11
LA-GL-ON-LCD
z 06: Bypass enable/disable when UPS is off
Interface Setting
Parameter 3: Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable
DIS: Bypass disable
z 07: Bypass voltage range setting
Interface Setting
Parameter 2 & 3: Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high voltage point
For 208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac.
For 110/115/120/127 VAC models:
120-132: setting the high voltage point in parameter 3 from
120Vac to 132Vac
LLS: Bypass low voltage point
For 208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac
For 110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from 85Vac
to 115Vac.
z 08: Programmable outlets enable/disable
Interface Setting
Parameter 3: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Progr
ammable outlets disable
z 09: Programmable outlets setting
Interface Setting
Parameter 3: Set up backup time limits for programmable
outlets.
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode.
z 00: Exit setting