Modine Manufacturing BDP Product & Performance Data - page 7
7
6-189.5
➀
Ratings shown are for elevations up to 2,000 ft. For elevations above 2,000 feet, ratings should be reduced at the rate of 4% for each 1,000 feet above sea level. (In Canada see rating plate.)
Reduction of ratings requires use of a high altitude kit.
➁
Data taken at 55°F air temperature rise. At 65°F ambient and unit fired at full-rated input. Mounting height as measured from bottom of unit, and without deflector hoods.
➂
All motors used are produced, rated and tested by reputable manufacturers in accordance with NEMA standards and carry the standard warranty of both the motor manufacturer and Modine.
All motors are 115V single phase motors with built-in thermal overload protection. Model sizes 60-75 are open motors, sizes 100-400 are totally enclosed.
Table 7.3 - Blower Unit Model BDP Operating Electrical Data
Voltage
115/60/1
230/60/1
208/60/3
230/60/3
460/60/3
575/60/3
Motor Motor Total Total Motor Total Total Motor Total
Total Motor Total Total Motor Total Total Motor Total Total
HP
Rpm Amps Amps Watts Amps Amps Watts Amps Amps Watts Amps Amps Watts Amps Amps Watts Amps Amps Watts
1/4
1725
3.7
6.0
696
2.7
4.0
914
1.3
2.6
539
1.2
2.5
569
0.7
1.9
592
0.5
1.8
569
1/3
1725
5.0
7.3
845
2.5
3.8
868
1.2
2.5
518
1.2
2.5
569
0.6
1.9
569
0.8
2.1
753
1/2
1725
8.0
10.3 1190
4.0
5.3
1213
2.2
3.5
726
2.1
3.4
776
1.1
2.4
799
0.9
2.2
811
3/4
1725
11.0
13.3 1535
5.4
6.7
1535
2.8
4.1
851
2.7
4.0
914
1.4
2.6
937
1.1
2.3
926
1
1725
13.4
15.7 1811
6.7
8.0
1834
3.6
4.9
1018
3.5
4.8
1098
1.8
3.0
1121
1.5
2.6
1127
1-1/2
1725
15.2
17.5 2018
7.6
8.9
2041
4.8
6.1
1267
4.8
6.1
1397
2.4
3.6
1397
1.9
3.1
1386
2
1725
---
---
---
---
---
---
6.8
8.1
1683
6.0
7.3
1673
3.0
4.3
1673
2.3
3.5
1616
3
1725
---
---
---
---
---
---
9.9
11.2
2328
8.2
9.5
2179
4.1
5.4
2179
3.4
4.6
2248
5
1725
---
---
---
---
---
---
15.2
16.5
3430
13.0 14.3 3283
6.5
7.8
3283
5.3
6.5
3341
gENERAL PERFORMANCE DATA - MODELS HDB & BDP
Table 7.1 - Blower Unit Model HDB and BDP general Performance Data
Model HDB Sizes
Model BDP Sizes
60
75
100
125
150
175
200
250
300
350
400
Btu/Hr Input
➀
60,000 75,000 100,000 125,000 150,000 175,000 200,000 250,000 300,000 350,000 400,000
Btu/Hr Ouput
➀
48,000 60,000
80,000
100,000 120,000 140,000 160,000 200,000 240,000 280,000 320,000
Entering Airflow
Range (CFM)
635-
1111
794-
1389
1140-
2116
1235-
2058
1587-
2778
1852-
3241
2116-
3704
2646-
4630
3175-
5556
3704-
6481
4233-
6584
Outlet Velocity (FPM)
437-726 546-908 443-781 488-773
869
892
773
966
1026
1037
1008
Air Temp. Rise (°F)
40-70 40-70 35-65
45-75
40-70
40-70
40-70
40-70
40-70
40-70
40-70
Max. Mounting
Height (Ft.)
➁
7-13
7-16
8-19
8-17
14
15
13
16
18
19
19
Heat Throw (Ft.) @
Max Mtg Ht
➁
20-45 24-57 27-68
27-59
49
52
47
58
64
67
68
Motor Type
➂
P.S.C.
P.S.C.
P.S.C.
P.S.C.
T.E
T.E
T.E
T.E
T.E
T.E
T.E
Motor HP
1/4
1/3
1/2
1/2
Motor RPM
Max
1100
Max
1100
Max 1100 Max 1100
1725
1725
1725
1725
1725
1725
1725
See Table 9.1
Table 7.2 - Blower Unit Model HDB Operating Electrical Data
Supply
Voltage
Power Code
Model HDB Sizes
Model BDP Sizes
60
75
100
125
150
175
200
250
300
350
400
115V
01 (115V)
Motor Amps
5.4
7.1
9.5
9.5
See Table 7.3
1 Phase
Total Amps
6.4
8.1
11.5
11.5
Transformer kVA
n/a
n/a
n/a
n/a
208V
1 Phase
01 (115V) with
Transformer
Transformer kVA
1.0
1.0
1.5
1.5
208V Total Amps
3.54
4.48
6.36
6.36
230V
1 Phase
01 (115V) with
Transformer
Transformer kVA
1.0
1.0
1.5
1.5
230V Total Amps
3.20
4.05
5.75
5.75
208V
01 (115V) with
Transformer
Transformer kVA
1.0
1.0
1.5
1.5
3 Phase
208V Total Amps
3.54
4.48
6.36
6.36
230V
01 (115V) with
Transformer
Transformer kVA
1.0
1.0
1.5
1.5
3 Phase
230V Total Amps
3.20
4.05
5.75
5.75
460V
01 (115V) with
Transformer
Transformer kVA
1.0
1.0
1.5
1.5
3 Phase
460V Total Amps
1.60
2.03
2.88
2.88
575V
01 (115V) with
Transformer
Transformer kVA
1.0
1.0
1.5
1.5
3 Phase
575V Total Amps
1.28
1.62
2.30
2.30
115V
1 Phase
208V
3 Phase
230V
3 Phase
460V
3 Phase
575V
3 Phase