NAPCO RPXP4GT Installation Instructions Manual

Manual is about: Keypad Control Panel/Communicator

Summary of RPXP4GT

  • Page 1

    Xp-400 & rpxp4gt keypad control panel/communicator installation instructions wi1370 1/05 © napco 2005 ®.

  • Page 2

    2 wi1370 xp-400 installation instructions general information the napco express xp-400 control panel provides up to 4 hardwired/wireless zones. Up to four 4-digit user codes can be programmed. Ambush, when selected, uses user 4 code as an ambush code. The xp-400 is wireless ready. When used with a g...

  • Page 3

    3 specifications current & voltage ratings alarm output -------------------------- burg: 12 vdc, 2a (max.) output current limiting -------------- burg: 2.25 a aux power: 750 ma residential burglary (4 hour standby) combined standby current: -------- 350 ma bell output: ---------------------------- 2...

  • Page 4

    4 wi1370 xp-400 installation instructions 4 zone control panel keypad zone doubling resistors (2.2k & 3.9k) operating instructions xp-400 programming instructions xp-400 xp-400 rpxp4gt zdr oi300 wi1371 ordering information listings and approvals ul household burglary warning system control unit stan...

  • Page 5

    5 programming the panel refer to xp-400 programming instructions (wi1371) defaulting the panel 1. Remove power from the panel. 2. Remove all wiring from terminal 15 (pgm) and terminal 3. 3. Connect terminal 15 (pgm) to terminal 3. 4. Apply power to the xp-400 control panel. 5. After a few seconds th...

  • Page 6

    6 wi1370 xp-400 installation instructions installation mounting the panel mount the panel close to an unswitched ac source, a cold-water pipe ground, and a telephone line connection. Mounting the keypad a keypad should be located near an exit/entry door. To remove the keypad from the backplate, inse...

  • Page 7

    7 pgm wiring the pgm is a switched negative output that is activated depending on the programming option (s) that have been selected [08], [23] - [25]. Connect the device controlled by the pgm between +pwr and the pgm terminal (maximum load of 50 ma). Keypad operation keypad zone leds indicate zone ...

  • Page 8

    8 wi1370 xp-400 installation instructions arming/disarming with a keyfob the system can be armed by pressing the k key, and disarmed by pressing the l key on the keyfob. Zones programmed as exit/entry follower zones can be bypassed when the m or n keys on the keyfob have been programmed for interior...

  • Page 9

    9 full setting the system with automatic bypassing - home/away with delay zones from the keypad press c b to return protection to home/away with delay zones that have been automatically bypassed. Three minutes are allowed to walk through exit/ entry and exit/entry follower zones . Using a keyfob (ge...

  • Page 10

    10 wi1370 xp-400 installation instructions while in user program mode the w armed, x ready and h system trouble leds will continue to flash, follow the example below to program a user 2’s code to 1923. User mode programming example: 1.Press 2 , zone 2 led will flash 2.Enter 1 9 2 3 , zone 2 led will...

  • Page 11

    11 dealer commands a 6 dow nload (pr ogr ammin g required) establish a connection between the pcd phone line and the control panel phone line. When ready, tell the installer to arm, then disarm. Then enter a6 in order to establish a connection. Phone connection to installer will go "dead" as downloa...

  • Page 12

    12 wi1370 xp-400 installation instructions to eliminate this fixed 20-second entry delay, also program zones as exit/entry follower zones [02]. To return protection to zones of this type, press cb from the keypad or m or n from a keyfob. Program the keyfob aux 1 or aux 2 button for full set [81-7]. ...

  • Page 13

    13 [08]pgm output enables the pgm output on a zone trip for each zone selected. The pgm output will remain on until reset. System times [10]exit delay the delay time which permits exit through an exit/entry zone [00] after the system is armed, allows a user to leave the premises without setting off ...

  • Page 14

    14 wi1370 xp-400 installation instructions [21]keypad features 2 (1) audible panic - keypad panic will not turn the bell on unless this option is programmed. (2) exit/entry with urgency - select to give an audible indication of exit and entry times. During the last 10 seconds of entry and exit time,...

  • Page 15

    15 (3) panic - program to activate the pgm on a panic alarm. (4) test timer - program to activate the pgm during a test timer report. [25]programmable output features 3 (1) ac fail - program to activate the pgm on the loss of ac. (15 minute delay) (2) low battery - program to activate the pgm on a l...

  • Page 16

    16 wi1370 xp-400 installation instructions pager alarm data is the same as 4/2 format with the exception that the 2 digit report code is transmitted before the 4 digit subscriber id. [33]receiver options (1) 2300 hz hs/kissoff - select 2300 hz handshake and kissoff. (2) sumcheck - only used for the ...

  • Page 17

    17 [37]system reporting, telco 1 (1) y ac fail report - program to activate an ac fail report (15 minute fixed report delay). (2) low battery report - program to activate a low battery report. (3) *trouble report - program to activate a trouble report. (4) reserved * includes bell cut, receiver fail...

  • Page 18

    18 wi1370 xp-400 installation instructions telephone number 3 programming [50] - [59] programming is the same as for telco 1. Program to split/double report to telco 3. Refer to sections [30] through [39]. Report codes [60]zone report codes report code for zones 1 through 4. 4/2 format - the zone re...

  • Page 19

    19 [66]ambush report code program a 2-digit report code for ambush. To send an ambush report, program a user code for user 4, program report user 4 as ambush [20-4] and select reporting for telco 1 [36-2] and/or telco 3 [56-2]. Enhanced communicator features [67]telephone number 1 ( 1) opening after...

  • Page 20

    20 wi1370 xp-400 installation instructions [71-74] wireless transmitters enter the rf id# and the point number that is to be mapped to the zone. Programming example map point 1 of a window door transmitter with an rf id# of 0012b0:0 to zone 3. 1. Enter dealer mode. 2. Enter b ( beeps) 73 (beeps) 3. ...

  • Page 21

    21 7 full set system program a 7 in the aux 1 and/or aux 2 option to fully set the system when the k and the m or n buttons on the keyfob are pressed, or when the m or n buttons are pressed when the system is armed with exit/entry follower zones or home/away with delay zones that have been bypassed....

  • Page 22

    22 wi1370 xp-400 installation instructions site at the site perform the following three steps: 1. Arm the panel. 2. Disarm the panel. 3. Enter a6 . The panel will now call the download computer running pcpreset. Pcpreset will answer the call, establish a connection, and then download the account tha...

  • Page 23

    23 system troubles use the system trouble chart on the following page to determine the specific system trouble (s). During normal panel operation the h system led has the following two modes of operation: steady 1-7 possible trouble groups, ac is present flashing 1-7 possible trouble groups, ac is n...

  • Page 24

    24 wi1370 xp-400 installation instructions keypad beeps or h system flashes zone led on system trouble condition cause/action 1 beep y led 1 y ac power failure this trouble will occur if ac power is not present. Ensure that the transformer is connected to an unswitched power source. 2 low battery if...

  • Page 25

    25 troubleshooting 1. The bell output drops to about 3 volts in alarm. The battery/bell circuit is protected by a pc board trace which may have burned open by reversal of the battery leads. It is on the back of the pc board just adjacent to the red & black battery leads. Send in for service if this ...

  • Page 26

    26 wi1370 xp-400 installation instructions 8. How do i remove keypad sounder on alarm? The keypad sounder follows the burg output. If you need to remove the keypad sounder, then you must remove the burg output from that zone. 9. Transmitters not responding? Open transmitter case - keypad should go i...

  • Page 27

    27 16 vac 20 va transformer napco trf12 (or equivalent see wi1370). Class 2 transformer. (3) -4 +5 +6 1 2 +3 gem-recv-xp8 + red (+) black e1 e2 rechargeable battery 12 vdc 4ah or 7ah all outputs are current limited warning to prevent risk of electric shock disconnect telephone lines prior to servici...

  • Page 28

    Napco limited warranty napco security systems, inc. (napco) warrants its products to be free from manufacturing defects in materials and workmanship for thirty-six months following the date of manufacture. Napco will, within said period, at its option, repair or replace any product failing to operat...