Lapara 10KR User Manual - page 18
17
17
LA-ON-RACK 6K/10K
Code
Description
Bypass AC ECO
CVCF
Battery
Battery
Test
11
Shutdown point for programmable output
Y Y
Y
Y Y Y
12
Hot standby function enable/disable
Y
Y
Y
Y
Y
Y
13
Battery voltage adjustment
Y
Y
Y
Y
Y
Y
14
Charger voltage adjustment
Y
Y
Y
Y
Y
Y
15
Output voltage adjustment
Y
Y Y
*Y means that this program can be set in this mode.
**Programmable output setting is not supported by Rack models.
01: Output voltage
Interface Setting
Parameter 3: Output voltage
You may choose the following output voltage in parameter 3:
208:
Presents output voltage is 208Vac
220:
Presents output voltage is 220Vac
230:
Presents output voltage is 230Vac
240:
Presents output voltage is 240Vac
02: Output frequency
Interface Setting
60 Hz, CVCF mode
50 Hz, Normal mode
ATO
Parameter 2: Output Frequency
Setting the output frequency. You may choose following three
options in parameter 2:
50.0Hz:
The output frequency is setting for 50.0Hz.
60.0Hz:
The output frequency is setting for 60.0Hz.
ATO:
If selected, output frequency will be decided according to the
latest normal utility frequency. If it is from 46Hz to 54Hz, the output
frequency will be 50.0Hz. If it is from 56Hz to 64Hz, the output
frequency will be 60.0Hz. ATO is default setting.
Parameter 3: Frequency mode
Setting output frequency at CVCF mode or not CVCF mode. You
may choose following two options in parameter 3:
CF:
Setting UPS to CVCF mode. If selected, the output frequency
will be fixed at 50Hz or 60Hz according to setting in parameter 2. The
input frequency could be from 46Hz to 64Hz.
NCF:
Setting UPS to normal mode (not CVCF mode). If selected, the
output frequency will synchronize with the input frequency within
46~54 Hz at 50Hz or within 56~64 Hz at 60Hz according to setting in
parameter 2. If 50 Hz selected in parameter 2, UPS will transfer to
battery mode when input frequency is not within 46~54 Hz. If 60Hz
selected in parameter 2, UPS will transfer to battery mode when
input frequency is not within 56~64 Hz.
*If Parameter 2 is ATO, the Parameter 3 will show the current
frequency.
03: Voltage range for bypass
Interface Setting
Parameter 2:
Set the acceptable low voltage for bypass. Setting
range is from 110V to 209V and the default value is 110V.
Parameter 3:
Set the acceptable high voltage for bypass. Setting
range is from 231V to 276V and the default value is 264V.