24 (cont) 4.Remove grille and panel grille panel twist off the screws connecting the panel, chassis and motor support with screwd-river, and then remove the panel. Twist off the screws co...

  • Page 68

    68 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 18−24 (cont) 7.Remove electric box electric box twist off the screws on electric box, cut off the tieline with scissors or pliers, pull out the wiring terminal, pull it upwards to remove the...

  • Page 69

    328 080000 01 69 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 18−24 (cont) 9.Remove motor support motor support twist off the tapping screws fixingthe motor support, pull it upwardsand then remove the motor support. Twist off the screws connecting isol...

  • Page 70

    70 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 18−24 (cont) 12.Remove gas valve and liquid valve liquid valve gas valve twist off the 2 bolts fixing the valve sub-assy. Unsolder the soldering joint between gas valve and air-return pipe a...

  • Page 71

    328 080000 01 71 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 18−24 (cont) 15.Remove left side plate left side plate twist off the screws connecting the left side plate and chassis with screwdriver, and then remove the left side plate. Pull it upwards ...

  • Page 72

    72 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 30−36 steps handle 2.Remove the top panel top panel remove the screws connecting the top panel with the front panel and left and right side plate, and then remove the top panel. 3.Remove the...

  • Page 73

    328 080000 01 73 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 30−36 (cont) steps 4.Remove the grille and panel grille panel twist off the screws connecting the panel, chassis and motor support with a screwdriver. Next, remove the panel. Twist off the s...

  • Page 74

    74 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 30−36 (cont) steps 7.Remove the electric box electric box electric box (fireproofing) 8.Remove the motor motor twist off the tapping screws securing the motor. Pull out the motor’s leading w...

  • Page 75

    328 080000 01 75 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 30−36 (cont) steps 9.Remove the motor support motor support twist off the tapping screws securing the motor support. Pull it upwards and then remove the motor support. Twist off the screws c...

  • Page 76

    76 328 080000 01 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 30−36 (cont) steps 12.Remove the gas valve and liquid valve liquid valve gas valve twist off the 2 bolts fixing the valve sub-assy. Unsolder the soldering joint between gas valve and air-ret...

  • Page 77

    328 080000 01 77 specifications subject to change without notice. Disassembly instructions outdoor unit sizes 30−36 (cont) steps 15.Remove the left side plate left side plate twist off the screws connecting the left side plate and chassis with a screwdriver , . Next, remove the left side plate. Pull...

  • Page 78

    78 328 080000 01 specifications subject to change without notice. Appendix appendix 1: fahrenheit and celsius reference sheet conversion formula for fahrenheit degree and celsius degree: tf=tcx1.8+32 table 35—set temperature fahrenheit display temperature ( _ f) fahrenheit ( _ f) celsius ( _ c) fahr...

  • Page 79

    328 080000 01 79 specifications subject to change without notice. Appendix 3: pipe expanding method note: improper pipe expanding is the main cause of refrigerant leakage. Please expand the pipe according to the following steps: a. Cut the pipe s confirm the pipe length according to the distance of ...

  • Page 80

    80 328 080000 01 specifications subject to change without notice. Appendix 4: list of resistance for the temperature sensor table 38—resistance table of ambient temperature sensor for indoor and outdoor units (15k) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w...

  • Page 81

    328 080000 01 81 specifications subject to change without notice. Table 39—resistance table of tube temperature sensors for indoor and outdoor (20k) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) -19 181.4 20 25.01 59 5.13 98 1.427...

  • Page 82

    82 328 080000 01 specifications subject to change without notice. Table 40—resistance table of discharge temperature sensors for outdoor (50k) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) temp ( _ c) resistance (k w) -29 853.5 10 98 49 18.34 88 4.754 -28 799...