Modine Manufacturing Model FC series Installation And Service Manual - page 7
7
AIR11-500.6
7
MECHANICAL SPECIFICATIONS / UNIT
Table 7.1
1 & 2 Row Unit Data Specifications
Unit
Size
002 003 004 006 008 010 012 014
Coil
Standard – 1 Row Face Area, Ft.
2
1.0 1.3 1.6 2.3 3.4 3.4 4.6 4.6
High Capacity – 2 Row Face Area, Ft.
2
1.1 1.5 1.8 2.7 3.6 3.6 4.8 4.8
Standard Coil Connections . . . . . . . . . . .
3/4" NPT
3/4" NPT
3/4" NPT
3/4" NPT
1" NPT
1" NPT
1" NPT
1" NPT
High Capacity Coil Connections . . . . . . .
5/8" ID
5/8" ID
5/8" ID
5/8" ID
1" NPT
1" NPT
1" NPT
1" NPT
Sweat Sweat Sweat Sweat
Blowers (Direct Drive)
No./Dia. x Width (Inches). . . . . . . . . . . . .
1 / 5-1/4 x 7 1 / 5-3/4 x 7 2 / 5-1/4 x 7 2 / 5-3/4 x 7 3 / 5-3/4 x 7 3 / 5-3/4 x 7 4 / 5-3/4 x 7 4 / 5-3/4 x 7
High Speed (Rpm) . . . . . . . . . . . . . . . . . .
1050 1050 1050 1050 1050 1050 1050 1050
Low Speed (Rpm)
➀
. . . . . . . . . . . . . . . .
625 625 625 625 625 625 625 625
High CFM. . . . . . . . . . . . . . . . . . . . . . . . .
250 330 450 620 840 1050 1240 1430
Low CFM
➀
. . . . . . . . . . . . . . . . . . . . . . .
150 195 270 370 545 685 805 930
➁ ➂
Motor HP. . . . . . . . . . . . . . . . . . . . . . . . .
1/30
1/30
1/20
1/20
1/30 1/20
1/30 1/20
1/20
1/20
Volts/Phase/Hertz. . . . . . . . . . . . . . . . . . . 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60
Amps, Standard Shaded Pole Motors . . .
1.7 1.7 2.1 2.1 3.8 3.8 4.2 4.2
Amps, PSC Motor . . . . . . . . . . . . . . . . . . .7 .7 1.05 1.05 1.75 1.75 2.1 2.1
Amps, High Static Motor . . . . . . . . . . . . .
4.4 4.4 4.4 4.4 8.8 8.8 8.8 8.8
Unit Weight – Lbs.
Model FC . . . . . . . . . . . . . . . . . . . . . . . . .
85 90 105 125 185 185 210 210
Model WCC . . . . . . . . . . . . . . . . . . . . . . . 90 100 115 135 205 205 240 240
▲
①
Standard solid state speed control offers infinite speed control between high and low speed/CFM.
②
Sizes 002-006 have one motor. Sizes 008-014 have two motors.
➂
High Static Motors are .4 HP for sizes 002-006 and .8 HP for sizes 008-014.
Table 7.2
3 & 4 Row Unit Data Specifications
Unit
Size
002 003 004 006 008 010 012 014
Coil
High Capacity - 3 Row Face Area, Ft. 2
0.9
1.2
1.5
2.3
3.6
3.6
4.6
4.6
High Capacity - 4 Row Face Area, Ft.2
0.9
1.2
1.5
2.3
3.6
3.6
4.6
4.6
High Capacity Coil Connections . . . . . . .
3/4" NPT
3/4" NPT
3/4" NPT
3/4" NPT
1" NPT
1" NPT
1" NPT
1" NPT
Blowers (Direct Drive)
No./Dia. x Width (Inches). . . . . . . . . . . . .
1 / 5-1/4 x 7 1 / 5-3/4 x 7 2 / 5-1/4 x 7 2 / 5-3/4 x 7 3 / 5-3/4 x 7 3 / 5-3/4 x 7 4 / 5-3/4 x 7 4 / 5-3/4 x 7
High Speed (Rpm) . . . . . . . . . . . . . . . . . .
1625 1625 1625 1625 1625 1625 1625 1625
Low Speed (Rpm)
➀
. . . . . . . . . . . . . . . .
1370 1370 1370 1370 1370 1370 1370 1370
High CFM . . . . . . . . . . . . . . . . . . . . . . . . .
260 340 470 650 880 1100 1300 1500
Low CFM
➀
. . . . . . . . . . . . . . . . . . . . . . .
200 260 360 500 730 920 1080
1250
Motor HP. . . . . . . . . . . . . . . . . . . . . . . . .
0.4 0.4 0.4 0.4 0.8 0.8 0.8 0.8
Volts/Phase/Hertz. . . . . . . . . . . . . . . . . . . 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60 115/1/60
Amps, High Static Motor . . . . . . . . . . . . .
4.4
4.4
4.4
4.4
8.8
8.8
8.8
8.8
Shipping Weight – Lbs.
Model FC . . . . . . . . . . . . . . . . . . . . . . . . .
85 90 105 125 185 185 210 210
Model WCC . . . . . . . . . . . . . . . . . . . . . . . 90 100 115 135 205 205 240 240
▲
Dampers (optional equipment)
When specified, the unit shall be equipped with a 25% or 100%
galvanized steel fresh air blade damper. Model FC, floor units
only.
When dampers are specified, indicate one of the following:
1. These dampers shall be controlled from the end pocket
with a manual control assembly that indicates the open and
closed positions.
2. The damper shall be controlled by an electric, spring-return
type motor, which will be energized when the blower motor
is turned on thus moving the damper to the 25% or 100%
position. It will be de-energized and close the damper when
the blower motor is off.
Motors, Blowers and Drives
Blowers shall be of the centrifugal, forward curved type, to
provide even air distribution and low sound level.
All units shall have shaded pole (permanent split capacitor
available when specified as optional equipment) direct-drive
motors. The motor and blower assembly shall be capable
of being easily removed from the unit. Motors are built for
continuous duty to NEMA standards.
Grilles (optional equipment)
When specified, aluminum linear bar inlet and/or outlet grilles
shall be provided.
When specified, outlet grilles may have two-way deflection louvers.
Filters
All air, both fresh and return, shall be filtered by a cleanable
expanded aluminum filter.