Moeller SmartWire Startup Manual - page 25
SmartWire Startup Guide V1.02
abyExtendedInfo
Meaning
0
Profibus DP slave address
1..4
No
meaning
5
Length bytes of the device diagnostics *
6, 7
No meaning
8
Byte 1 Profibus standard diagnostics (STATUS 1)
bit0: Device not responding
bit1: Slave not ready
bit2: Divergent configuration
bit3: Extended diagnostics data present
bit4: Unknown command
bit5: Invalid response
bit6: Incomplete parametric programming
bit7: Parameterization by another master
9
Byte 2 Profibus standard diagnostics (STATUS 2)
bit0: Ready for new startup sequence
bit1: No parameterization
bit2: 1
bit3: Watchdog activated
bit4: FREEZE command active
bit5: SYNC command active
bit6: Reserved
bit7: Slave not configured
10
Byte 3 Profibus standard diagnostics
Æ No meaning
11
Byte 4 Profibus standard diagnostics
Æ Profibus DP master address
Profibus DP standard diagnostics data block (=
6 bytes)
12, 13
Byte 5,6 Profibus standard diagnostics
Æ Profibus DP slave ID number
For SWIRE-GW-DP: 77
dec
/ 18
dec
= 4D12
hex
14
Length byte of device-specific data **
Æ for SWIRE-GW-DP with max. 16 SWIRE slaves = 8
15
Status type (130)
Æ for diagnostics message in HW configurator (PC)
16 Slot
number
(0)
Æ Diagnostics refers to SWIRE-GW-DP
17
Status specifier (0)
Æ No other information present
18
Status SmartWire module 1-4
bit0/1: SmartWire module 1
bit2/3: SmartWire module 2
bit4/5: SmartWire module 3
bit6/7: SmartWire module 4
19
Status SmartWire module 5-8
bit0/1: SmartWire module 5
bit2/3: SmartWire module 6
bit4/5: SmartWire module 7
bit6/7: SmartWire module 8
20
Status SmartWire module 9-12
bit0/1: SmartWire module 9
bit2/3: SmartWire module 10
bit4/5: SmartWire module 11
bit6/7: SmartWire module 12
Profibus DP device diagnostics (5 – 8 bytes)
21
Status SmartWire module 13-16
bit0/1: SmartWire module 13
bit2/3: SmartWire module 14
bit4/5: SmartWire module 15
bit6/7: SmartWire module 16
Bit assignment:
00 = everything
ok
* Length bytes of the device diagnostics: DP standard diagnostics (6 bytes) + Length bytes of the device diagnostics
** Depends on the connected SWIRE slaves
© by Moeller GmbH
25 / 42