    Online ups 1k/2k/3k uninterruptible power supply system user manual en.

  • Page 2: Table of Contents

    1 la-gl-on-lcd table of contents 1. Important safety warning……………………………………………… 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5. Maintenance, service and faults 3 2. Installation and setup…………………………………………………… 4 2.1. Rear panel view 4 2.2. Setup the ups 5 3. Operati...

  • Page 3

    2 la-gl-on-lcd 1. Important safety warning please comply with all warnings and operating instructions in this manual strictly. Save this manual properly and read carefully the following instructions before installing the unit. Do not operate this unit before reading through all safety information an...

  • Page 4

    3 la-gl-on-lcd 1.5. Maintenance, service and faults z the ups system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance personnel. Z caution - risk of electric shock. Even after the unit is disconnected from the mains (building wiring outlet), components insid...

  • Page 5

    4 la-gl-on-lcd 2. Installation and setup note: before installation, please inspect the unit. Be sure that nothing inside the package is damaged. Please keep the original package in a safe place for future use. Note: there are two different types of online ups: standard and long-run models. Please re...

  • Page 6

    5 la-gl-on-lcd 2.2. Setup the ups step 1: ups input connection plug the ups into a two-pole, three-wire, grounded receptacle only. Avoid using extension cords. Z for 208/220/230/240vac models:the power cord is supplied in the ups package. Z for 110/115/120/127vac models: the power cord is attached t...

  • Page 7

    6 la-gl-on-lcd step 5: disable and enable epo function keep the pin 1 and pin 2 closed for ups normal operation. To activate epo function, cut the wire between pin 1 and pin 2. Step 6: turn on the ups press the on/mute button on the front panel for two seconds to power on the ups. Note: the battery ...

  • Page 8

    7 la-gl-on-lcd 3. Operations 3.1. Button operation button function on/mute button ¾ turn on the ups: press and hold on/mute button for at least 2 seconds to turn on the ups. ¾ mute the alarm: when the ups is on battery mode, press and hold this button for at least 5 seconds to disable or enable the ...

  • Page 9

    8 la-gl-on-lcd display function backup time information indicates the backup time in pie chart. Indicates the backup time in numbers. H: hours, m: minute, s: second fault information indicates that the warning and fault occurs. Indicates the warning and fault codes, and the codes are listed in detai...

  • Page 10

    9 la-gl-on-lcd 3.3. Audible alarm battery mode sounding every 4 seconds low battery sounding every second overload sounding twice every second fault continuously sounding bypass mode sounding every 10 seconds 3.4. Lcd display wordings index abbreviation display content meaning ena enable dis disable...

  • Page 11

    10 la-gl-on-lcd z 01: output voltage setting interface setting parameter 3: output voltage for 208/220/230/240 vac models, you may choose the following output voltage: 208: present output voltage is 208vac 220: present output voltage is 220vac 230: present output voltage is 230vac 240: present outpu...

  • Page 12

    11 la-gl-on-lcd z 06: bypass enable/disable when ups is off interface setting parameter 3: enable or disable bypass function. You may choose the following two options: ena: bypass enable dis: bypass disable z 07: bypass voltage range setting interface setting parameter 2 & 3: set the acceptable high...

  • Page 13

    12 la-gl-on-lcd 3.6. Operating mode description operating mode description lcd display online mode when the input voltage is within acceptable range, ups will provide pure and stable ac power to output. The ups will also charge the battery at online mode. Eco mode energy saving mode: when the input ...

  • Page 14

    13 la-gl-on-lcd 3.8. Warning indicator warning icon (flashing) alarm low battery sounding every second overload sounding twice every second battery is not connected sounding every second over charge sounding every second site wiring fault sounding every second epo enable sounding every second fan fa...

  • Page 15

    14 la-gl-on-lcd 4. Troubleshooting if the ups system does not operate correctly, please solve the problem by using the table below. Symptom possible cause remedy the ac input power is not connected well. Check if input power cord firmly connected to the mains. No indication and alarm even though the...

  • Page 16

    15 la-gl-on-lcd symptom possible cause remedy fault code is shown as 14 and the icon is lighting on lcd display and alarm is continuously sounding. The ups shut down automatically because short circuit occurs on the ups output. Check output wiring and if connected devices are in short circuit status...

  • Page 17

    16 la-gl-on-lcd 6. Specifications model la-gl-on-1k-lcd (l) la-gl-on-2k-lcd (l) la-gl-on-3k-lcd (l) capacity* 1000 va / 800 w 2000 va / 1600 w 3000 va / 2400 w input low line transfer 160 vac / 140 vac / 120 vac / 110 vac ± 5 % or 80 vac / 70 vac / 60 vac / 50 vac ± 5 % ( based on load percentage 10...