Latronics PVE1200 Instruction Manual - page 9
10
Note 1:
Note 2
The DC input is suitable for connection to solar modules
only, when MPPT is enabled.
:
Do not exceed recommended Maximum DC Input Power.
Note 3:
All solar modules should be of the same type and brand.
Therefore the maximum power point and voltage variation with
temperature are consistent for all modules, which will ensure
maximum system output.
SOLAR INPUT CONFIGURATION
Panel Power
At 25 C
o
75W
90W
100W
125W
140W
150W
165W
180W
Module
Type
12V
12V
12V
12V
24V
24V
24V
24V
Number of Panels
Per String
4
4
4
4
2
2
2
2
Solar Input
Power
1200W
1080W
1200W
1000W
1120W
1200W
1320W
1080W
No. of Strings
4
3
3
2
4
4
4
3
PVE 1200
Panel Power
At 25 C
o
90W
100W
110W
125W
140W
150W
160W
165W
180W
Module
Type
12V
12V
12V
12V
24V
24V
24V
24V
24V
Number of Panels
Per String
8
8
8
8
4
4
4
4
4
Solar Input
Power
2160W
2400W
2640W
2000W
2240W
2400W
2560W
1980W
2160W
Number
of Strings
3
3
3
2
4
4
4
3
3
PVE 2500
DIP SWITCH SETTINGS
Switch 1 -MPPT / Battery mode
Switch 2 - 50/60 Hz
Switch 4
Switch 5
Switch 6
In the ON position
the Maximum Power Point Tracking is enabled.
This is required when the DC input is Photovoltaic Solar Modules only.
In the OFF position the Maximum Power Point Tracking is disabled and the
voltage tracking will operate at a fixed voltage of 54V (PVE1200) or 108V
(PVE2500). This setting is required in a system where a 48V (PVE1200) or
96V (PVE2500) Battery Bank is required on the DC input.
In the ON position the Inverter is set for 60Hz operation.
In the OFF position
the Inverter is set for 50Hz operation.
Must be in OFF position
for normal operation. The ON position is
a factory AC test setting.
Must be in the OFF position
for normal operation. The ON position
is a factory DC test setting.
Not used.
(default)
(default)
(default)
(default)
(default)
Switch 3
Battery type selector not used if switch 1 is ON.
ON = Gel/SLA battery.
OFF = Flooded battery.
7
DIP SWITCH LOCATION
MAIN PCB
DIP Switch located on Main PCB
1 2 3 4 5 6
OFF
ON
WARNING:
Due to dangerous voltages existing inside the unit, make sure
the circuit breaker switch are turned off before opening the unit.
Only
are permitted to adjust these
settings.
qualified Trades Persons