Lancer 810 LX Installation And User Manual

Other manuals for 810 LX: User Manual, Technical Manual

Summary of 810 LX

  • Page 1

    Lancer reserves the right to make any changes in the manuals in order to improve them . Installation and user’s manual 810 lx / 815 lx.

  • Page 3: Installation Manual

    Installation manual 810 lx / 815 lx.

  • Page 5

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 5 unpackaging and setting in place • remove the box and the plastic film from around the washer. • open the door of the washer by pulling the handle towards you and then lower the door to the horizontal position. Remove and inspect the content...

  • Page 6: Characteristics

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 6 characteristics (standard) heat loss : 600 kcal/h (2380 btu/h). Noise level : 63 dba in accordance with the european council directive of june 14, 1989, concerning the harmonization of the legislation of european union member states regardin...

  • Page 7: Characteristics

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 7 characteristics (with plinth / 02010020) heat loss : 600 kcal/h (2380 btu/h). Noise level : 63 dba in accordance with the european council directive of june 14, 1989, concerning the harmonization of the legislation of european union member s...

  • Page 8: Characteristics

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 8 characteristics (400tri without neutral / 90010007) heat loss : 600 kcal/h (2380 btu/h). Noise level : 63 dba in accordance with the european council directive of june 14, 1989, concerning the harmonization of the legislation of european uni...

  • Page 9: Characteristics

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 9 characteristics (400 without neutral - with plinth / 90010007 + 02010020) heat loss : 600 kcal/h (2380 btu/h). Noise level : 63 dba in accordance with the european council directive of june 14, 1989, concerning the harmonization of the legis...

  • Page 10: Operating Environment

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 10 operating environment the washer is designed for use in the following conditions : • an indoor environment. • altitude up to 2000 meters (6,562 feet). • temperature between 5°c and 40°c (41°f and 104°f). • maximum relative humidity of 80% u...

  • Page 11: Water Connections

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 11 water connections (pressurized demineralized water supply - standard) cold water : a valve with a male threaded nozzle, 20/27 diameter, (3/4" hose thread) is required. Flow rate : 20 l/min (5.3 gpm) with a minimum pressure of 200 kpa (2 bar...

  • Page 12: Water Connections

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 12 water connections (demineralized water tank supply / 90010187) cold water : a valve with a male threaded nozzle, 20/27 diameter, (3/4" hose thread) is required. Flow rate : 20 l/min (5.3 gpm) with a minimum pressure of 200 kpa (2 bar or 29 ...

  • Page 13: Water Connections

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 13 water connections (demineralized water tank supply with plinth base stand / 90010187 + 02010020) cold water : a valve with a male threaded nozzle, 20/27 diameter, (3/4" hose thread) is required. Flow rate : 20 l/min (5.3 gpm) with a minimum...

  • Page 14: Water Connections

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 14 water connections (intermediate pressure demineralized supply / 01060206) cold water : a valve with a male threaded nozzle, 20/27 diameter, (3/4" hose thread) is required. Flow rate : 20 l/min (5.3 gpm) with a minimum pressure of 200 kpa (2...

  • Page 15

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 15 drain discharge cooling water : (90010077) utilizes the cold water valve as specified above. Cold water source should be less than 25 °c. Condenser : (90010078) utilizes the cold water valve as specified above. Cold water source should be l...

  • Page 16

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 16 waters intakes must be located in this area (standard).

  • Page 17

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 17 waters intakes must be located in this area (plinth / 02010020).

  • Page 18

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 18 flush and drain all water supply lines to remove debris before making connections to flexible hoses. The hoses required to connect the washer to the various water inlets are supplied with the machine. The maximum length of flexible hoses sh...

  • Page 19: Electrical Connection

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 19 electrical connection (standard - 400tri+n+t) b efore carrying out any work on the washer , make sure it is switched off at the electrical disconnect switch . E lectrical supply : check for correct voltage supply at the electrical panel bef...

  • Page 20: Electrical Connection

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 20 electrical connection (230tri+t / 90010101) b efore carrying out any work on the washer , make sure it is switched off at the electrical disconnect switch . E lectrical supply : check for correct voltage supply at the electrical panel befor...

  • Page 21: Electrical Connection

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 21 electrical connection (200tri+t 50-60hz / 90010002-90010012) b efore carrying out any work on the washer , make sure it is switched off at the electrical disconnect switch . E lectrical supply : check for correct voltage supply at the elect...

  • Page 22: Electrical Connection

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 22 electrical connection (230mono+t / 90010100) b efore carrying out any work on the washer , make sure it is switched off at the electrical disconnect switch . E lectrical supply : check for correct voltage supply at the electrical panel befo...

  • Page 23: Electrical Connection

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 23 electrical connection (400tri without neutral / 90010007) b efore carrying out any work on the washer , make sure it is switched off at the electrical disconnect switch . E lectrical supply : check for correct voltage supply at the electric...

  • Page 24

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 24 electrical connection the electrical disconnect switch can be installed to the left, to the right, or behind the washer. The circuit breaker must be labelled as the protection device for the lancer washer. -1- electrical disconnect switch (...

  • Page 25: Discharge Of Waste Waters

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 25 discharge of waste waters (standard with no condenser) provide a fixed standpipe and plumbing trap with a minimum inside diameter of 40 mm (1 ½ inches). Height above floor level : 500 mm (20 inches) minimum and 700 mm (27 ½ inches) maximum....

  • Page 26: Discharge Of Waste Waters

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 26 discharge of waste waters (standard with condenser / 90010078) provide 2 fixed standpipes (as shown) and plumbing trap with minimum inside diameters of 40 mm (1 ½ inches) per standpipe. Height above floor level : 500 mm (20 inches) minimum ...

  • Page 27: Discharge Of Waste Waters

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 27 discharge of waste waters (plinth with no condensor / 02010020) provide a fixed standpipe and plumbing trap with a minimum inside diameter of 40 mm (1 ½ inches). Height above floor level : 1000 mm (40 inches) minimum and 1200 mm (47 ½ inche...

  • Page 28: Discharge Of Waste Waters

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 28 discharge of waste waters (plinth with condenser / 02010020 + 90010078) provide 2 fixed standpipes (as shown) and plumbing trap with minimum inside diameters of 40 mm (1 ½ inches). Height above floor level : 1000 mm (40 inches) minimum and ...

  • Page 29

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 29 i n order to avoid the alarm n °2 on the display ( see user ’ s manual ), check that the emptying tube ( s ) is / are installed properly according to the diagrams below ..

  • Page 30: Wall Fixation

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 30 wall fixation (plinth / 02010020) it is recommended to fix the washer against the wall. You can choose, according to the space available around the washer, the location of the fixing plate to the wall : on the side or on top of the cover (s...

  • Page 31: Discharge of Steam

    810-815 lx / installation ni_810-815_lx_pilote_ang_a.Doc 31 discharge of steam (no condenser) two solutions : • if you decide that it is not necessary to install a flexible hose, you must turn the steam draining pipe as show. • otherwise, provide, by others, the connection of a flexible hose with an...

  • Page 32: The Washing Products

    810 lx / installation ni_810-815_lx_pilote_ang_a.Doc 32 the washing products (standard) non-foaming detergent place a container of non-foaming liquid detergent next to the washer at a maximum height of 150 mm (6 inches) above floor level. Remove the cap from the detergent container and insert the de...

  • Page 33: The Washing Products

    810 lx / installation ni_810-815_lx_pilote_ang_a.Doc 33 the washing products (with plinth / 02010020) non-foaming detergent place a container of non-foaming liquid detergent inside the plinth cabinet below the wash chamber. Remove the cap from the detergent container and insert the detergent suction...