The power inverter will also shut down if the input voltage exceeds its rating. This
protects the inverter against excessive input voltage. The input level will be red
blinking. Although the power inverter incorporates protection against over voltage, it
may still be damaged if the input voltage is allowed to exceed 20V (12V version) or
40V (24V version). or 75V (48V version).
7. Troubleshooting:
7-1. Common Problems:
Television or other communication equipment interference:
Operation of the power inverter can interfere with television reception on some
channels. If this situation occurs, the following steps may help to alleviate the
problem.
• Make sure that the chassis ground lug on the back of the power inverter is solidly
connected to the ground system of your vehicle, boat, shelter, or home.
• Make sure the neutral is bonded to ground ( See page 7)
• Move the television as far away from the power inverter as possible.
• Keep the cables between the battery and the power inverter as short as possible
and twist them together with about 2 to 3 twists per foot. This minimizes radiated
interference from the cables.
Overheating:
Check for clean air intake and an exhaust opening, and check that the fan is
operating.
No Output:
Check the input fuses (remove cover).
Check for correct input voltage