Megger MFT1700 series Quick Start Manual

Other manuals for MFT1700 series: User Manual
Manual is about: Multifunction testers

Summary of MFT1700 series

  • Page 1

    M mft1700/1800 series multifunction tester quick start guide g safety warnings n safety warnings and precautions must be read and understood before the instrument is used. They must be observed during use. N the circuit under test must be switched off, de-energised and isolated before test connectio...

  • Page 2

    N the instrument should not be used if any part of it is damaged. N test leads, probes and crocodile clips must be in good order, clean and with no broken or cracked insulation. N all test leads supplied with the instrument form part of the measuring circuit of the instrument. They must not be modif...

  • Page 3

    Note the instrument must only be used by suitably trained and competent persons users of this equipment and/or their employers are reminded that health and safety legislation requires them to carry out valid risk assessments of all electrical work so as to identify potential sources of electrical da...

  • Page 4

    Terminal panel voltage/frequency/phase rotation [v, hz, rot] measurement: automatic. Large display shows volts ac, small display shows frequency phase rotation: l1 : l2 : l3 = normal l1 : l3 : l2 = reversed warnings: maximum voltage range 600 vac setup options: none continuity measurement [Ω] - meas...

  • Page 5

    Functions: buzzer on/off buzzer threshold: buzzer sounds below 2 Ω. To change limit go to setup warnings: live circuit test inhibit at 3 v setup options: test current: 200 ma / 15 ma auto reverse testing: on/off continuity buzzer threshold: 0.5 Ω, 1 Ω, 2 Ω, 5 Ω, 10 Ω, 20 Ω, 50 Ω and 100 Ω insulation...

  • Page 6

    Note: third lead can be connected. The third lead will enable reverse polarity detection. Measurement: press and release test button. Supply: l-e = 90 vac - 280 vac l1(in) -l2(out) = 90 vac – 480 vac (phase - phase) functions: 0º and 180º (quick press), type ac, a, s, b selection (press and hold) rc...

  • Page 7

    Loop impedance testing [ma] – measures circuit loop impedance note: third lead can be connected. The third lead will enable reverse polarity detection measurement: press test to start. L-e tests start automatically. Supply: l-e = 50 vac - 280 vac l-l, l-n = 50 vac – 480 vac zmax: stores maximum loop...

  • Page 8

    Loop impedance r1+r2 testing [ma] measurement: press test to start. Warnings: over voltage setup options: none megger limited archcliffe road dover t + 44 (0) 1304 502100 kent, ct17 9en f + 44 (0) 1304 207342 england e uksales@megger.Com megger 4271 bronze way t +1 (800) 723-2861 (u.S.A. Only) dalla...