Oilon GT 28 Operation Manual - page 17
GT02 1408 EN
15 (24)
a. Press the
OK
button to access the menu system.
b. Press the
Information (i)
button for 5 seconds, select
Commissioning
user
level and press
OK
button.
3. Take the heating circuit into use.
a. Select
Configuration
menu and press
OK
button.
b. Select free heating circuit (
5710 Heating circuit 1
or
5715 Heating circuit 2
) to
be added and press the
OK
button.
c. Change the value to
On
and press the
OK
button.
d. Select operating line
6200 Save sensors
, give value
Yes
and press
OK
button.
4. Configure the heating curve and flow temperatures for the heating circuit, see
chapter
Configuring heating curve
.
2.14. Saving new default settings
If you experience an extended power failure, all settings made will be lost and the
heat pump reverts back to its default factory settings. If you want to keep all settings in
memory, you can save them as new default settings.
If you save all current settings as new default settings, the
original factory settings that they replace will be permanently
overwritten.
1. Press the
OK
button to access the menu system.
2. Select
Configuration
and press the
OK
button.
3. Select operating line
6204: Save parameters
and press the
OK
button.
4. Change the value to
Yes
and press the
OK
button.
2.15. Adjusting room temperature with remote controller
Remote controller is an optional extra, these instructions applies only if remote
controller is part of the heat pump delivery.
1. Turn adjusting wheel to increase or decrease comfort setpoint setting.
2. Confirm setting by pressing
Operating mode
-button.
3. For reduced setpoint, press
OK
-button. Select program page
Heating circuit
and
change
Reduced setpoint
setting.
After changing room temperature setting, wait at least 2 hours
for temperature to adapt.
2.16. Operating lines
The following tables present the most commonly used operating lines in the control
system.