Offsets
30° or 45°
ELBOWS
The chimney for the FP16 can be installed with a maximum
of four 45° elbows(in Canada) and four 30° elbows(in
U.S.A.) as shown in Fig. #10.
Installation:
1. NOTE: Install the fi rst elbow and turn it in the required
direction.
2. Install the necessary chimney lengths to achieve the
required offset. Lock the chimney lengths together
according to the chimney manufacturer’s instructions.
If the offset length is made of two (2) chimney lengths
or more, many chimney manufacturers may require that
you use an offset or roof support halfway up the offset. If
penetrating a wall, install a wall radiation shield supplied
by the chimney manufacturer and install according to the
manufacturer's instructions.
3. Use another elbow to turn the chimney vertically and
secure the elbow.
4. Use a plumb bob to line up the centre of the hole with the
center of the fl ue collar on the fi replace. Cut a hole for the
chimney in the ceiling/fl oor. Frame the hole as described
on page 15.
5. Install a fi restop following the chimney manufacturer's
directions.
6. Follow the chimney manufacturer's guidelines for
supporting the offsets. Reminder - The chimney must be
supported after the fi rst 20'(6.1m).
FIG. #10
6’ (1.83m)
15’ (4.6m)
18” (457mm)
Minimum width of floor protection from side of door opening(in U.S.A.) and
from side of unit(in Canada).
Fireplace Clearances and Dimensions
35’ (10.7m)
Recommended maximum chimney height (at sea level) from top of fireplace
to rain cap.
Minimum distance of adjacent wall to side of fireplace door.
Distance of combustible material from side, back standoffs and framing kit.
Ceiling clearance: from the base of the fireplace to the
ceiling.
Minimum chimney height: minimum total chimney height from fireplace
bottom to below the chimney rain cap.
Maximum unsupported chimney height.
Minimum depth of non-combustible ember protector: from the front of the
fireplace.
Minimum distance to side facing from fireplace door opening.
12” (305mm)
15” (381mm)
20’ (6.1m)
NOTE: IT IS REQUIRED THAT ALL
CHIMNEY SYSTEM CONNECTIONS BE
SECURED WITH (3)-#8 X ½"(12 MM)
METAL SCREWS.