N-Tron 102MC User Manual & Installation Manual

Other manuals for 102MC: User Manual & Installation Manual
Manual is about: Media Converter & Industrial Ethernet Switches

Summary of 102MC

  • Page 1

    (revised 2011-04-15) 1 100 series media converter & industrial ethernet switches user manual & installation guide.

  • Page 2

    (revised 2011-04-15) 2 industrial media converter and ethernet switch installation guide 102mc-xx 105tx 106fx2 110fx2-xx-yy 102mce-xx-yy 105tx-sl 108tx 111fx3-xx-yy 104tx 105fx-xx 108tx-hv 112fx4-xx-yy 105fxe-xx-yy 114fx6-xx-yy 116tx where: xx=st or sc and yy= 15, 40 or 80

  • Page 3

    (revised 2011-04-15) 3 copyright, © n-tron corp., 2011 820 s. University blvd., suite 4e mobile, al usa 36609 all rights reserved. Reproduction, adaptation, or translation without prior written permission from n-tron corp. Is prohibited, except as allowed under copyright laws. Ethernet is a register...

  • Page 4

    (revised 2011-04-15) 4 general safety warnings warning: do not operate the equipment in the presence of flammable gasses or fumes. Operating electrical equipment in such an environment constitutes a definite safety hazard. Warning: if the equipment is used in the manner not specified by n-tron corp....

  • Page 5

    (revised 2011-04-15) 5 hazardous location installation requirements 1. This equipment is suitable for use in class i, div 2, groups a, b, c, and d hazardous locations, or unclassified or non-hazardous locations only. 2. Warning: explosion hazard - substitution of any component may impair suitability...

  • Page 6

    (revised 2011-04-15) 6 100 series industrial ethernet switches the 100 series unmanaged industrial ethernet switches support high speed layer 2 switching between ports. This series of switches are housed in a ruggedized aluminum enclosure, and provide category-5 compliant 10/100-baset connections fo...

  • Page 7

    (revised 2011-04-15) 7 package contents please make sure the package contains the following items: 1. 100 series media converter or ethernet switch 2. Instruction sheet contact your carrier if any items are damaged. Unpacking remove all the equipment from the packaging, and store the packaging in a ...

  • Page 8

    (revised 2011-04-15) 8 din-rail mounting install the unit in a standard din rail. Recess the unit to allow at least 2” of horizontal clearance for cat5e cable bend radius. To install the plastic clip units to 35mm industrial din rail, place the top edge of the included mounting bracket on the back o...

  • Page 9: Urmk

    (revised 2011-04-15) 9 urmk 1000-pm most n-tron™ products are designed to be mounted on industry standard 35mm din rail. However, din rail mounting may not be suitable for all applications. Our universal rack mount kit (p/n: urmk) may be used to mount the 100 series enclosures to standard 19" racks,...

  • Page 10

    (revised 2011-03-14) 10 front panel from top to bottom: spd speed led lnk/act link/activity led rj45 ports auto sensing 10/100baset connection green led lights when power is connected note: the top led indicates link/activity (lnk/act), and the lower led indicates speed (spd) status..

  • Page 11

    (revised 2011-03-14) 11 led’s: the table below describes the operating modes: led color description on power is applied. Off power is off. Lnk/act on link established, no activity on cable. Blinking link established, activity on cable off no link activity on cable. Spd on link is 100mbps. Off link i...

  • Page 12

    (revised 2011-03-14) 12 • 110fx2, 111fx3, 112fx4, and 114fx6 power connector (top view) (must be powered by class 2 source only) unscrew & remove the dc voltage input plug from the top header. Install the dc power cables into the plug (observing polarity on unit). Plug the voltage input plug back in...

  • Page 13

    (revised 2011-03-14) 13 all leds will flash on momentarily. Verify the power led stays on (green). Note: either v 1 or v 2 can be connected to power for minimal operation. For redundant power operation, v 1 and v 2 plugs must be connected to separate dc voltage sources. Use wire sizes of 12-28 gauge...

  • Page 14

    (revised 2011-03-14) 14 in the event all cat5e patch cable distances are small (i.E. All ethernet devices are located the same local cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to chassis ground at both ends in systems void of low le...

  • Page 15

    (revised 2011-03-14) 15 connecting the unit for fx/fxe units, remove the dust cap from the fiber optic connectors and connect the fiber optic cables. The tx port (located on the bottom connector) on the fx/fxe models should be connected to the rx port of the far end station. The rx port (located on ...

  • Page 16

    (revised 2011-03-14) 16 fcc statement this product complies with part 15 of the fcc-a rules. Operation is subject to the following conditions: (1) this device may not cause harmful interference (2) this device must accept any interference received, including interference that may cause undesired ope...

  • Page 17

    (revised 2011-03-14) 17 102mc/mce - key specifications physical height: 2.87” (7.28 cm) width: 1.49” (3.78 cm) depth: 3.53” (8.96 cm) weight: 0.5 lbs. (0.22 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) input current: 140ma max. @ 24vdc (steady state) inrush current: 8.5 amp/0.7...

  • Page 18

    (revised 2011-03-14) 18 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: en61000-6-4, en55011 - class a fcc title 47, part 15, subpart b - class a ices-003 – class a ems: en61000-6-2 en61000-4-2 (esd...

  • Page 19

    (revised 2011-03-14) 19 104tx/105tx - key specifications physical height: 2.87” (7.28 cm) width: 1.49” (3.78 cm) depth: 3.53” (8.96 cm) weight: 0.6 lbs. (0.27 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) input current: 215 ma max. @ 24vdc (steady state) inrush current: 7.8 amp/...

  • Page 20

    (revised 2011-03-14) 20 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: en61000-6-4, en55011 - class a fcc title 47, part 15, subpart b - class a ices-003 – class a ems: en61000-6-2 en61000-4-2 (esd...

  • Page 21

    (revised 2011-03-14) 21 105tx-sl - key specifications physical height: 4″ (10.2 cm) width: 1″ (2.6 cm) depth: 3.7″ (9.2 cm) weight: 0.7 lbs. (0.32 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) input current: 215 ma max. @ 24vdc (steady state) inrush current: 3.0 amp/1.0 ms max. ...

  • Page 22

    (revised 2011-03-14) 22 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: ansi c63.4 fcc title 47, part 15, subpart b - class a ices-003 – class a emc: en61000-6-4 – class a (emissions) en55024 (immun...

  • Page 23

    (revised 2011-03-14) 23 106fx/fx2 - key specifications physical height: 3.83” (9.73 cm) width: 1.50” (3.81 cm) depth: 4.80” (12.2 cm) weight: 0.6 lbs. (0.27 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) input current: 270 ma max. @ 24vdc (steady state) inrush current: 8.0 amp/0....

  • Page 24

    (revised 2011-03-14) 24 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: iec61000-6-2, en55011 - class a fcc title 47, part 15, subpart b - class a ices-003 – class a ems: en61000-6-2 en61000-4-2 (es...

  • Page 25

    (revised 2011-03-14) 25 108tx - key specifications physical height: 3.5” (8.89 cm) width: 1.49” (3.78 cm) depth: 3.53” (8.96 cm) weight: 0.7 lbs. (0.31 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) -hv option: 10-60 vdc (regulated) input current: 250 ma max. @ 24vdc (steady stat...

  • Page 26

    (revised 2011-03-14) 26 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. The high voltage model is tÜv approved gs per en 60950-1. Emi: en61000-6-4, en55011 - class a fcc title 47, part 15, subpart b - cl...

  • Page 27

    (revised 2011-03-14) 27 105fx - key specifications physical height: 3.83” (9.72 cm) width: 1.49” (3.78 cm) depth: 3.53” (8.96 cm) weight: 0.6 lbs. (0.27 kg) din rail 35 mm electrical input voltage: 10-30 vdc (regulated) input current: 270ma max. @ 24vdc (steady state) inrush current: 8.0 amp/0.7 ms ...

  • Page 28

    (revised 2011-03-14) 28 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: en 61000-6-4, en 55011 - class a fcc title 47, part 15, subpart b - class a ices-003 – class a ems: en 61000-6-2 iec 61000-4-2...

  • Page 29

    (revised 2011-03-14) 29 110fx2 - key specifications physical height: 4.3” (10.8 cm) width: 2.4” (6.1 cm) depth: 4.6” (11.5 cm) weight: 1 lbs. 5 oz (0.60 kg) din rail 35 mm electrical input voltage: 10-49 vdc (regulated) input current: 355 ma max. @ 24vdc (steady state) environmental surrounding air ...

  • Page 30

    (revised 2011-03-14) 30 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: fcc cfr title 47, part 15, subpart b - class a ices-003 – class a emc: en61000-6-2/4 en61000-4-2 (esd) en61000-4-3 (rs) en6100...

  • Page 31

    (revised 2011-03-14) 31 111fx3 - key specifications physical height: 4.3” (10.8 cm) width: 2.4” (6.1 cm) depth: 4.6” (11.5 cm) weight: 1 lbs. 5 oz (0.60 kg) din rail 35 mm electrical input voltage: 10-49 vdc (regulated) input current: 410 ma max. @ 24vdc (steady state) environmental surrounding air ...

  • Page 32

    (revised 2011-03-14) 32 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: fcc cfr title 47, part 15, subpart b - class a ices-003 – class a emc: en61000-6-2/4 en61000-4-2 (esd) en61000-4-3 (rs) en6100...

  • Page 33

    (revised 2011-03-14) 33 112fx4 - key specifications physical height: 4.3” (10.8 cm) width: 3.1” (7.9 cm) depth: 4.6” (11.5 cm) weight: 1 lbs. 9 oz (0.70 kg) din rail 35 mm electrical input voltage: 10-49 vdc (regulated) input current: 455 ma max. @ 24vdc (steady state) environmental surrounding air ...

  • Page 34

    (revised 2011-03-14) 34 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: fcc cfr title 47, part 15, subpart b - class a ices-003 – class a emc: en61000-6-2/4 en61000-4-2 (esd) en61000-4-3 (rs) en6100...

  • Page 35

    (revised 2011-03-14) 35 114fx6 - key specifications physical height: 4.3” (10.8 cm) width: 3.1” (7.9 cm) depth: 4.6” (11.5 cm) weight: 1 lbs. 10 oz (0.73 kg) din rail 35 mm electrical input voltage: 10-49 vdc (regulated) input current: 545 ma max. @ 24vdc (steady state) environmental surrounding air...

  • Page 36

    (revised 2011-03-14) 36 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: fcc cfr title 47, part 15, subpart b - class a ices-003 – class a emc: en61000-6-2/4 en61000-4-2 (esd) en61000-4-3 (rs) en6100...

  • Page 37

    (revised 2011-03-14) 37 116tx - key specifications physical height: 5.8″ (14.6 cm) width: 2.0″ (5.1 cm) depth: 4.1″ (10.3 cm) weight: 1 lb. 1 oz (.48 kg) din rail 35 mm electrical input voltage: 10-49 vdc (regulated) input current: 300 ma max. @ 24vdc (steady state) environmental surrounding air tem...

  • Page 38

    (revised 2011-03-14) 38 regulatory approvals: safety: suitable for use in class i, division 2, groups a, b, c and d hazardous locations, or nonhazardous locations only. Emi: ansi c63.4 fcc cfr title 47, part 15, subpart b - class a ices-003 – class a emc: en61000-6-4 – class a (emissions) en 55024 (...

  • Page 39

    (revised 2011-03-14) 39 n-tron limited warranty n-tron, corp. Warrants to the end user that this hardware product will be free from defects in workmanship and materials, under normal use and service, for the applicable warranty period from the date of purchase from n-tron or its authorized reseller....