M-system R7G-SC-SHL Instruction Manual - page 2
R7G-SC-SHL
P. 2 / 6
EM-7817-A Rev.1
HLS ID
COLOR
FUNCTION
PWR
Green
Turnsonwhentheinternal5Vis
supplied normally.
RUN1/RUN2
Green
Turns on when the refresh data is
received normally.
CC-Link ID COLOR
FUNCTION
RUN1/RUN2
Red
Turns on when the refresh data is
received normally.
ERR1/ERR2
Red
Turns on when the received data
is abnormal.
SD1/SD2
Red
Turns on when the module is
transmitting.
RD1/RD2
Red
Turns on when the module is
receiving.
■
CC-Link STATION ADDRESS
Station Address is selected between 1 and 63 in decimal.
The left switch determines the tenth place digit, while the
right switch does the ones place digit of the address. Setting
“n” with the rotary switches, the addresses are assigned to
n,n+1forCH1,CH2respectively.
*ForCC-Linknetworkparameters,thefollowingstationin-
formation for two stations is required.
Stationtype:RemoteI/O,Dataallocation:1
5
4
3
2 1 0 9
8
7
6
5
4
3
2 1 0 9
8
7
6
Station Address
Setting (x1)
Station Address
Setting (x10)
■
HLS MODULE ADDRESS
ModuleAddressisselectedbetween01Hand3FHinhexa-
decimal. The left switch determines the sixteenths place
digit, while the right switch does the ones place digit of the
address.
Setting “m” with the rotary switches, the addresses are as-
signedtom,m+1forCH1,CH2respectively.
■
OPERATING MODE
•HLS transfer rate
HLS TRANSFER RATE
CH1, CH2
SW1-1
12Mbps(*)
12M
6Mbps
6M
•HLS output at the loss of communication
OUTPUT AT THE LOSS OF
COMMUNICATION
CH1
CH2
SW1-2
SW1-3
Holdtheoutput(*)
(maintains the last data re-
ceived normally)
H1
H2
Resettheoutput(turnedoff)
C1
C2
•CC-Link output at the loss of communication
OUTPUT AT THE LOSS OF
COMMUNICATION
CH1, CH2
SW1-4
Hold the output (maintains the
last data received normally) (*)
H
Resettheoutput(turnedoff)
C
(*)Factorysetting
■
CC-Link BAUD RATE
BaudRateisselectedwiththerotaryswitch.
5
4
3
2 1 0 9
8
7
6
Baud Rate Setting
0 : 156 kbps
1 : 625 kbp
s
2 : 2.5 Mbps
3 : 5 Mbps
4 : 10 Mbps
■
TERMINATING RESISTOR
To use the terminating resistor, turn the switch ON, and
OFFtoinvalidate.(FactorysettingOFF)
■
STATUS INDICATOR LED
Module Address Setting (LSD)
Module Address Setting (MSD)
012
3
4
5
67
89A
B
C
D
EF
012
3
4
5
67
89A
B
C
D
EF