Macurco DVP-120 Installation & Operating Instructions Manual

Other manuals for DVP-120: User Instructions
Manual is about: Detection and Ventilation Control Panel

Summary of DVP-120

  • Page 1

    Dvp-120 installation & operating instructions.

  • Page 2

    Revision 0.07 2 table of contents 1 introduction ....................................................................................................................................... 5 1.1 general information ............................................................................................

  • Page 3

    Revision 0.07 3 figure 3-4 normal system display ..................................................................................................................... 17 figure 3-5 sensor prompt ............................................................................................................

  • Page 4

    Revision 0.07 4 list of tables table 2-1 main power connections .................................................................................................................... 10 table 2-2 recommended wire gauge.......................................................................................

  • Page 5: 1  Introduction

    Revision 0.07 5 1 introduction 1.1 general information the dvp-120 gas detection and ventilation control panel is a microcomputer based control panel used to operate ventilation fans based on the inputs from remotely mounted gas transducers. The unit is fully tested prior to leaving the factory, and...

  • Page 6

    Revision 0.07 6 cm-2b d c b - a + output power coil coil exhaust fans 120 vac alarm 120 vac power main fan power starter relays 120 vac coils macurco dvp-120 gas detection and ventilation control panel exhaust fan exhaust fan cm-2b, cm-3 or ss102hc-1 cm-2b, cm-3 or ss102hc-1 cm-2b, cm-3 or ss102hc-1...

  • Page 7

    Revision 0.07 7 figure 1-2 dvp-120 internal view.

  • Page 8

    Revision 0.07 8 1.4 specifications 1 – size: 10” x 12” x 2” (254 mm x 305 mm x 51 mm) – weight: tbd – enclosure: nema 1 equivalent steel – operating temperature: 0° to 50 °c (-32 to 122 °f) – operating humidity: 0% to 95% rh non-condensing – power input: 100 – 240 vac, 1 amp, 47 – 63 hz, single phas...

  • Page 9: Warning

    Revision 0.07 9 2 installation & connection 2.1 mounting the dvp-120 mounting holes are provided in the dvp-120 case at the four corners. The top two are keyhole shaped so that the panel can be hung and then the two bottom screws driven to hold the panel. Conduit entry holes are provided on the top,...

  • Page 10

    Revision 0.07 10 2.3 main power connection the main power cable should be routed into the bottom left conduit entry. Macurco recommends a minimum wire size of awg18. The modular connector will accept wire from 12 to 24 awg. The safety ground wire should be secured to the ground stud at the bottom le...

  • Page 11

    Revision 0.07 11 each 8-terminal sensor modular connector may be disconnected from the pcb connector to ease wire installation. The terminals will accept wire from 16 to 28 awg. To install a wire, strip back approximately 0.25 in. (6 mm) of insulation, and insert the bare wire into the terminal. Tig...

  • Page 12

    Revision 0.07 12 2.5 relay connection all poles of the three relays are available at the modular connector j2 (see figure 2-2 for details). J2 is a 9- position variant of the high voltage modular connector used for power input. Each terminal can accommodate a wire size 12 to 24 awg. Insert this face...

  • Page 13

    Revision 0.07 13 2.6 horn & strobe connection the external horn and strobe connections are available at the modular connector j5 (see figure 2-3 for details). J5 as a 4-position connector, similar to the sensor interface connectors. Insert this face of connector into mating connector on control circ...

  • Page 14

    Revision 0.07 14 2.7 interfacing macurco sensors all macurco co, no2 and combustible gas sensors with current loop outputs may be used with the dvp-120. Data sheets for the macurco sensors listed in table 2-8 are provided as an appendix to this manual. Power connections to macurco sensors used with ...

  • Page 15: 3  Operation

    Revision 0.07 15 3 operation 3.1 initial operating mode when power is first applied to the dvp-120, a few simple tests will be performed, e.G. Cycle through all status lights, and display the system name and model # (figure 3-1). The system will then proceed to normal mode, if the operating paramete...

  • Page 16

    Revision 0.07 16 3.1.2 user interface the lcd display is used to show detailed information about the status of the control system and the configuration parameters to the user. The keypad (figure 3-3) is used to select the information displayed and to enter the configuration parameters, which are sto...

  • Page 17

    Revision 0.07 17 3.1.3 normal status display mo n 1 0 : 2 3 r 1 o f f s 0 1 c o 5 p p m figure 3-4 normal system display the display shows the day of the week and the time of day, in 24-hour format. It also shows the status of one of the relays, r1 in this example, and the type and indicated gas con...

  • Page 18

    Revision 0.07 18 a l a r m s i l e n c e d f o r 5 m i n u t e s figure 3-7 alarm silenced message if relay 1 has be configured as an alarm relay it will be turned on when an alarm condition is recognized and will be turned off when all audio indicators have been silenced. Silencing applies to the c...

  • Page 19

    Revision 0.07 19 when the hush key is pressed, the internal buzzer will be silenced for eight (8) hours. If the horn or strobe turn on delays have not finished then they will also be silence. If the delays have finished, the hush key must be held for three (3) seconds in order to silence the horn an...

  • Page 20

    Revision 0.07 20 3.3 setting the system configuration the configuration menus can be entered from normal mode by pressing the menu key. While in configuration mode, the user can review all configuration parameters to check the current operating conditions. As an aid when configuring the control pane...

  • Page 21

    Revision 0.07 21 3.3.1 system menu the top menu level allows the user to select: – configure system – configure sensors – configure relays, horn & strobe – configure zones – configure signals the up and down cursor keys can be used to scroll through the entries in the list, while the left or right k...

  • Page 22

    Revision 0.07 22 3.3.2.2 set day of week t i m e : 2 2 : 5 5 d a y : 2 t u e s d a y figure 3-19 set day of the week this display example shows that tuesday is the current day of the week. The underline character indicates that the day can be changed by entering the corresponding digit: – 1 monday –...

  • Page 23

    Revision 0.07 23 3.3.2.4 enter password p a s s w o r d * * * * figure 3-21 enter password ? This display shows that the password is 4 digits long. When the first digit is entered, the panel will show. P a s s w o r d _ _ _ 1 figure 3-22 password prompt ? If the password is not entered correctly the...

  • Page 24

    Revision 0.07 24 3.3.3 configure sensors submenu there is a list of parameters for each sensor in the system, either currently wired or configured but presently disconnected. The left and right cursor keys can be used to move from one sensor to another; doing so always goes to the first display (sum...

  • Page 25

    Revision 0.07 25 3.3.3.4 warning set point s e n s o r 0 1 c o w a r n i n g : _ _ 5 0 p p m figure 3-27 sensor’s warning level the default warning levels for the sensors are: – carbon monoxide 50 ppm – nitrogen dioxide 3.0 ppm – combustible 2,000 ppm (5% lel for methane) setting a warning level of ...

  • Page 26

    Revision 0.07 26 3.3.4 configure relays, horn & strobe submenu there is a list of parameters for each relay in the system. The left and right cursor keys can be used to move from one relay, horn or strobe to another. Doing so always goes to the first (summary) display. The up and down keys will scro...

  • Page 27

    Revision 0.07 27 3.3.5 configure horn submenu the configuration parameters for the horn are the same as those for relays. A horn would not normally require a minimum on time but this parameter allows a more versatile configuration. 3.3.5.1 horn summary h o r n 4 n o r m . O f f d e l a y o n figure ...

  • Page 28

    Revision 0.07 28 3.3.6 configure strobe submenu the configuration parameters for the strobe are the same as those for relays. A strobe would not normally require a minimum on time but this parameter allows a more versatile configuration. 3.3.6.1 strobe summary s t r o b e 5 n o r m . O f f d e l a y...

  • Page 29

    Revision 0.07 29 3.3.7 configure zones submenu the dvp-120 ventilation control can support up to three zones. The zone functionality makes the dvp-120 very flexible. For example, each zone can be configured to monitor a separate set of 4 sensors and control a single relay. Another control scheme use...

  • Page 30

    Revision 0.07 30 3.3.7.3 timed day selection z 1 g r o u p 1 t i m e d d a y s : 1 w e e k d a y s figure 3-43 timer days selection valid entries are: – 1 weekdays, monday thru friday, (default) – 2 weekends, saturday and sunday 3.3.7.4 start time z 1 g r o u p 1 t i m e d s t a r t t i m e : 0 7 : ...

  • Page 31

    Revision 0.07 31 3.3.7.7 rising trip point z 1 g r o u p 1 n o 2 r i s i n g : 2 . 5 p p m figure 3-48 rising trip point entry the default rising trip points are: – carbon monoxide 100 ppm – nitrogen dioxide 2.5 ppm – combustible 2,000 ppm 3.3.7.8 falling trip point z 1 g r o u p 1 n o 2 f a l l i n...

  • Page 32

    Revision 0.07 32 3.3.8 configure signals submenu the dvp-120 can drive the buzzer, horn and strobe with different sound patterns to indicate the severity of the current conditions. These patterns are selectable by the installer using this group of submenus. Once again, the left and right keys will s...

  • Page 33

    Revision 0.07 33 3.3.8.4 alarm strobe signal a l a r m s i g n a l s s t r o b e : 1 c o n t i n . Figure 3-55 strobe alarm signal this display example shows that the strobe will signal an alarm condition with a continuous signal. The signal definitions are: – 1 continuous (default) – 2 intermittent...

  • Page 34

    Revision 0.07 34 s t r o b e : 5 o f f figure 3-59 strobe warning signal this display example shows that the strobe will not signal a warning condition. The signal definitions are: – 1 continuous – 2 intermittent, one second on at two second intervals – 3 double tap, two beeps at 5 second intervals ...

  • Page 35

    Revision 0.07 35 3.3.8.12 trouble strobe signal t r o u b l e s i g n a l s s t r o b e : 5 o f f figure 3-63 strobe trouble signal this display example shows that the strobe will not signal a trouble condition. The signal definitions are: – 1 continuous – 2 intermittent, one second on at two second...

  • Page 36: 4  Troubleshooting

    Revision 0.07 36 4 troubleshooting the dvp-120 is extensively tested at the factory to ensure reliable operation. Most problems can be traced to the set-up of configurable features and modes, system wiring or trouble with the sensors. 4.1 system status light flashing the system status light (section...

  • Page 37: Warning

    Revision 0.07 37 4.3 no power warning 120/240 vac terminals are located within the dvp-120, presenting a hazard to service technicians. Only qualified technicians should open the dvp-120 case and service the internal circuits. Ensure power is removed from the dvp-120 prior to servicing the unit. The...