    Engineering, installation and service manual cac series cool cube portable air-cooled spot cooler form eism-cac, 110114 rev 1.

  • Page 2

    Table of conents page general description …................................. 1 product data and specifications............ 2 unit description standard features.................................. 3 applications / operation.......................... 4 electrical............................................

  • Page 3

    Nomenclature c ac 12 1 1 cool cube portable voltage air-cooled single phase nominal capacity 12..........12,000 btu/hr general description the oceanaire cac1211 is a portable air-cooled spot cooler designed for permanent or temporary spot cooling. The entire air conditioning unit has been built in a...

  • Page 4

    2 technical specifications model: cac1211 cooling capacity 12,000 btuh voltage 115 v cooling amps 12.0 a max fuse size 15 a cooling watts 1180 w in rush amps 63 a eer 10.0 compressor type rotary compressor motor 1 hp compressor rla 9.5 a compressor lra 50 a evaporator blower centrifugal evap cfm - h...

  • Page 5

    Standard features cabinet the cac1211 series spot cooler has a cabinet that is constructed of 18 gauge steel with a polyester powder coated finish. The matte black finish compliments any surrounding space, and the cabinet is lined with sound-absorbing insulation for cool, quiet comfort. The cac1211 ...

  • Page 6

    4 applications spot cooler the cac1211 can be used in an open environment to cool specific objects or "spots". Spot cooling is a convenient and economical way to provide air conditioning where cooling the entire space is impractical. Cool air is discharged from the unit and is directed where it is n...

  • Page 7: Not Repaired

    5 service cord the cac1211 is equipped with a ten foot long service cord with lcdi (leakage current detection & interruption) device that serve as a means of electrical protection. Do not use the lcdi as an on/off switch for the unit a damaged lcdi power supply cord must be replaced with a new power...

  • Page 8

    6 condensate reservoir tank the cac1211, has a 2-gallon polyethylene tank for collecting condensate. The tank is located in the lower, front section of the unit. A high water level cut-out switch is used to stop the compressor and condenser fan automatically when the tank's pre-set water level has b...

  • Page 9

    7 installation instructions receiving—inspection: upon receiving your cac1211, inspect the packaging for any damage. All units are shipped on a skid, and packaged in a triple-wall carton for added protection. In shipment, some wear may occur on the packaging. If the packaging is heavily damaged or b...

  • Page 10

    8 caution - when hanging or permanently connecting the cac1211, all applicable local/state/federal building codes must be followed. The structural beam(s) must be capable of properly supporting the weight of the unit (130 lbs.) when installed—unit is to be plumb and level installation—hanging applic...

  • Page 11

    9 installation—permanently connected the cac1211 power cord may be removed and the unit be permanently connected to a power source for applications where desired. Once the cac1211 is installed and se- cured for a stationary installation, the unit can be permanently wired. 1. Remove the left side pan...

  • Page 12

    10 installation—stacking kit, sk-1 two or three coolcube units are required when redundancy is critical, cooling large are- as, or high heat loads. The cac1211 can be stacked on top of each other to produce a capacity of 24,000 or 36,000 btuh, while maintaining the same foot print. To facilitate the...

  • Page 13

    11 installation—rack mounting kit, rck-1 the 19-inch rack kit allows for the cool cube to be installed into any eia-310-d 4-post of 2-post rack enclosure. The kit includes (2) heavy duty rails (4) side mounting brackets and a rear mounting rail. The rails have a vibration dampening foam layer secure...

  • Page 14: Accessories

    Accessories 12.

  • Page 15

    Accessories ceiling panel duct kit, ck-8 a ceiling panel kit is available for discharging the condenser air above a drop ceiling.. The ceiling panel duct kits are furnished with an 8-inch white vinyl coated flexible duct that allows for conven- ient installation. A 2ft x 2ft ceiling duct-panel is in...

  • Page 16

    Accessories condensate pump kit , cpc-1 the condensate pump provides for the automatic removal of condensate water during the cooling pro- cess. The pump is capable of pumping against a 20 foot head, allowing for the routing of the drain line above the drop-ceiling to a nearby drain. The pump is con...

  • Page 17

    Accessories discharge air nozzle kit assembly (cnk-1) the optional discharge nozzle kits are used to direct the conditioned air to a specific target area. By concen- trating the airflow, the nozzles increase the air velocity towards production lines to cool personnel or equip- ment. In server rooms,...

  • Page 18

    16 evaporator return air plenum, cep-6 an evaporator return air plenum is available for installations where it is required to duct air to the inlet of the evaporator. The evaporator return air plenums allow the user to connect round duct (flexible or rigid) to the return air intake to reduce air noi...

  • Page 19: Mode

    17 when power is connected, the controller will display “888” momentarily, and will then go blank. Press the power button, then press the temp select button until the set point is displayed. Adjust the set point to the desired temperature, and the unit will heat/cool as required. The systems control...

  • Page 20

    Controller programming menu 1) make sure the unit has power. 2) pushing the power button, turn the unit “off”. 3) press the following buttons in sequence “s-u-d-s”: 4) the display will begin flashing p1 and a number. If there is no display, repeat the sequence, making sure the unit has power, but is...

  • Page 21

    19 model code settings cac1211 p1 = 80, p2 = 50 cac1211 program parameters notice program parameters are not controller default values. They are oceanaire factory settings display faults lac….Low ac line power aaa…failed air sensor (unit will not run) con… empty condensate bucket—units with a bucket...

  • Page 22

    20 troubleshooting guide the following steps and procedures are recommended for correcting the problems indicated. In the event that the problem can not be corrected, service may be required. Problem: unit does not power up cause: power interruption remedy: check external power supply making sure th...

  • Page 23

    Replacement procedure for parts it is recommended that all oceanaire units be serviced by a licensed technician warning—to avoid injury, disconnect unit power prior to servicing warning—hazardous moving parts do not operate unit with panels removed a. Fan motors 1. Remove cabinet's left-side panel (...

  • Page 24

    22 preventive maintenance arcticaire spot coolers are designed to last a long time and to give maximum performance and reliability with minimum maintenance. To prolong the life of the unit, regular maintenance must be performed as specified below: blower motors the motors on all units have permanent...

  • Page 25

    23.

  • Page 26

    24 wiring diagram when field wiring—-use copper conductors only.

  • Page 27

    Manufacturer’s limited warranty the manufacturer (oceanaire, inc.) warrants to the original owner that the product will be free from defects in material or workmanship for a period not to exceed one (1) year from date of installation. If upon examination by the manufacturer the product is shown to h...

  • Page 28: Useful Information

    Useful information model: serial number: date purchased: installed by: date installed: for technical support, or to locate a distributor for service parts, contact oceanaire at (847) 583-0311 or 1-866-getaire (438-2473). Please indicate the model number and serial number of the unit to assure proper...