Modine Manufacturing BDP Product & Performance Data

Manual is about: power vented gas-fired unit heaters

Summary of BDP

  • Page 1

    6-189.5 6-189.5 july, 2009 gas-fired power vented unit heaters propeller & blower models model hd model hdb model pdp model bdp.

  • Page 2: Warning

    6-189.5 2 table of contents table of contents page design features - all models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 design features - model hd/hdb . . . . . . . . . . . . . . ....

  • Page 3

    6-189.5 3 design features - all units feature model hd hdb pdp bdp cabinet and air mover aluminized steel cabinet (gauge indicated) 22 ga. 22 ga. 20 ga. 20 ga. Low profile casing design • • baked-on polyester powder paint for durability and corrosion resistence • • • • adjustable air-deflector blade...

  • Page 4

    4 6-189.5 design features - models hd/hdb ➀ power exhauster (std) all hd series (low profile) unit heaters are supplied with a round vent pipe connection. ➁ pressure switch (std) an automatic reset vent pressure switch is supplied on all hd series (low profile)unit heaters and is designed to prevent...

  • Page 5

    5 6-189.5 all units include the standard (std) features, and may include the optional (opt) features shown. ➀ gas valve (see table 12.2) a) single stage gas valve - (std) the main gas valve is factory installed on the unit heater gas train. The main gas valve provides the pilot, regulator, main gas,...

  • Page 6

    6 6-189.5 general performance data - models hd & pdp table 6.1 - propeller unit model hd and pdp general performance data ➀ ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (in canada se...

  • Page 7

    7 6-189.5 ➀ ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (in canada see rating plate.) reduction of ratings requires use of a high altitude kit. ➁ data taken at 55°f air temperature ...

  • Page 8

    8 6-189.5 table 8.1 - power code description - hdb models power code unit voltage hdb60 hdb75 hdb100 hdb125 01 115/60/1 1/4 hp 1/3 hp 1/2 hp 1/2 hp blower performance data - model hdb 70 65 60 55 50 45 40 0.00 0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 1235 1323 1425 1543 1684 1852 2058 2315 external s...

  • Page 9

    9 6-189.5 blower performance data - model bdp power code electric power 01 115/60/1 02 230/60/1 04 208/60/3 05 230/460/60/3 07 575/60/3 09 115/60/1 10 230/60/1 12 208/60/3 13 230/460/60/3 15 575/60/3 17 115/60/1 18 230/60/1 20 208/60/3 21 230/460/60/3 23 575/60/3 25 115/60/1 26 230/60/1 28 208/60/3 ...

  • Page 10

    10 6-189.5 0.0 static air pressure 0.1 static air pressure 0.2 static air pressure 0.3 static air pressure temp sheave sheave sheave sheave rise airflow rpm hp drive turns rpm hp drive turns rpm hp drive turns rpm hp drive turns (°f) (cfm) no. Open no. Open no. Open no. Open blower performance data ...

  • Page 11

    11 6-189.5 hp & drive hp & drive to order from this catalog from price list ➃ 1/4 -191 = 1/4 -197 1/3 -191 = 1/3 -197 1/3 -95 = 1/3 -96 1/3 -95 = 1/3 -96 1-1/2 -193 = 1-1/2 -198 1/4 -212 = 1/4 -213 1/3 -212 = 1/3 -213 1/3 -102 = 1/3 -101 1-1/2 -105 = 1-1/2 -180 1/3 -203 = 1/3 -204 1-1/2 -105 = 1-1/2...

  • Page 12

    12 6-189.5 gas control data - all models table 12.1- electrical/control code selection details - all models ➀ unit power code must match supply voltage, control voltage must match unit power. ➁ certain 208v and 230v electrical distribution systems have connections available for supplying 115v servic...

  • Page 13

    13 6-189.5 accessories table 13.1 - field installed accessories table 13.2 - field installed thermostats single-stage thermostats two-stage thermostats feature model hd hdb pdp bdp cabinet and air mover vertical deflector blades - allows directional discharge air control in the left and right direct...

  • Page 14

    14 6-189.5 performance data - hoods for propeller models table 14.1 - downtown hood general performance data for hd/pdp (feet) h s s figure 14.1 - 30°, 60°, and 90° downward deflector hoods mounting height x y y z z x 60 downturn 30 downturn note: x = feet from heater to start of floor coverage y = ...

  • Page 15

    15 6-189.5 performance data - velocity generating nozzles table 15.1 - blower unit model bdp velocity generating nozzle performance data (feet) ➁ s s h s t t h s s 40° splitter nozzle 90° vertical nozzle 5-way nozzles max. Mounting ht. (ft.) h 26 25 27 29 31 32 32 heat throw (ft.) t 79 76 81 86 94 9...

  • Page 16

    16 6-189.5 unit selection selection procedure in order to properly select a unit heater it is necessary to have the following basic information. 1. Heating output capacity model size output is to be matched against the heat loss to be replaced. 2. External static pressure (blower units only) the ext...

  • Page 17

    17 6-189.5 selection example conditions (blower unit) in the following example, select a unit heater to meet the following conditions: 1. Heating output capacity = 156,000 btu/hr per design engineer 2. External static pressure = 0.2. 3. Internal static pressure = 0.0. No static producing accessories...

  • Page 18

    18 6-189.5 dimensional data - model hd/hdb propeller units - model hd figure 18.1 - dimensional drawings - model hd figure 18.2 - dimensional drawings - model hdb blower units - model hdb table 18.1 - dimensions (inches) - hd table 18.3 - clearance to combustibles, model hd/hdb rear view access view...

  • Page 19

    19 6-189.5 dimensional data - model pdp propeller units - model pdp dimension model number symbol pdp 150 pdp 175 pdp 200 pdp 250 pdp 300 pdp 350 pdp 400 a 21 23-1/2 25-5/8 25-5/8 28-5/8 33-5/8 40 b 35-1/4 35-1/4 40-1/4 40-1/4 40-1/4 40-1/4 40-1/4 c 22 22 25 25 25 25 25 d 18-9/16 21-1/16 23-3/16 23-...

  • Page 20

    20 6-189.5 dimensional data - model bdp w x f c cc g dd j m (approx.) l (min. Distance to wall) n s o k ee 5 cc dd j p q x v r x t / 8 " 7 4 / 16 " 9 5 / 4 " 3 / 16 " 9 filter rack (optional) blower enclosure (optional) a h d (opening) bb e aa b k l (min. Distance to wall) g ➀ for some models, this ...

  • Page 21

    21 6-189.5 specifications - all models general a. Standards all unit(s) shall include: a.1. C.S.A. (canadian standards association) design certification for use in both the us and canada to the ansi z83.8 - latest revision, standard for “gas unit heater and gas-fired duct furnaces” for safe operatio...

  • Page 22

    22 6-189.5 specifications - all models g.4.B. The motor shall be rated for: (a) 115v/60hz/1ph (b) 208v/60hz/1ph (pdp model) (c) 230v/60hz/1ph (pdp model) g.5. Blower models shall meet the following requirements. G.5.A. The motor type shall be single-speed, totally enclosed (te) (odp on units 75mbh a...

  • Page 23

    23 6-189.5 model nomenclature figure 23.1 - model number designations mbh input 100 - 100,000 btu/hr input 200 - 200,000 btu/hr input 250 - 250,000 btu/hr input etc. (refer to pages 6 & 7) heat exchanger type a - aluminized s - stainless steel ignition type e - unit equipped with intermittent pilot ...