AIR11-500.6
Standard
PSC
High Static
Unit Motor
Motor
Motor
Motor
size
qty.
HP
Total Amps HP Total Amps HP Total Amps
002 & 003
1
1/30
1.7
1/30
0.70
0.4
4.40
004 & 006
1
1/20
2.1
1/20
1.05
0.4
4.40
008 & 010
1 1/30
1/30
0.8
1
1/20
1/20
0.8
012 & 014
2
1/20
4.2
1/20
2.10
0.8
8.80
Table 9.4 - Motor Ratings (115 volts/60hz/1Ø)
3.8
1.75
8.80
DIMENSIONAL / MOTOR DATA
Table 9.3 - Coil Connection Dimensions
(inches)
Unit Size
K L M N
002 thru 006
22-1/2 7-3/8 15-1/4 2-3/8
008 thru 014
25-5/8 9-1/4 18 1-5/8
➀
Filters are permanent/cleanable.
Approx.
A B C F G J Unit
Unit
Weight
Size
lbs.
002
38-3/4 25 9-3/4 5-1/8 15-5/8 –
90
003
43-3/4 25 9-3/4 5-1/8 19-5/8 –
100
004
48-3/4 25 9-3/4 5-1/8 27-5/8 –
115
006
61-3/4 25 9-3/4 5-1/8 39-5/8 –
135
008
71-3/4 28 12 5-1/8 47-5/8 9-3/4 205
010
71-3/4 28 12 5-7/8 47-5/8 9-3/4 205
012
83-3/4 28 12 5-1/8 59-5/8 9-3/4 240
014
83-3/4 28 12 5-7/8 59-5/8 9-3/4 240
Table 9.1 - Cabinet Dimensions (inches)
Table 9.2 - Filter Dimensions (inches)
➀
Model Size
Filter Size
002
8-1/2 x 20-3/4 x 1/2
003
8-1/2 x 25-3/4 x 1/2
004
8-1/2 x 30-3/4 x 1/2
006
8-1/2 x 43-3/4 x 1/2
008 & 010
10-3/4 x 49-3/4 x 1/2
012 & 014
10-3/4 x 61-3/4 x 1/2
Figure 9.1 - Wall or Ceiling Model WCC, Sizes 002-014 Steam/Hot Water Cabinet Unit Heaters
➀
EXPOSED OR RECESSED WALL/CEILING MOUNTED
COIL CONNECTIONS
SIZES 002-006:
3
/
4
" NPT FOR STANDARD COIL
5
/
8
" I.D. SWEAT FOR TWO ROW COIL
SIZES 008-014: 1" NPT, ONE OR TWO ROW COIL
C
F
G
K
M
Optional
Inlet
L
N
Standard
Outlet
Optional
Outlet
1
/
2
"
3"
11"
A
SIZES
002-006
4
5
/
8
" X
3
/
8
"
SLOTTED
MOUNTING
HOLES IN
REAR
FLANGE
B
4
1
/
4
"
4
1
/
4
"
9
3
/
4
"
J
7
/
16
" MOUNTING HOLES
MODEL SIZES 008-014 ONLY
2
3
/
4
"
Standard
Inlet
NOTE: Left hand piping is standard, right hand piping available when specified.
Bottoms of end compartments are open for piping and electrical access.
(Size 008-014 only)
SPEED
CONTROL
AND J-BOX
SEE PAGE 10, COIL CONNECTION DIMENSIONS