Summary of NPE-180A

  • Page 1

    To determine the size of a common vent: venting intake and exhaust to di erent locations ● venting intake and exhaust to the same location ● 12" (300mm) min. 12" (300mm) min. 36" (900mm) min. Exhaust intake cap condensate drain w d h exhaust intake condensate drain exhaust intake cap condensate drai...

  • Page 2

    Caution 3. Refer to the common vent table below to determine the maximum allowable lengths for the common vent, based on the total btu/h rating, and the diameter of the vent pipe. Note regardless of the vent size listed in the table, the connection to the common vent must always be as large as the l...