1 1 la-on-rack 6k/10k please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information and operating instructi...
2 2 la-on-rack 6k/10k table of contents 1. Safety and emc instructions ...............................................................................................3 1.1. T ransportation and s torage .....................................................................................................
3 3 la-on-rack 6k/10k 1. Safety and emc instructions please read carefully the following user manual and the safety instructions before installing the unit or using the unit! 1.1. Transportation and storage please transport the ups system only in the original package to protect against shock and imp...
4 4 la-on-rack 6k/10k 1.4. Operation do not disconnect the earth conductor cable on the ups or the building wiring terminals in any time since this would cancel the protective earth of the ups system and of all connected loads. The ups system features its own, internal current source (batteries). Th...
5 5 la-on-rack 6k/10k 2. Installation and operation there are two different types of online ups: standard and long-run models. Please refer to the following model table. Model type model type 6kr 6kr-l 10kr standard model 10kr-l long-run model parallel function is also available for these two types ...
6 6 la-on-rack 6k/10k diagram 6: 6kr/10kr battery pack rear panel 1. Rs-232 communication port 2. Usb communication port 3. Emergency power off function connector (epo connector) 4. Share current port (only available for parallel model) 5. Parallel port (only available for parallel model) 6. Intelli...
7 7 la-on-rack 6k/10k 2.3. Single ups installation in stallation and wiring must be performed in accordance with the local electric laws/regulations and execute the following instructions by professional personnel. 1) make sure the mains wire and breakers in the building are enough for the rated cap...
8 8 la-on-rack 6k/10k warning: (only for standard model) ● make sure the ups is not turned on before installation. The ups should not be turned on during wiring connection. ● do not try to modify the standard model to the long-run model. Particularly, do not try to connect the standard internal batt...
9 9 la-on-rack 6k/10k 6) refer to the following wiring diagram: diagram 1: power cable connection 2.5. Software installation for optimal computer system protection, install ups monitoring software to fully configure ups shutdown. Install cd or visit the website http://www.Power-software-download.Com...
10 10 la-on-rack 6k/10k 3. Operations 3.1. Button operation button function on/enter button turn on the ups: press and hold the button more than 0.5s to turn on the ups. Enter key: press this button to confirm the selection in setting menu. Off/esc button turn off the ups: press and hold the button ...
11 11 la-on-rack 6k/10k display function backup time information indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, m: minutes, s: seconds fault information indicates that the warning and fault occurs. Indicates the fault codes, and the codes are listed in detail...
12 12 la-on-rack 6k/10k 3.3. Audible alarm description buzzer status muted ups status bypass mode beeping once every 2 minutes battery mode beeping once every 4 seconds fault mode beeping continuously yes warning overload beeping twice every second low battery battery unconnected over charge epo ena...
13 13 la-on-rack 6k/10k 3. Connect devices to ups after the ups is turned on, you can connect devices to the ups. 1) turn on the ups first and then switch on the devices one by one, the lcd panel will display total load level. 2) if it is necessary to connect the inductive loads such as a printer, t...
14 14 la-on-rack 6k/10k 7. Turn off the ups with utility power supply in ac mode 1) turn off the inverter of the ups by pressing “off” button for at least 0.5s, and then the buzzer will beep once. The ups will turn into bypass mode. Note 1: if the ups has been set to enable the bypass output, it wil...
15 15 la-on-rack 6k/10k 3.5. Parallel operation 1. Parallel system connection 1) make sure all of the upss are parallel models, and follow the wiring refer to section 2-3. 2) turn off the input and output breakers of each ups, and turn off the battery breaker if the ups is long-run model. 3) remove ...
16 16 la-on-rack 6k/10k 3.6. Abbreviation meaning in lcd display abbreviation display content meaning ena enable dis disable ato auto bat battery ncf normal mode (not cvcf mode) cf cvcf mode sub subtract add add on on off off fbd not allowed opn allow res reserved 3.7. Lcd setting there are three pa...
17 17 la-on-rack 6k/10k code description bypass ac eco cvcf battery battery test 11 shutdown point for programmable output y y y y y y 12 hot standby function enable/disable y y y y y y 13 battery voltage adjustment y y y y y y 14 charger voltage adjustment y y y y y y 15 output voltage adjustment y...
18 18 la-on-rack 6k/10k 04: frequency range for bypass interface setting parameter 2: set the acceptable low frequency for bypass. 50 hz system: setting range is from 46.0hz to 49.0hz. 60 hz system: setting range is from 56.0hz to 59.0hz. The default value is 46.0hz/56.0hz. Parameter 3: set the acce...
19 19 la-on-rack 6k/10k 09: battery backup time setting interface setting parameter 3: 000~999: set the maximum backup time from 0min to 999min. Ups will shut down to protect battery after backup time arrives. The default value is 990min. Dis: disable battery discharge protection and backup time wil...
20 20 la-on-rack 6k/10k 13: battery voltage adjustment interface setting parameter 2: select “add” or “sub” function to adjust battery voltage to real figure. Parameter 3: the voltage range is from 0v to 5.7v, the default value is 0v. 14: charger voltage adjustment interface setting parameter 2: you...
21 21 la-on-rack 6k/10k operating mode/status description when input frequency is within 46 to 64hz, the ups can be set at a constant output frequency, 50 hz or 60 hz. The ups will still charge battery under this mode. Cvcf mode lcd display description when the input voltage is beyond the acceptable...
22 22 la-on-rack 6k/10k 3.9. Fault code fault event fault code icon fault event fault code icon bus start failure 01 none negative power fault 1a none bus over 02 none battery scr short circuited 21 none bus under 03 none inverter relay short circuited 24 none bus unbalance 04 none battery voltage l...
23 23 la-on-rack 6k/10k 4. Trouble shooting if the ups system does not operate correctly, please solve the problem by using the table below. Symptom possible cause remedy no indication and alarm in the front display panel even though the mains is normal. The ac input power is not connected well. Che...
24 24 la-on-rack 6k/10k 5. Storage and maintenance 5.1. Storage before storing, charge the ups at least 7 hours. Store the ups covered and upright in a cool, dry location. During storage, recharge the battery in accordance with the following table: storage temperature recharge frequency charging dur...
25 25 la-on-rack 6k/10k 6. Specifications model la-on-6k-rack la-on-10k-rack capacity* 6000 va / 4800 w 10000 va / 8000 w input low line loss 110 vac ± 3 % at 50% load; 176 vac ± 3 % at 100% load low line comeback low line loss voltage + 10v high line loss 300 vac ± 3 % voltage range high line comeb...